Installation, Start-Up and Service

Instructions

CONTENTS

Page

SAFETY CONSIDERATIONS

. . . . . . . . . . . . . . . . . . 1

INSTALLATION

. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6

Step 1 — Complete Pre-Installation Checks

. .. 1-4

• UNPACK UNIT
• INSPECT SHIPMENT
• CONSIDER SYSTEM REQUIREMENTS
• CHECK ACCURATER® METERING DEVICE

Step 2 — Rig and Mount Unit

. . . . . . . . . . . . . . . . 4

• MOUNTING ON GROUND
• MOUNTING ON ROOF
• RIGGING

Step 3 — Complete Refrigerant
Piping Connections

. . . . . . . . . . . . . . . . . . . . . . . . 4,5

• INSTALL FILTER DRIER AND MOISTURE

INDICATOR

• MAKE PIPING SWEAT CONNECTIONS
• PROVIDE SAFETY RELIEF

Step 4 — Make Electrical Connections

. . . . . . 6

• POWER WIRING
• CONTROL CIRCUIT WIRING

START-UP

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6,7

Preliminary Checks

. . . . . . . . . . . . . . . . . . . . . . . . 6

Leak Test

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Evacuate and Dehydrate

. . . . . . . . . . . . . . . . . . . . 6

Charge System

. . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

To Start Unit

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

SERVICE

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-11

MAINTENANCE

. . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

TROUBLESHOOTING

. . . . . . . . . . . . . . . . . . . . 12,13

SAFETY CONSIDERATIONS

Installing and servicing air conditioning equipment can

be hazardous due to system pressure and electrical compo-
nents. Only trained and qualified service personnel should
install or service air conditioning equipment.

Untrained personnel can perform basic maintenance, such

as cleaning and replacing filters. All other operations should
be performed by trained service personnel. When working
on air conditioning equipment, observe safety precautions in
literature, tags, and labels attached to unit.

Follow all safety codes. Wear safety glasses and work gloves.

Use quenching cloth for brazing operations. Have fire ex-
tinguisher available. Read these instructions thoroughly. Con-
sult local building codes and National Electrical Code (NEC)
for special installation requirements.

Before installing or servicing system, always turn off
main power to system. There may be more than one dis-
connect switch. Turn off accessory heater power if ap-
plicable. Electrical shock can cause personal injury.

INSTALLATION

Step 1 — Complete Pre-Installation Checks

UNPACK UNIT (see Fig. 1.) — Move unit to final location.
Remove carton from unit, being careful not to damage serv-
ice valves and grilles.

INSPECT SHIPMENT — File claim with shipping com-
pany if shipment is damaged or incomplete.

CONSIDER SYSTEM REQUIREMENTS — Consult
local building codes and NEC for special installation
requirements.

Allow sufficient space for airflow clearance, wiring, re-

frigerant piping, and servicing unit. See Fig. 2 and 3.

Locate unit so that airflow is unrestricted on both sides.

Refer to Fig. 2 and 3.

Unit may be mounted on a level pad directly on base legs

or mounted on raised pads at support points. See Fig. 2 and
3 for center of gravity.

HEAT PUMP

Fig. 1 — Model 38QR018C-060C

38QR018C-060C

Commercial Heat Pumps

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book 1

4

Tab

5a 5a

PC 111

Catalog No. 563-882

Printed in U.S.A.

Form 38QRC-1SI

Pg 1

3-92

Replaces: New

Summary of Contents for 38QR018C-060C

Page 1: ...gloves Use quenching cloth for brazing operations Have fire ex tinguisher available Read these instructions thoroughly Con sult local building codes and National Electrical Code NEC for special insta...

Page 2: ...6C 3 7 sq ft 34 m2 5 Do not use screws longer than 1 2 in 13 mm near return air opening UNIT WEIGHT LB KG DIMENSIONS in mm A B C 38QR018C 154 70 13 329 5 8 15 88 3 8 9 53 38QR024C 167 76 38QR030C 180...

Page 3: ...longer than 1 2 in 13 mm near return air opening UNIT WEIGHT LB KG DIMENSIONS in mm A B C 38QR036C 249 113 13 11 16 28 97 7 8 22 22 3 8 9 53 38QR048C 252 114 1311 16 28 97 7 8 22 22 3 8 9 53 38QR060C...

Page 4: ...s should be used and fastened through slots pro vided in unit mounting feet MOUNTING ON ROOF Mount unit on a level platform or frame at least 6 in above roof surface Isolate unit and tubing from struc...

Page 5: ...through piping while brazing to prevent formation of copper oxide To avoid damage while brazing service valves should be wrapped with a heat sinking material such as a wet cloth When brazing tubing s...

Page 6: ...unit in system where voltage may fluctuate above or below permissible limits See Table 2 for recommended fuse sizes When making electrical connections provide clearance at unit for refrig erant pipin...

Page 7: ...meter or continuity tester If necessary refer to Carrier Stand ard System Techniques Manual Chapter 2 for complete information Pumpdown Procedure The system may be pumped down in order to make repairs...

Page 8: ...opens DO NOT attempt to simulate the system abnormalities high pressures pose a serious safety hazard High pressure switch is also checked with an ohmmeter similar to checking low pressure switch If...

Page 9: ...pts the nor mal system heating operation to defrost the outdoor coil if the coil saturated suction temperature indicates freezing temperatures Defrost control board can be field set to check need for...

Page 10: ...wet bulb temperature with a sling psychrometer 6 Refer to Table 3 Find air temperature entering outdoor coil and wet bulb temperature entering indoor coil At this intersection note the superheat temp...

Page 11: ...of Table 5 Heating Operation Pressure Table Fixed Restrictor High Pressure at Suction Valve Low Pressure at Liquid Valve Suction Pressure at Compressor UNIT 38QR INDOOR DRY BULB TEMP F OUTDOOR TEMPERA...

Page 12: ...HOOTING CHART HEATING CYCLE LEGEND NC Normally Closed ODT Outdoor Thermostat NOTE For systems with indoor units equipped with microprocessor control see separate controls service and troubleshooting m...

Page 13: ...TROUBLESHOOTING CHART COOLING CYCLE LEGEND NC Normally Closed NOTE For systems with indoor units equipped with microprocessor control see separate controls service and troubleshooting manual 13...