Table 1 – Indoor Unit Capacity Chart
Connectable Indoor Unit Capacity
Index *
7
9
12
15
18
24
30
36
48
54
72
96
Outside air
40VMA
•
•
•
•
•
4-way cassette
40VMF
•
•
•
•
•
•
•
•
Compact 4-way cassette
40VMC
•
•
•
•
High wall
40VMW
•
•
•
•
•
•
•
Low static duct
40VML
•
•
•
•
•
•
Medium static duct
40VMM
•
•
•
•
•
•
•
•
•
High static duct
40VMH
•
•
•
•
•
•
•
Vertical AHU
40VMV
•
•
•
•
•
•
Underceiling/floor
40VMU
•
•
•
•
•
•
•
Floor console recessed
40VMR
•
•
•
•
•
•
* For example: The capacity index of 40VMF009---3 and 40VMV024 is 9 and 24 respectively.
2. Capacity Range
Connected capacity ratio =
Total capacity index of the indoor units
Capacity index of the outdoor units
Keep a proper connected capacity ratio for the entire system.
Table 2 - Connected Capacity Ratio
Min. combination ratio
Max. combination ratio
40VMH for all IDUs *1 ,
40VMV for all IDUs
40VMA connected with
other IDUs
At least one 40VMH *1 or
40VMV connected
Other indoor unit
models
50%
100%
100% *2
130% *3
135%
NOTES
*1 When 40VMH048, 054, 072, 096---3 is installed.
*2 When outside air units (40VMA) and standard indoor units are connected, the total capacity index of the 40VMA must be
limited to 30% or less of the capacity index of the outdoor unit.
*3 When the total capacity of 40VMH048, 054, 072, 096---3 or 40VMV exceeds 30%, the combination must not exceeds 100%.
5
Summary of Contents for 38VMA Series
Page 8: ...II Refrigerant Circuit 1 Refrigerant Circuit Diagram Figure 17 38VMA072 096 120HDS 8...
Page 9: ...Figure 18 38VMA144HDS 9...
Page 11: ...2 Functional Parts Layout Figure 19 38VMA072 096 120HDS 11...
Page 12: ...Figure 20 38VMA0144HDS 12...
Page 14: ...Figure 22 Cooling Oil Return 14...
Page 15: ...Figure 23 Heating Oil Return and Defrost 15...
Page 16: ...Figure 24 Heating Operation 16...
Page 17: ...b 38VMA144HDS Figure 25 Cooling Operation 17...
Page 18: ...Figure 26 Cooling Oil Return 18...
Page 19: ...Figure 27 Heating Oil Return and Defrost 19...
Page 20: ...Figure 28 Heating Operation 20...
Page 21: ...III Function and Control 1 Operation Mode Figure 29 Operation Mode 21...
Page 77: ...VIII Appendix 1 Wiring Diagram Figure 36 38VMA072 096 120HDS5 1 77...
Page 78: ...Figure 37 38VMA144HDS5 1 78...
Page 79: ...Figure 38 38VMA072 096 120HDS6 1 79...
Page 80: ...Figure 39 38VMA144HDS6 1 80...
Page 81: ...2 Electronic Control Box Layout Figure 40 38VMA072 096 120HDS5 1 Figure 41 38VMA144HDS5 1 81...
Page 82: ...Figure 42 38VMA072 096 120HDS6 1 Figure 43 38VMA144HDS6 1 82...
Page 83: ...Figure 44 Main control board layout Figure 45 ENC1 Outdoor unit addressing 83...
Page 84: ...Figure 46 ENC4 network addressing Figure 47 ENC3 S12 Indoor unit quantity setting 84...
Page 85: ...Figure 48 S5 Running mode priority setting Figure 49 S6 Auto addressing 85...
Page 86: ...Figure 50 S11 anti snow setting Figure 51 S16 Mode setting 86...
Page 87: ...Figure 52 S17 Heating mode setting Figure 53 S18 Cooling mode setting 87...
Page 93: ...Figure 55 Control Board Views 93...
Page 97: ...2 38VMA144HDS5 1 Figure 56 3 Phase Heat Pump Exploded View 97...
Page 98: ...98...
Page 99: ...Figure 57 Control Board Views 99...
Page 103: ...3 38VMA072HDS6 1 38VMA096HDS6 1 38VMA120HDS6 1 Figure 58 3 Phase Heat Pump Exploded View 103...
Page 104: ...Figure 59 Control Board Views 104...
Page 108: ...4 38VMA144HDS6 1 Figure 60 3 Phase Heat Pump Exploded View 108...
Page 109: ...109...