7-2. Operation Data
<Cooling>
<Heating>
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent.
(Thermistor themometer)
2. Connecting piping condition : 5 m
Model name
Standard
Indoor
Outdoor
Compressor
pressure fan mode fan mode revolution
Indoor Outdoor P (MPa) T1 (°C) T2 (°C) (rps)
27/19 35/- 42NQV025H 0.9 to 1.1 12 to 14 37 to 39 High High 49
42NQV035M 0.8 to 1.0 11 to 13 39 to 41 High High 77
42NQV035H 0.8 to 1.0 11 to 13 46 to 48 High High 63
42NQV045M 0.7 to 0.9 10 to 12 47 to 49 High High 89
42NQV045H 0.8 to 1.0 11 to 13 40 to 42 High High 83
condition(°C)
Tempeature
Heat exchanger
pipe temp.
Model name
Standard
Indoor
Outdoor
Compressor
RAS-
pressure
fan mode
fan mode
revolution
Indoor
Outdoor
P (MPa)
T1 (°C)
T2 (°C)
(rps)
20/- 7/6 42NQV025H 2.5 to 2.7 39 to 41 0 to 3 High High 60
42NQV035M 2.7 to 2.9 43 to 45 0 to 2 High High 80
42NQV035H 2.6 to 2.8 41 to 43 0 to 2 High High 66
42NQV045M 2.5 to 2.7 39 to 41 0 to 2 High High 89
42NQV045H 2.7 to 2.9 43 to 45 0 to 2 High High 83
Tempeature
Heat exchanger
condition(°C)
pipe temp.
FILE NO. SVM-07013