background image

14                                                                 

Specifications subject to change without notice.                                                                         38MAR-04SI

Step 6 - Electrical Connections

Install All Power and Interconnecting Wiring to 
Outdoor Units

1. Mount the outdoor power disconnect.
2. Run the power wiring from the main box to disconnect per NEC

and local codes.

3. Remove the field wiring cover from the unit by loosening the

screws.

4. Remove the caps on the conduit panel. 
5. Connect the conduit to conduit panel (see Fig. 22).
6. Properly connect both the power supply and control lines to the

terminal block per the connection diagram for the appropriate unit

capacity and voltage.

7. Ground the unit in accordance with NEC and local electrical codes. 
8. Use the lock nuts to secure the conduit.
9. Reinstall the field wiring cover.

Fig. 22 —Field Wiring

WIRING

All wires must be sized per NEC (National Electrical Code) or CEC 
(Canadian Electrical Code) and local codes. Use Electrical Data table MCA 
(minimum circuit amps) and MOCP (maximum over current protection) to 
correctly size the wires and the disconnect fuse or breakers respectively.

Power and Communication Wiring:

 The main power is supplied to 

the outdoor unit. The field supplied 14/3 power/communication 
wiring, from the outdoor unit to the indoor unit, consists of four (4) 
wires and provides the power for the indoor unit. Two wires are high 
voltage AC power, one is communication wiring and the other is a 
ground wire.

To minimize communication interference:

 If installed in a high 

Electromagnetic field (EMF) area and communication issues arise, a 
14/2 stranded shielded wire can be used to replace 2 (L2/N) and 3 (S) 
between the outdoor and indoor units - landing the shield onto the 
ground in the outdoor unit only.

Table 9 — Wiring Sizes

NOTE: 

Matching with Conventional or Multi-Family Fan Coils 

requires separate power for the indoor and outdoor units. A 24V 
interface kit is required for compatibility. Refer to the 24V Interface 
Kit Installation Manual.

EQUIPMENT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage or 
improper operation.
Be sure to comply with local codes while running wire from 
indoor unit to outdoor unit. 
Every wire must be connected firmly. Loose wiring may cause the 
terminal to overheat or result in unit malfunction. A fire hazard 
may also exist. Therefore, ensure all wiring is tightly connected. 
No wire should be allowed to touch the refrigerant tubing, 
compressor or any moving parts. 
Disconnecting means must be provided and shall be located 
within sight and readily accessible from the air conditioner. 
Connecting cable with the conduit shall be routed through hole in 
the conduit panel.

CAUTION

Over

1.57" (40mm)

Terminal Block

Conduit panel

Conduit

Outdoor unit

CABLE

CABLE SIZE

REMARKS

Connection Cable

14AWG

3 wire + Ground 1

Φ

 208/230 V

(Stranded wire is recommended)

EQUIPMENT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage or
improper operation. Wires should be sized based on NEDC and
local codes.

WARNING

EQUIPMENT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage or
improper operation. Be sure to comply with local codes while
running wire from the indoor unit to the outdoor unit. Every wire
must be connected firmly. Loose wiring may cause the terminal to
overheat or result in unit malfunction. A fire hazard may also exist.
Ensure all wiring is tightly connected.
No wire should touch the refrigerant tubing, compressor or any
moving parts. Disconnecting means must be provided and shall be
located within sight and readily accessible from the air conditioner.
Connecting cable with conduit shall be routed through the hole in
the conduit panel.

CAUTION

Summary of Contents for 38MA R Series

Page 1: ...4 CLEARANCES 7 INSTALLATION REQUIREMENTS 8 INSTALLATION 8 Step 1 Check Equipment 8 Step 2 Mount Unit 8 Step 3 Condensate Drain Installation 9 Step 4 Refrigerant Piping 10 Step 5 Evacuate Coil And Tubi...

Page 2: ...ER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe...

Page 3: ...ries Fig 2 Outdoor Unit NOTE If the outdoor unit is higher than the indoor unit prevent rain from flowing into the indoor unit along the connection pipe by making a downward arc in the connection pipe...

