76
2
Purpose of refrigerant pipe insulation
During operation, temperature of gas pipe
and liquid pipe shall be over-heating or
over-cooling extremely. Therefore, it is
necessary to carry out insulation; otherwise
it shall debase the performance of unit and
burn compressor.
Gas pipe temperature is very low during
cooling. If insulation is not enough, it shall
form dew and cause leakage.
Temperature of gas pipe is very high
(generally 50-100
℃
) during heating.
Insulation work must be carried out to
prevent hurt by carelessness touching.
3
Insulation
material
selection
for
refrigerant pipe
The burning performance should over
120
℃
According to the local law to choose
insulation materials
The thickness of insulation layer shall be
above 10mm.If in hot or wet environment
place, the layer of insulation should be
thicker accordingly.
4
Installation highlights of insulation
construction
Gas pipe and liquid pipe shall be insulated
separately, if the gas pipe and liquid pipe
were insulated together; it will decrease the
performance of air conditioner.
Liquid pipe
Insulation meterial
Gas pipe
The insulation material at the joint pipe
shall be 5~10cm longer than the gap of the
insulation material.
The insulation material at the joint pipe
shall be inserted into the gap of the insulation
material.
The insulation material at the joint pipe
shall be banded to the gap pipe and liquid pipe
tightly.
The linking part should be use glue to paste
together
Be sure not bind the insulation material
over-tight, it may extrude out the air in the
material to cause bad insulation and cause
easy aging of the material.
13.8.2
Insulation of drainage pipe
1
Operational procedure of refrigerant
pipe insulation
Select the suitable pipe → insulation (except
joint section) → piping layout and connection→
drainage test→ insulate the joint parts
2
Purpose of drainage pipe insulation
The temperature of condensate drainage water
is very low. If insulation is not enough, it shall
form dew and cause leakage to damage the
house decoration.
3
Insulation
material
selection
for
drainage pipe
The insulation material should be flame
retardant material, the flame retardancy of
the material should be selected according
to the local law.
Thickness of insulation layer is usually
above 10mm.
Use specific glue to paste the seam of
insulation material, and then bind with
adhesive tape. The width of tape shall not
be less than 5cm. Make sure it is firm and
avoid dew.
4
Installation and highlights of insulation
construction
The single pipe should be insulated before
connecting to another pipe, the joint part
should be insulated after the drainage test.
There should be no insulation gap between
the insulation material.
Engineering of electrical wiring
1
Highlights
of
electrical
wiring
installation
Summary of Contents for 38QUA009DS
Page 8: ...5 2 2 Part names of Indoor Outdoor units Cassette Unit...
Page 9: ...6 A5 Ducted Units A6 Ducted Units...
Page 10: ...7 Floor ceiling Units...
Page 11: ...8 HESP DUCTED Units...
Page 35: ...32 6 Wiring Diagram 6 1 Indoor Unit 40QTD018DS 40QTD024DS 40QTD036DS 40QTD048DS...
Page 36: ...33 40QSM018DS 40QSM024DS 40QSM036DS 40QSM048DS...
Page 37: ...34 40QZL018DS 40QZL024DS 40QZL036DS...
Page 38: ...35 40QZL048DS 40QZL060DS...
Page 40: ...37 6 2 Outdoor Unit 38QUA018DS 38QUA024DS...
Page 41: ...38 38QUA036DS...
Page 42: ...39 38QUA048DS 38QUA060DS...
Page 44: ...41 40QSM018DS Code 0 Code 1 Code 2 Code 3 Code 4...
Page 45: ...42 40QSM024DS Code 0 Code 1 Code 2 Code 3 Code 4...
Page 46: ...43 40QSM036DS Code 0 Code 1 Code 2 Code 3 Code 4...
Page 47: ...44 40QSM048DS Code 0 Code 1 Code 2 Code 3 Code 4...
Page 60: ...57 12 Field Wiring 18K 24K 36K 48K...
Page 61: ...58 60K...
Page 104: ...101 P U P V...
Page 105: ...102 P W P N...