Indoor unit Operation
Cooling oil return operation
Status
Fan
Electronic Expansion Valve
Thermal ON
OFF
480P
OFF
OFF
480P
Thermal OFF
OFF
480P
Defrost starting condition: Defrost operation is started when the outdoor heat exchanger temperature becomes lower than
threshold temperature. Defrost operation is conducted once in a maximum of 2 hours.
Table 27 - Restart Standby
Component
Cooling Operation
Heating Operation
Compressor
OFF
OFF
Outdoor unit fan (FAN A)
OFF
OFF
Outdoor unit fan (FAN B)
OFF
OFF
Four way valve (ST1)
OFF
Holds
Electronic expansion valve (EXV A)
350P
Initial pulse step
Electronic expansion valve (EXV B)
350P
Initial pulse step
Electronic expansion valve (EXV C)
0P
0P
Solenoid valve (SV4)
OFF
OFF
Solenoid valve (SV7)
OFF
OFF
Ending conditions
12 minutes
12 minutes
3. Overload Control
To maintain the required set point, the air flow of all indoor units are set to low speed if the connected capacity of the indoor
units is more than 120%. However, the air flow of the indoor units will return to normal once the connected capacity of
indoor unit is less than 105%.
4. Stopping Operation
Table 28 - When System is in Stop Mode
Component
Operation
Compressor
OFF
Outdoor unit fan (FAN A)
OFF
Outdoor unit fan (FAN B)
OFF
Four way valve (ST1)
OFF
Electronic expansion valve (EXV A)
350P
Electronic expansion valve (EXV B)
350P
Electronic expansion valve (EXV C)
0P
Solenoid valve (SV4)
OFF
Solenoid valve (SV7)
OFF
Ending conditions
Indoor unit thermostat is turned ON
Stop operation of follower units while header unit is still in operation in a modular system.
33
Summary of Contents for 38VMA Series
Page 8: ...II Refrigerant Circuit 1 Refrigerant Circuit Diagram Figure 17 38VMA072 096 120HDS 8...
Page 9: ...Figure 18 38VMA144HDS 9...
Page 11: ...2 Functional Parts Layout Figure 19 38VMA072 096 120HDS 11...
Page 12: ...Figure 20 38VMA0144HDS 12...
Page 14: ...Figure 22 Cooling Oil Return 14...
Page 15: ...Figure 23 Heating Oil Return and Defrost 15...
Page 16: ...Figure 24 Heating Operation 16...
Page 17: ...b 38VMA144HDS Figure 25 Cooling Operation 17...
Page 18: ...Figure 26 Cooling Oil Return 18...
Page 19: ...Figure 27 Heating Oil Return and Defrost 19...
Page 20: ...Figure 28 Heating Operation 20...
Page 21: ...III Function and Control 1 Operation Mode Figure 29 Operation Mode 21...
Page 77: ...VIII Appendix 1 Wiring Diagram Figure 36 38VMA072 096 120HDS5 1 77...
Page 78: ...Figure 37 38VMA144HDS5 1 78...
Page 79: ...Figure 38 38VMA072 096 120HDS6 1 79...
Page 80: ...Figure 39 38VMA144HDS6 1 80...
Page 81: ...2 Electronic Control Box Layout Figure 40 38VMA072 096 120HDS5 1 Figure 41 38VMA144HDS5 1 81...
Page 82: ...Figure 42 38VMA072 096 120HDS6 1 Figure 43 38VMA144HDS6 1 82...
Page 83: ...Figure 44 Main control board layout Figure 45 ENC1 Outdoor unit addressing 83...
Page 84: ...Figure 46 ENC4 network addressing Figure 47 ENC3 S12 Indoor unit quantity setting 84...
Page 85: ...Figure 48 S5 Running mode priority setting Figure 49 S6 Auto addressing 85...
Page 86: ...Figure 50 S11 anti snow setting Figure 51 S16 Mode setting 86...
Page 87: ...Figure 52 S17 Heating mode setting Figure 53 S18 Cooling mode setting 87...
Page 93: ...Figure 55 Control Board Views 93...
Page 97: ...2 38VMA144HDS5 1 Figure 56 3 Phase Heat Pump Exploded View 97...
Page 98: ...98...
Page 99: ...Figure 57 Control Board Views 99...
Page 103: ...3 38VMA072HDS6 1 38VMA096HDS6 1 38VMA120HDS6 1 Figure 58 3 Phase Heat Pump Exploded View 103...
Page 104: ...Figure 59 Control Board Views 104...
Page 108: ...4 38VMA144HDS6 1 Figure 60 3 Phase Heat Pump Exploded View 108...
Page 109: ...109...