93
Remark:
Use a multimeter to test the DC
voltage between 2 port and 3 port of
outdoor unit. The red pin of
multimeter connects with 2 port while
the black pin is for 3 port.
When AC is normal running, the
voltage will move alternately between
-50V to 50V.
If the outdoor unit has malfunction,
the voltage will move alternately with
positive value.
While if the indoor unit has
malfunction, the voltage will be a
certain value.
Remark,
The old label is L1,L2,S, L1,L2
The new label is 1, 2, 3, L1,L2
Remark:
Use a multimeter to test the
resistance of the reactor which does
not connect with capacitor.
The normal value should be around
zero ohm. Otherwise, the reactor
must have malfunction and need to
be replaced.
Summary of Contents for 38QUA009DS
Page 8: ...5 2 2 Part names of Indoor Outdoor units Cassette Unit...
Page 9: ...6 A5 Ducted Units A6 Ducted Units...
Page 10: ...7 Floor ceiling Units...
Page 11: ...8 HESP DUCTED Units...
Page 35: ...32 6 Wiring Diagram 6 1 Indoor Unit 40QTD018DS 40QTD024DS 40QTD036DS 40QTD048DS...
Page 36: ...33 40QSM018DS 40QSM024DS 40QSM036DS 40QSM048DS...
Page 37: ...34 40QZL018DS 40QZL024DS 40QZL036DS...
Page 38: ...35 40QZL048DS 40QZL060DS...
Page 40: ...37 6 2 Outdoor Unit 38QUA018DS 38QUA024DS...
Page 41: ...38 38QUA036DS...
Page 42: ...39 38QUA048DS 38QUA060DS...
Page 44: ...41 40QSM018DS Code 0 Code 1 Code 2 Code 3 Code 4...
Page 45: ...42 40QSM024DS Code 0 Code 1 Code 2 Code 3 Code 4...
Page 46: ...43 40QSM036DS Code 0 Code 1 Code 2 Code 3 Code 4...
Page 47: ...44 40QSM048DS Code 0 Code 1 Code 2 Code 3 Code 4...
Page 60: ...57 12 Field Wiring 18K 24K 36K 48K...
Page 61: ...58 60K...
Page 104: ...101 P U P V...
Page 105: ...102 P W P N...