Page 4: ...37 24 946 37 24 946 37 24 946 DEPTH D IN MM 13 11 333 13 11 333 13 11 333 14 17 360 16 14 410 16 14 410 16 14 410 L1 IN MM 20 24 514 20 24 514 20 24 514 21 26 540 26 50 673 26 50 673 26 50 673 L2 IN...

Page 5: ...ithout notice 5 DIMENSIONS CONT Fig 5 Size 18K 33 69 in 856mm 21 28 in 540mm 33 19 in 843mm 2 61 in 66mm 2 80 in 71mm 13 80 in 351mm 0 47 in 12mm 0 51 in 13mm 13 69 in 348mm 2 39 in 61mm 3 64 in 92mm...

Page 6: ...SI DIMENSIONS CONT Fig 6 Sizes 24K 30K and 36K 31 91 in 810mm 17 90 in 455mm 0 47 in 12mm 15 81 in 402mm 2 68 in 68mm 4 27 in 109mm 17 90 in 455mm 0 94 in 24mm 2 87 in 73mm 26 49 in 673mm 3 38 in 86mm...

Page 7: ...inlet Air outlet 59in 150cm or more when facing each other Blowing into the air inlet of other condenser shall be avoided 24in 60cm or more 59in 150cm or more on a multiple parallel unit arrangement 2...

Page 8: ...or details and PE Professional Engineer Certification if required For extreme outdoor conditions applications refer to the Cold ClimateApplication Guideline Ductless PRODUCT INSTALLATION Installation...

Page 9: ...NOTE Basepan built in with multiple holes for proper draining during defrost For applications where it is required to seal these holes and re direct the condensate drain rubber plugs are available th...

Page 10: ...25 7 5 25 7 5 25 7 5 25 7 5 25 7 5 Max Outdoor indoor height difference Ft m 32 10 32 10 32 10 65 20 65 20 82 25 82 25 Max Piping Length with no additional refrigerant charge Ft m 26 8 26 8 26 8 26 8...

Page 11: ...tial to achieving an airtight seal a After removing the burrs from the cut pipe seal the ends with PVC tape to prevent foreign materials from entering the pipe b Sheath the pipe with insulating materi...

Page 12: ...ng including the outdoor unit valves NOTE DO NOT open the service valves until pressure test is complete 7 Pressure Test Piping NOTE Use refrigeration gauges that are pressure rated for R410a refriger...

Page 13: ...the most positive way of assuring a system is free of air and moisture see Figure 20 Fig 20 Deep Vacuum Graph Triple Evacuation Method The triple evacuation method should be used when vacuum pump is...

Page 14: ...Conventional or Multi Family Fan Coils requires separate power for the indoor and outdoor units A 24V interface kit is required for compatibility Refer to the 24V Interface Kit Installation Manual EQU...

Page 15: ...7 MCA 15 9 9 18 20 20 25 Max Fuse CB AMP 20 15 15 25 30 30 35 Compressor Volts PH Hz 115 1 60 208 230 1 60 208 230 1 60 208 230 1 60 208 230 1 60 208 230 1 60 208 230 1 60 RLA 9 5 25 5 65 12 3 14 15 1...

Page 16: ...n this equipment Maintenance frequency may vary depending upon geographic areas TROUBLESHOOTING For ease of service the systems are equipped with diagnostic code display LEDs on both the indoor and ou...

Page 17: ...units F0 Protection of over current F1 Open circuit or short circuit of outdoor ambient temperature sensor T4 F2 Open circuit or short circuit of condenser coil temperature sensor T3 F3 Open circuit o...

Page 18: ...t indoor unit verified YES ______ NO ______ REMARKS _______________________________________________________________________________________________________ ____________________________________________...

Page 19: ...r Codes Were there any error codes present at start up YES ______ NO ______ Comments __________________________________________________________________________________________________________________...

Page 20: ...wood Parkway Atlanta GA 30339 Edition Date 06 20 Catalog No 38MAR 04SI Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurri...

Reviews: