Guide specifications

Air-Cooled, Split-System

Heat Pump

38YCG

1-1/2 To 5 Tons Nominal

GENERAL

System Description

Outdoor-mounted, air-cooled, split-system heat pump unit 

suitable for ground or rooftop installation. Unit consists of a 
hermetic compressor, an air-cooled coil, propeller-type 
condenser fan, and a control box. Unit will discharge supply 
air upward as shown on contract drawings. Unit will be used 
in a refrigeration circuit to match up to a packaged fan coil or 
coil unit.

Quality Assurance

Unit will be rated in accordance with the latest edition of 

ARI Standard 240.

Unit will be certified for capacity and efficiency, and listed 

in the latest ARI directory.

Unit construction will comply with latest edition of 

ANSI/ASHRAE and with NEC.

Unit will be constructed in accordance with UL standards 

and will carry the UL label of approval. Unit will have c-UL 
approval.

Unit cabinet will be capable of withstanding Federal Test 

Method Standard No. 141 (Method 6061) 500-hr salt spray 
test.

Air-cooled condenser coils will be leak tested at 150 psig 

and pressure tested at 300 psig.

Delivery, Storage, and Handling

Unit will be shipped as single package only and is stored 

and handled per unit manufacturer’s recommendations.

Warranty (for inclusion by specifying engineer)

U.S. and Canada only.

PRODUCTS

Equipment

Factory-assembled, single piece, air-cooled heat pump unit. 

Contained within the unit enclosure will be all factory wiring, 
piping, controls, compressor, refrigerant charge (R-22), and 
special features required prior to field start-up.
Unit Cabinet

Unit cabinet will be constructed of galvanized steel, 

bonderized, and coated with a powder coat paint.

Fans

Condenser fan will be direct-drive propeller type, 

discharging air upward.

Condenser fan motors will be totally enclosed, 1-phase type 

with class B insulation and permanently lubricated bearings.

Shafts will be corrosion resistant.
Fan blades will be statically and dynamically balanced.
Condenser fan openings will be equipped with steel wire 

safety guards.
Compressor

Compressor will be hermetically sealed.
Compressor will be mounted on rubber vibration isolators.

Condenser Coil

Condenser coil will be air cooled.
Coil will be constructed of aluminum fins mechanically 

bonded to copper tubes which are then cleaned, dehydrated, and 
sealed.
Refrigeration Components

Refrigeration circuit components will include liquid tube 

shutoff valve with sweat connections, suction tube shutoff 
valves with sweat connections, system charge of refrigerant 
R-22, compressor oil, accumulator, and reversing valve.

Operating Characteristics

The capacity of the unit will meet or exceed ____ Btuh at a 

suction temperature of ____ F. The power consumption at full 
load will not exceed ____ kW.

Combination of the unit and the evaporator or fan coil unit 

will have a total net cooling capacity of ____ Btuh or greater at 
conditions of ____ CFM entering air temperature at the 
evaporator at ____ F wet bulb and ____ F dry bulb, and air 
entering the unit at ____ F.

The system will have an SEER of ____ Btuh/watt or greater 

at DOE conditions.

Electrical Requirements

Nominal unit electrical characteristics will be ____ v, 

1 phase, 60 hz. The unit will be capable of satisfactory operation 
within voltage limits of ____ v to ____ v.

Unit electrical power will be single point connection.
Control circuit will be 24v.

Special Features

Refer to section of this literature identifying accessories and 

descriptions for specific features and available enhancements.

Summary of Contents for 38YCG Series

Page 1: ...son All models are listed with UL U S and Canada CEC and ARI FEATURES Electrical Range All sizes of the 38YCG are offered in single phase 208 230v Size Range The 38YCG is available in 7 nominal sizes...

Page 2: ...ection while not restricting airflow and maintaining ease of coil inspection and cleaning Unit Design All units are equipped with totally enclosed fan motors for greater reliability under adverse weat...

Page 3: ...ty CFM Motor HP Motor RPM 60 Hz Propeller Type Direct Drive Vertical 1900 1900 2300 3000 3000 3300 3300 1 12 1 12 1 4 1 4 1 4 1 4 1 4 1100 1125 1125 1100 1100 1100 1100 CONDENSER COIL Face Area Sq Ft...

Page 4: ...Sound Hood Size 060 34 KHAOT0301FST Outdoor Thermostat All Sizes KHAOT0201SEC Secondary Outdoor Thermostat All Sizes KSATX0601HSO TXV Hard Shutoff Size 018 042 KSATX0701HSO TXV Hard Shutoff Size 048...

