64
/
78
12.3.1.4 Open or short circuit of temperature sensor.
Check the connections
between temperature
sensor and PCB. Are the
connections good?
Check the connections
between temperature
sensor and PCB. Are the
connections good?
Correct the connections.
Correct the connections.
No
Yes
No
Replace the sensor.
Replace the sensor.
Replace the indoor PCB
Replace the indoor PCB
Measure the resistance value
of the sensor via Appendix 1
Measure the resistance value
of the sensor via Appendix 1
Is it normal?
Is it normal?
Yes
12.3.1.5 Full-water malfunction
(For cassette / A5 duct)
If the water-level switch
is inserted well?
If the water-level switch
is inserted well?
No
Insert the water-level switch well
Insert the water-level switch well
If the water-level switch
is broken?
If the water-level switch
is broken?
Yes
Replace the water-level switch
Replace the water-level switch
Replace the water pump, If
malfunction
is
still
not
solved
Replace the water pump, If
malfunction
is
still
not
solved
Yes
No
Yes
Replace the indoor main PCB
Replace the indoor main PCB
Power off, then restart the unit 2 minutes
later. Is it still displaying the error code?
Power off, then restart the unit 2 minutes
later. Is it still displaying the error code?
Yes
Summary of Contents for 38QUS018DS2 Series
Page 16: ...16 78 3 4 A5 Duct ...
Page 19: ...19 78 ...
Page 20: ...20 78 5 Wiring Diagram Outdoor 38QUS018DS2 Outdoor 38QUS027DS3 ...
Page 21: ...21 78 Outdoor 38QUS036DS4 High wall 42QHF009DS 42QHF012DS 42QHF018DS ...
Page 22: ...22 78 A5 Duct 42QSM009DS A5 Duct 42QSM012DS 42QSM018DS ...
Page 23: ...23 78 Four way cassette 42QTD009DS Four way cassette 42QTD012DS 42QTD018DS ...
Page 24: ...24 78 Console ...