Copyright 2003 Carrier Corporation

Form 38YCG-4PD

 

Product
Data

 

38YCG (60 Hz)

Heat Pump

 

Sizes 018 thru 060

 

The 38YCG Outdoor Section of 

Split-System Heat Pumps is designed 
for quiet, reliable heating during the 
winter and cooling during the summer. 
With SEER ratings up to 11.5 and HSPF 
from 6.8 to 7.6, this heat pump system 
provides economy of operation through 
energy conservation when used with 
components designated by the 
manufacturer. The 38YCG recovers 
heat for indoor comfort from outdoor air 
during the heating season and, by 
automatically reversing the refrigerant 
system, removes indoor heat and excess 
humidity during the cooling season. 
All models are listed with UL (U.S. and 
Canada), CEC, and ARI.

 

FEATURES

 

Electrical Range

 

 — All sizes of the 

38YCG are offered in single phase 208–
230v. 

 

Size Range

 

 — The 38YCG is available 

in 7 nominal sizes from 018 through 060 
to meet the needs of residential and light 
commercial applications. 

 

Compressor 

 

— Designed specifically 

for heat pump duty, with energy 
efficiency during heating and cooling 
operation. Each compressor is 
hermetically sealed against 
contamination to assure long life and 
dependable performance, internally 
sprung (units with reciprocating 
compressor) and externally mounted on 
rubber isolators for quiet operation. 
Continuous compressor operation is 
approved down to –30°F (–34.4°C) 
in the heating mode, and down to 55°F 
(12.8°C) in the cooling mode (unless 
equipped for low-ambient operation). 
(See heating and cooling performance 
tables.) 

 

Summary of Contents for 38YCG Series

Page 1: ...son All models are listed with UL U S and Canada CEC and ARI FEATURES Electrical Range All sizes of the 38YCG are offered in single phase 208 230v Size Range The 38YCG is available in 7 nominal sizes...

Page 2: ...ection while not restricting airflow and maintaining ease of coil inspection and cleaning Unit Design All units are equipped with totally enclosed fan motors for greater reliability under adverse weat...

Page 3: ...ty CFM Motor HP Motor RPM 60 Hz Propeller Type Direct Drive Vertical 1900 1900 2300 3000 3000 3300 3300 1 12 1 12 1 4 1 4 1 4 1 4 1 4 1100 1125 1125 1100 1100 1100 1100 CONDENSER COIL Face Area Sq Ft...

Page 4: ...Sound Hood Size 060 34 KHAOT0301FST Outdoor Thermostat All Sizes KHAOT0201SEC Secondary Outdoor Thermostat All Sizes KSATX0601HSO TXV Hard Shutoff Size 018 042 KSATX0701HSO TXV Hard Shutoff Size 048...

Page 5: ...ol provides an approximate 5 minute delay after power to the compressor has been interrupted for any reason including normal room thermostat cycling SUGGESTED USE Installations in areas where power in...

Page 6: ...ations with multiple stage supplemental heaters 15 Secondary Outdoor Thermostat An SPDT temperature actuated switch which turns on third stage of supplemental electric heaters when outdoor air tempera...

Page 7: ...tors compressors contain internal overload protection FLA Full Load Amps LRA Locked Rotor Amps MCA Minimum Circuit Amps RLA Rated Load Amps OUTDOOR UNIT V PH 60 Hz OPERATING VOLTS COMPRESSOR FAN FLA M...

Page 8: ...22 1 2 030 33 22 1 2 33 15 16 3 3 16 3 4 3 11 16 18 1 8 19 3 4 21 5 8 14 3 8 18 7 8 22 1 16 12 1 2 12 14 22 1 2 X 22 1 2 036 33 34 30 27 15 16 3 3 16 3 4 6 1 2 23 1 2 27 1 4 29 1 8 20 26 3 8 29 9 16...

Page 9: ...50 60 70 80 2 9 5 9 8 8 11 7 14 7 17 6 20 5 70 60 50 40 30 20 10 KW BASED ON INDOOR ENT AIR AT 70 F AND AT RATED CFM 23 4 80 38YCG01832 F A B 4BNF018 38YCG02432 F A B 4BNF024 38YCG03033 F A B 4BNF030...

Page 10: ...0 22 800 TDR TXV 10 00 8 80 22 800 3 22 14 000 2 30 7 0 FF1DNA024 22 000 TDR 10 00 9 05 22 800 3 18 14 100 2 28 7 0 FF1DNA030 23 000 TDR 10 00 9 05 22 800 3 24 14 200 2 30 7 0 FK4 C D NF001 23 000 TDR...

Page 11: ...4 000 3 28 20 000 2 38 7 4 CK3BA042 34 800 TDR 11 20 10 20 34 000 3 30 20 000 2 40 7 4 CK5A CK5BA042 34 800 TDR 11 20 10 25 34 000 3 30 20 000 2 40 7 4 CK5A CK5BT042 34 600 TDR 11 20 10 20 34 000 3 30...

Page 12: ...00 3 12 29 800 2 32 7 20 CE3AA048 45 000 NONE 10 00 10 00 9 35 47 000 3 12 29 600 2 34 7 20 CE3AA060 46 000 NONE 10 00 10 00 9 45 47 000 3 18 29 800 2 38 7 50 CF5AA048 44 500 NONE 10 00 10 00 9 30 46...

Page 13: ...R 10 50 9 65 56 000 3 14 38 000 2 46 7 2 CK3BA060 55 000 TDR 10 50 9 50 56 000 3 24 38 000 2 48 7 4 CK5A CK5BA060 55 000 TDR 10 50 9 50 56 000 3 24 38 000 2 48 7 4 CK5A CK5BT060 55 000 TDR 10 50 9 45...

Page 14: ...4 6 14 5 2 13 2 06 2 00 2 00 2 00 16 4 14 7 13 5 13 7 13 7 8 99 11 8 11 3 13 7 13 7 2 25 2 17 2 11 2 12 2 12 14 9 13 3 12 1 12 5 12 6 8 46 11 2 10 7 12 5 12 6 2 33 2 24 2 16 2 19 2 19 700 72 67 63 62...

Page 15: ...7 8 18 0 18 0 11 8 15 4 14 7 18 0 18 0 2 91 2 80 2 71 2 72 2 72 19 8 17 7 16 2 16 7 16 7 11 2 14 7 14 1 16 7 16 7 3 04 2 91 2 80 2 84 2 84 900 72 67 63 62 57 26 7 24 4 22 7 22 4 22 2 13 9 18 1 17 6 22...

Page 16: ...1 1 3 65 3 51 3 40 3 43 3 43 1150 72 67 63 62 57 33 1 30 4 28 0 27 7 27 5 17 1 22 5 21 7 27 1 27 5 2 99 2 91 2 85 2 84 2 84 31 4 28 5 26 2 26 1 26 0 16 6 21 8 21 0 26 0 26 0 3 18 3 09 3 02 3 01 3 01 2...

Page 17: ...0 3 4 19 4 03 3 92 3 93 3 93 34 2 30 8 28 3 28 8 28 8 18 9 25 0 24 0 28 8 28 8 4 41 4 24 4 12 4 14 4 14 32 1 28 8 26 4 27 3 27 3 18 2 24 2 23 2 27 3 27 3 4 63 4 45 4 32 4 37 4 37 Multipliers for Deter...

Page 18: ...15 5 04 4 93 4 93 4 94 39 9 36 7 33 9 34 5 34 5 22 2 30 0 28 8 34 5 34 5 5 57 5 43 5 30 5 33 5 33 37 6 34 3 31 6 32 6 32 6 21 5 29 1 27 8 32 6 32 6 5 99 5 82 5 67 5 72 5 72 Multipliers for Determinin...

Page 19: ...7 13 4 62 45 88 36 27 5 04 43 37 35 26 5 51 40 85 34 21 5 99 38 17 33 09 6 49 44 66 35 83 4 54 42 32 34 76 4 94 40 01 33 73 5 37 37 63 32 66 5 84 35 12 31 52 6 33 44 33 44 33 4 54 42 42 42 42 4 95 40...

Page 20: ...4 43 4 7 93 7 78 7 66 7 67 7 67 2000 72 67 63 62 57 64 4 58 8 54 7 54 0 53 5 33 1 43 1 41 7 52 4 53 5 5 79 5 67 5 58 5 56 5 55 61 5 56 0 52 1 51 6 51 4 32 1 42 0 40 6 51 0 51 4 6 29 6 15 6 06 6 04 6...

Page 21: ...1 45 1 46 1 48 12 6 12 7 12 9 11 2 11 3 11 4 1 53 1 54 1 56 14 9 15 0 15 2 13 5 13 7 13 8 1 62 1 63 1 64 17 3 17 5 17 6 17 3 17 5 17 6 1 72 1 73 1 74 20 3 20 5 20 7 20 3 20 5 20 7 1 86 1 87 1 88 23 4...

Page 22: ...1 86 1 89 1 91 19 1 19 5 19 7 17 4 17 7 18 0 1 96 1 98 1 99 22 2 22 6 22 9 22 2 22 6 22 9 2 06 2 07 2 09 26 0 26 5 26 9 26 0 26 5 26 9 2 20 2 21 2 21 29 8 29 9 30 0 29 8 29 9 30 0 2 34 2 30 2 30 75 70...

Page 23: ...34 4 34 8 33 9 34 4 34 8 2 87 2 87 2 89 39 2 39 8 40 3 39 2 39 8 40 3 3 07 3 07 3 08 75 950 1050 1150 10 6 10 8 11 0 9 78 9 97 10 1 2 07 2 11 2 14 13 7 14 0 14 2 12 6 12 8 13 0 2 20 2 23 2 26 16 9 17...

Page 24: ...4 6 25 0 21 4 21 8 22 2 2 96 3 01 3 06 28 7 29 2 29 7 26 1 26 6 27 0 3 20 3 24 3 28 33 8 34 4 34 8 33 8 34 4 34 8 3 46 3 49 3 53 39 2 39 8 40 3 39 2 39 8 40 3 3 76 3 78 3 81 45 2 45 9 46 4 45 2 45 9 4...

Page 25: ...2 27 0 27 4 27 7 3 82 3 84 3 88 35 4 35 8 36 2 32 2 32 6 33 0 4 10 4 11 4 13 40 7 41 3 41 8 40 7 41 3 41 8 4 41 4 41 4 42 46 8 47 4 47 9 46 8 47 4 47 9 4 79 4 77 4 77 53 5 54 2 54 8 53 5 54 2 54 8 5...

Page 26: ...71 33 51 29 76 3 93 39 35 35 81 4 19 45 79 45 79 4 50 53 31 53 31 4 89 62 02 62 02 5 38 1650 19 55 17 99 3 37 24 10 22 15 3 56 28 90 26 35 3 74 34 04 30 24 3 94 39 95 36 35 4 19 46 48 46 48 4 47 54 12...

Page 27: ...MBtuh Total Power Capacity MBtuh Total Power Capacity MBtuh Total Power EDB CFM Total Integ kW Total Integ kW Total Integ kW Total Integ kW Total Integ kW Total Integ kW Total Integ kW Total Integ kW...

Page 28: ...al features required prior to field start up Unit Cabinet Unit cabinet will be constructed of galvanized steel bonderized and coated with a powder coat paint Fans Condenser fan will be direct drive pr...

Reviews: