DIAGNOSIS AND SOLUTION (CONT)
Open circuit or short circuit of temperature sensor diagnosis and solution (E4/E5/F1/F2/F3)
Error Code
E4/E5/F1/F2/F3
Malfunction decision conditions
If the sampling voltage is lower than 0.06V or higher than 4.94V, the LED displays the failure.
Supposed causes
S
Wiring mistake
S
Sensor faulty
S
PCB faulty
Troubleshooting
Check the connection
between the temperature
sensor and PCB.
Correct the connection
No
Yes
Replace indoor or outdoor
main PCB
Measure the resistance
value of the sensor
Replace the sensor
No
Yes
Fig. 35 – Check the connection
Summary of Contents for 38MHRB series
Page 7: ...7 DIMENSIONS OUTDOOR CONT Unit inch mm Fig 3 Size 24K...
Page 11: ...11 WIRING DIAGRAMS COOLING ONLY Fig 7 Wiring Diagram Size Cooling Only Size 12K 115V...
Page 12: ...12 WIRING DIAGRAMS COOLING ONLY CONTINUED Fig 8 Wiring Diagram Cooling Only Size 12K 230V...
Page 13: ...13 WIRING DIAGRAMS COOLING ONLY CONTINUED Fig 9 Wiring Diagram Cooling Only Sizes 18 24K...
Page 14: ...14 WIRING DIAGRAMS HEAT PUMP Fig 10 Wiring Diagram Heat Pump Size 12K 115V...
Page 15: ...15 WIRING DIAGRAMS HEAT PUMP CONTINUED Fig 11 Wiring Diagram Heat Pump Sizes 09 12 18 230V...
Page 16: ...16 WIRING DIAGRAMS HEAT PUMP CONTINUED Fig 12 Wiring Diagram Heat Pump Size 24 230V...
Page 37: ...37 DIAGNOSIS AND SOLUTION CONT Fig 36 P U Fig 37 P V...
Page 38: ...38 DIAGNOSIS AND SOLUTION CONT Fig 38 P W Fig 39 N U...
Page 39: ...39 DIAGNOSIS AND SOLUTION CONT Fig 40 N V Fig 41 N W...