Page 5: ...ol provides an approximate 5 minute delay after power to the compressor has been interrupted for any reason including normal room thermostat cycling SUGGESTED USE Installations in areas where power in...

Page 6: ...ations with multiple stage supplemental heaters 15 Secondary Outdoor Thermostat An SPDT temperature actuated switch which turns on third stage of supplemental electric heaters when outdoor air tempera...

Page 7: ...tors compressors contain internal overload protection FLA Full Load Amps LRA Locked Rotor Amps MCA Minimum Circuit Amps RLA Rated Load Amps OUTDOOR UNIT V PH 60 Hz OPERATING VOLTS COMPRESSOR FAN FLA M...

Page 8: ...22 1 2 030 33 22 1 2 33 15 16 3 3 16 3 4 3 11 16 18 1 8 19 3 4 21 5 8 14 3 8 18 7 8 22 1 16 12 1 2 12 14 22 1 2 X 22 1 2 036 33 34 30 27 15 16 3 3 16 3 4 6 1 2 23 1 2 27 1 4 29 1 8 20 26 3 8 29 9 16...

Page 9: ...50 60 70 80 2 9 5 9 8 8 11 7 14 7 17 6 20 5 70 60 50 40 30 20 10 KW BASED ON INDOOR ENT AIR AT 70 F AND AT RATED CFM 23 4 80 38YCG01832 F A B 4BNF018 38YCG02432 F A B 4BNF024 38YCG03033 F A B 4BNF030...

Page 10: ...0 22 800 TDR TXV 10 00 8 80 22 800 3 22 14 000 2 30 7 0 FF1DNA024 22 000 TDR 10 00 9 05 22 800 3 18 14 100 2 28 7 0 FF1DNA030 23 000 TDR 10 00 9 05 22 800 3 24 14 200 2 30 7 0 FK4 C D NF001 23 000 TDR...

Page 11: ...4 000 3 28 20 000 2 38 7 4 CK3BA042 34 800 TDR 11 20 10 20 34 000 3 30 20 000 2 40 7 4 CK5A CK5BA042 34 800 TDR 11 20 10 25 34 000 3 30 20 000 2 40 7 4 CK5A CK5BT042 34 600 TDR 11 20 10 20 34 000 3 30...

Page 12: ...00 3 12 29 800 2 32 7 20 CE3AA048 45 000 NONE 10 00 10 00 9 35 47 000 3 12 29 600 2 34 7 20 CE3AA060 46 000 NONE 10 00 10 00 9 45 47 000 3 18 29 800 2 38 7 50 CF5AA048 44 500 NONE 10 00 10 00 9 30 46...

Page 13: ...R 10 50 9 65 56 000 3 14 38 000 2 46 7 2 CK3BA060 55 000 TDR 10 50 9 50 56 000 3 24 38 000 2 48 7 4 CK5A CK5BA060 55 000 TDR 10 50 9 50 56 000 3 24 38 000 2 48 7 4 CK5A CK5BT060 55 000 TDR 10 50 9 45...

Page 14: ...4 6 14 5 2 13 2 06 2 00 2 00 2 00 16 4 14 7 13 5 13 7 13 7 8 99 11 8 11 3 13 7 13 7 2 25 2 17 2 11 2 12 2 12 14 9 13 3 12 1 12 5 12 6 8 46 11 2 10 7 12 5 12 6 2 33 2 24 2 16 2 19 2 19 700 72 67 63 62...

Page 15: ...7 8 18 0 18 0 11 8 15 4 14 7 18 0 18 0 2 91 2 80 2 71 2 72 2 72 19 8 17 7 16 2 16 7 16 7 11 2 14 7 14 1 16 7 16 7 3 04 2 91 2 80 2 84 2 84 900 72 67 63 62 57 26 7 24 4 22 7 22 4 22 2 13 9 18 1 17 6 22...

Page 16: ...1 1 3 65 3 51 3 40 3 43 3 43 1150 72 67 63 62 57 33 1 30 4 28 0 27 7 27 5 17 1 22 5 21 7 27 1 27 5 2 99 2 91 2 85 2 84 2 84 31 4 28 5 26 2 26 1 26 0 16 6 21 8 21 0 26 0 26 0 3 18 3 09 3 02 3 01 3 01 2...

Page 17: ...0 3 4 19 4 03 3 92 3 93 3 93 34 2 30 8 28 3 28 8 28 8 18 9 25 0 24 0 28 8 28 8 4 41 4 24 4 12 4 14 4 14 32 1 28 8 26 4 27 3 27 3 18 2 24 2 23 2 27 3 27 3 4 63 4 45 4 32 4 37 4 37 Multipliers for Deter...

Page 18: ...15 5 04 4 93 4 93 4 94 39 9 36 7 33 9 34 5 34 5 22 2 30 0 28 8 34 5 34 5 5 57 5 43 5 30 5 33 5 33 37 6 34 3 31 6 32 6 32 6 21 5 29 1 27 8 32 6 32 6 5 99 5 82 5 67 5 72 5 72 Multipliers for Determinin...

Page 19: ...7 13 4 62 45 88 36 27 5 04 43 37 35 26 5 51 40 85 34 21 5 99 38 17 33 09 6 49 44 66 35 83 4 54 42 32 34 76 4 94 40 01 33 73 5 37 37 63 32 66 5 84 35 12 31 52 6 33 44 33 44 33 4 54 42 42 42 42 4 95 40...

Page 20: ...4 43 4 7 93 7 78 7 66 7 67 7 67 2000 72 67 63 62 57 64 4 58 8 54 7 54 0 53 5 33 1 43 1 41 7 52 4 53 5 5 79 5 67 5 58 5 56 5 55 61 5 56 0 52 1 51 6 51 4 32 1 42 0 40 6 51 0 51 4 6 29 6 15 6 06 6 04 6...

Page 21: ...1 45 1 46 1 48 12 6 12 7 12 9 11 2 11 3 11 4 1 53 1 54 1 56 14 9 15 0 15 2 13 5 13 7 13 8 1 62 1 63 1 64 17 3 17 5 17 6 17 3 17 5 17 6 1 72 1 73 1 74 20 3 20 5 20 7 20 3 20 5 20 7 1 86 1 87 1 88 23 4...

Page 22: ...1 86 1 89 1 91 19 1 19 5 19 7 17 4 17 7 18 0 1 96 1 98 1 99 22 2 22 6 22 9 22 2 22 6 22 9 2 06 2 07 2 09 26 0 26 5 26 9 26 0 26 5 26 9 2 20 2 21 2 21 29 8 29 9 30 0 29 8 29 9 30 0 2 34 2 30 2 30 75 70...

Page 23: ...34 4 34 8 33 9 34 4 34 8 2 87 2 87 2 89 39 2 39 8 40 3 39 2 39 8 40 3 3 07 3 07 3 08 75 950 1050 1150 10 6 10 8 11 0 9 78 9 97 10 1 2 07 2 11 2 14 13 7 14 0 14 2 12 6 12 8 13 0 2 20 2 23 2 26 16 9 17...

Page 24: ...4 6 25 0 21 4 21 8 22 2 2 96 3 01 3 06 28 7 29 2 29 7 26 1 26 6 27 0 3 20 3 24 3 28 33 8 34 4 34 8 33 8 34 4 34 8 3 46 3 49 3 53 39 2 39 8 40 3 39 2 39 8 40 3 3 76 3 78 3 81 45 2 45 9 46 4 45 2 45 9 4...

Page 25: ...2 27 0 27 4 27 7 3 82 3 84 3 88 35 4 35 8 36 2 32 2 32 6 33 0 4 10 4 11 4 13 40 7 41 3 41 8 40 7 41 3 41 8 4 41 4 41 4 42 46 8 47 4 47 9 46 8 47 4 47 9 4 79 4 77 4 77 53 5 54 2 54 8 53 5 54 2 54 8 5...

Page 26: ...71 33 51 29 76 3 93 39 35 35 81 4 19 45 79 45 79 4 50 53 31 53 31 4 89 62 02 62 02 5 38 1650 19 55 17 99 3 37 24 10 22 15 3 56 28 90 26 35 3 74 34 04 30 24 3 94 39 95 36 35 4 19 46 48 46 48 4 47 54 12...

Page 27: ...MBtuh Total Power Capacity MBtuh Total Power Capacity MBtuh Total Power EDB CFM Total Integ kW Total Integ kW Total Integ kW Total Integ kW Total Integ kW Total Integ kW Total Integ kW Total Integ kW...

Page 28: ...al features required prior to field start up Unit Cabinet Unit cabinet will be constructed of galvanized steel bonderized and coated with a powder coat paint Fans Condenser fan will be direct drive pr...

Reviews: