5
Table 2 - Electrical data
50VZ (40PZ/38VZ)
015
025
030
031
040
045
055
065
075
Nominal voltage
±
10%*
V
230
400
230
400
230
400
230
400
230
400
230
400
230
400
230
400
230
400
Nominal power input**
kW
7.3
7.3
11.1
11.1
14.0
14.0
14.6
14.6
18.1
18.1
21.4
21.4
25.4
25.4
30.0
30.0
37.6
37.6
Nominal current drawn**
A
23.8
13.8
33.1
19.1
39.4
22.8
44.9
26.0
52.6
30.4
64.9
37.5
74.3
43.0
87.8
50.8
122.1 67.1
Effective power input
kW
6.8
6.8
10.2
10.2
13.0
13.0
13.6
13.6
16.8
16.8
19.0
19.0
22.2
22.2
26.1
26.1
33.1
33.1
Effective current drawn
A
21.6
12.5
30.5
17.6
37.0
21.4
41.9
24.2
56.5
32.6
57.9
33.4
70.0
40.5
76.6
44.3
102.0 59.0
Starting current
A
139.5 80.0
174.1 106.3 219.0 133.3 165.9 95.3
235.2 134.0 278.4 156.7 329.1 187.8 384.5 219.0 450.1 256.0
Maximum power input***
kW
7.9
7.9
12.2
12.2
15.5
15.5
16.1
16.1
21.8
21.8
25.2
25.2
29.6
29.6
35.0
35.0
44.2
44.2
Maximum current drawn***
A
24.2
14.0
35.5
20.5
43.2
25.0
49.5
28.6
66.6
38.5
73.1
42.2
88.8
51.3
99.7
57.6
129.5 74.8
Condensing unit 38VZ
015
025
030
031
040
045
055
065
075
Nominal voltage
±
10%*
V
230
400
230
400
230
400
230
400
230
400
230
400
230
400
230
400
230
400
Nominal power input
+
kW
6.5
6.5
10.1
10.1
12.8
12.8
13.2
13.2
16.7
16.7
19.4
19.4
23.0
23.0
26.9
26.9
34.7
34.7
Nominal current drawn
+
A
20.6
11.9
29.9
17.3
36.6
21.2
37.8
21.9
56.2
32.5
59.4
34.3
72.7
42.0
79.1
45.7
106.6 61.6
Effective power input
kW
6.3
6.3
9.6
9.6
12.3
12.3
12.7
12.7
16.0
16.0
18.3
18.3
21.4
21.4
25.0
25.0
32.5
32.5
Effective current drawn
A
20.1
11.6
28.5
16.5
35.4
20.4
36.4
21.1
54.0
31.2
56.0
32.4
67.6
39.1
73.5
42.5
99.9
57.7
Starting current
A
136.7 78.4
170.1 104.0 214.1 130.5 161.1 92.5
226.9 129.2 270.9 151.2 319.2 180.9 372.2 211.9 434.2 246.8
Maximum power input
++
kW
7.7
7.7
11.5
11.5
14.9
14.9
15.3
15.3
20.6
20.6
24.0
24.0
29.1
29.1
33.8
33.8
43.9
43.9
Maximum current drawn
++
A
23.5
13.6
33.5
19.4
41.4
23.9
42.5
24.5
62.9
36.4
69.4
40.1
87.4
50.5
96.2
55.6
128.5 74.3
*
All units are built for 3-phase, 50 Hz supply.
**
Based on an outdoor air dry bulb temperature of 35
°
C and an indoor air wet bulb temperature of 19
°
C.
*** Based on an outdoor air dry bulb temperature of 46
°
C and an indoor air wet bulb temperature of 21
°
C.
+
Based on an outdoor air dry bulb temperature of 35
°
C and a dewpoint suction temperature of 7
°
C.
++
Based on an outdoor air dry bulb temperature of 46
°
C and a dewpoint suction temperature of 12
°
C.
50PZ (40PZ/38PZ)
015
025
030
031
040
045
055
065
075
Nominal voltage
±
10%*
V
230
400
230
400
230
400
230
400
230
400
230
400
230
400
230
400
230
400
Nominal power input
kW
Cooling**
7.2
7.2
11.2
11.2
13.6
13.6
14.6
14.6
18.1
18.1
21.6
21.6
25.4
25.4
30.2
30.2
38.5
38.5
Heating***
6.6
6.6
11.1
11.1
12.4
12.4
12.7
12.7
17.5
17.5
20.8
20.8
23.7
23.7
27.1
27.1
34.3
34.3
Nominal current drawn
A
Cooling**
23.7
13.7
33.2
19.2
38.4
22.2
46.0
26.6
55.0
31.8
66.1
38.2
73.3
42.4
88.0
50.9
118.5 68.6
Heating***
22.5
13.0
33.2
19.2
35.8
20.7
41.5
24.0
52.2
30.2
63.7
36.8
70.7
40.9
82.0
47.4
109.8 63.5
Effective power input
kW
Cooling
6.7
6.7
10.3
10.3
12.5
12.5
13.6
13.6
16.8
16.8
19.1
19.1
22.2
22.2
26.3
26.3
34.1
34.1
Heating
6.1
6.1
10.3
10.3
11.4
11.4
11.6
11.6
16.2
16.2
18.4
18.4
20.5
20.5
23.2
23.2
29.8
29.8
Effective current drawn
A
Cooling
22.1
12.7
30.5
17.7
35.3
20.4
42.8
24.8
51.0
29.5
59.4
33.8
64.1
37.1
76.6
44.3
105.0 60.8
Heating
20.8
12.0
30.8
17.8
32.9
19.0
37.9
21.9
48.3
28.0
56.4
32.6
61.2
35.4
70.2
40.6
95.4
55.2
Starting current
A
139.5 80.0
174.1 106.3 219.0 133.3 165.9 95.3
235.2 134.0 278.4 156.7 329.1 187.8 384.5 219.0 450.1 256.0
Maximum power input
kW
Cooling
+
8.0
8.0
12.4
12.4
15.2
15.2
16.3
16.3
21.6
21.6
25.3
25.3
30.4
30.4
34.9
34.9
44.5
44.5
Heating
++
7.5
7.5
13.1
13.1
15.8
15.8
14.4
14.4
20.3
20.3
23.7
23.7
28.1
28.1
32.8
32.8
41.6
41.6
Maximum current drawn
A
Cooling
+
26.3
15.2
36.8
21.3
42.9
24.8
51.4
29.7
65.6
37.9
77.4
44.7
87.7
50.7
101.7 58.8
137.0 79.3
Heating
++
25.6
14.8
39.2
22.7
45.6
26.4
47.1
27.2
60.6
35.0
72.6
41.9
83.8
48.5
99.2
57.4
133.2 77.0
*
All units are built for 3-phase, 50 Hz supply.
**
Based on an outdoor air dry bulb temperature of 35
°
C and an indoor air wet bulb temperature of 19
°
C.
***
Based on an outdoor air wet bulb temperature of 6
°
C and an indoor air dry bulb temperature of 21
°
C.
+
Based on an outdoor air dry bulb temperature of 46
°
C and an indoor air wet bulb temperature of 21
°
C.
++
Based on an outdoor air dry bulb temperature of 18
°
C.
Effective power input in accordance with EUROVENT.