Select a location free of dust or foreign matter which may
cause coil clogging.
-
Leave sufficient clearance for free air circulation (outdoor
supply and return air).
-
For minimum clearances between the units and walls or
roofs, see Fig. 20:
38XTZ 007 and 008
Fig. 20
Table 5 - Minimum clearances (mm)
A
B
C
D
E
F (*)
200
200
500
200
2000
5000 (*)
(*)
Leave a minimum of 1 m clearance around the unit.
38XTZ 011, 016, 020 and 024
Fig. 21
Table 6 - Minimum clearances (mm)
A
B
C
D (*)
500
500
1000
Free (*)
(*)
Leave a minimum of 1 m clearance around the unit.
38XTZ 014
Fig. 22
Table 7 - Minimum clearances (mm)
A
B
C
D (*)
500
1000
500
Free (*)
(*)
Leave a minimum of 1 m clearance around the unit.
-
If several units are installed close to each other in the same
area, ensure the minimum clearance between them to
allow free air flow.
38XTZ 007 and 008
Fig. 23
VISTA EN PLANTA
ROOF
FLOOR
WALL
FRONT VIEW
PLAN VIEW
Return air
Supply air
Return
air
Return air
Supply
air
PLAN VIEW
Return air
Supply air
PLAN VIEW
ROOF
WALL
Supply
air
Return air
Supply
air
Return air
WALL
FLOOR
RIGHT SIDE VIEW
RIGHT SIDE VIEW
Return air
Return air
Return air
PLAN VIEW
ROOF
Supply air
Return air
Return air
Control box
Access panel
WALL
FLOOR
FRONT VIEW
Control
box
Access
panel
FLOOR
Return air
Return
air
Return air
Return air
Supply air
Supply air
PLAN VIEW
NO
Return air
Return air
Return air
Return air
Supply air
Supply air
OK