background image

6

START-UP 
Preliminary Checks 

1. Check that all internal wiring connections are 
tight and that barriers, covers, and panels are in 
place. 
2. Make certain field electrical power source 
agrees with unit nameplate rating. 
3. Open all service valves. 

Leak Test— 

Field piping and fan coil must 

be leak tested by pressure method described in 
Carrier Standard Service Techniques Manual, 
Chapter 1, Section 1-6. Use R-22 at 
approximately 25 psig backed up with an inert 
gas to a total pressure not to exceed 245 psig. 

Evacuate and Dehydrate— 

Field piping 

and fan coil must be evacuated and dehydrated 
by either of the methods described in Carrier 
Standard Service Techniques Manual, Chapter 
1, Section 1-7. 

Charge System — 

Release factory charge 

into system by opening (backseating) liquid and 
suction line service valves. Add charge amount 
as required for the total system. 
Refer to separate indoor unit installation 
instructions for the required total system charge 
when connected to the indoor unit. 

PERCENTAGE DECREES IN CAPACITY DUE TO 

To Start Unit 

NOTE: When using in conjunction with FB4A 
Fan Coil, 42TX Fan Coil,40GKX Ceiling 
Cassette and 42S/HD Free Standing fan coils., 
refer to start-up instructions included with fan 
coil for correct start-up procedures. Be sure that 
field disconnect is closed. Set room thermostat 

below ambient temperature. Operate unit for 15 
minutes, then check system refrigerant charge. 
Unit compressor starts after a 5-minute delay if 
equipped with accessory Time Guard

t

II device. 

Table 6 - SYSTEM OPERATING CONDITIONS  

TEMPERATURE CONDITIONS 

LIMITS 

Maximum Cooling Ambient (F) 

125 

Minimum Cooling Ambient (F) (without 
accessory low-ambient kit) 

55 

Minimum Cooling ambient (F) (with 
accessory low-ambient kit) 

35 

Saturated Suction Temperature Range 
Minimum (F) / Maximum (F) 

20 / 55 

Saturated Condensing Temperature 
Range Minimum (F) / Maximum (F) 

60 / 150 

Maximum Compressor Discharge 
Temperature (F) 

275 

Minimum Discharge Superheat (F) 

60 

NOTE: For system controls see Electrical Data.

SERVICE

WARNING 

Before performing recommended maintenance, be 
sure unit main power switch is off. Failure to do so 
may result in electrical shock or injury from 
rotating fan blade. 

Outdoor Fan— 

A reinforced wire mount 

holds the outdoor fan assembly in place.  

Compressor Pressure Relief Valve — 

Valve is located in compressor. Relief valve 
opens at a pressure differential of approximately 
450 ± 50 psig between suction (low side) and 
discharge (high side) to allow pressure 
equalization. 

Internal Current and Temperature 
Sensitive Overload— 

Control resets 

automatically when internal compressor motor 
temperature drops to a safe level (overloads may 
require up to 45 minutes to reset). When an 
internal overload is suspected of being open, 
check by using an ohmmeter or continuity tester. 
If necessary, refer to Carrier Standard Systems 
Techniques Manual, Chapter 2, for complete 
information.

Pumpdown Procedure— 

The system 

may be pumped down in order to make repairs 
on low side without losing complete refrigerant 
charge. To pumpdown: 
1. Attach pressure gage to suction service valve 
gage port. 
2. Frontseat the liquid line valve.

CAUTION 

The 38HDL unit coils hold only the factory-
designated amount of refrigerant. Additional 
refrigerant may cause units to relieve pressure 
through compressor internal pressure relief 
valve (indicated by sudden rise of suction 
pressure) before suction pressure reaches 5 psig. 
If this occurs, shut off unit immediately, then 
frontseat the suction valve and remove and 
recover excess refrigerant following accepted 
practice. 

3. Start unit and run until suction pressure 
reaches 5 psig. 
4. Shut unit off and frontseat suction valve. 
5. Depressurize low side of unit and recover 
refrigerant following accepted practice.

Loss of Charge Pressure Switch 

This switch, mounted on the suction line, has 
fixed non-adjustable settings. To check pressure 
switch, attach pressure gage to suction service 
valve gage port. Slowly close liquid shutoff 
valve and allow compressor to pump down. Do 
not allow compressor to pump down below 2 
psig. Compressor should shut down when 
suction pressure drops to cutout pressure in 
Table 2, and should restart when pressure builds 
up to cut-in pressure shown in Table 2. 

High Pressure Switch 

—This switch, 

mounted on the discharge line, has fixed non-
adjustable settings & auto reset. To check 
pressure switch, attach pressure gauge to 

MAXIMUM LINE LENGTHS

UNIT

MAXIMUM

EQUIVALENT

FT

MAXIMUM LIFT

— FAN COIL

BELOW

CONDENSING

UNIT

MAXIMUM LIFT

— FAN COIL

ABOVE

CONDENSING

UNIT

38HK

50

30*

30*

*Maximum distance permitted is 30 ft from lowest
system component to highest system component. For
longer line application please refer to appendix A.

Summary of Contents for 38HQ 18-24

Page 1: ...vailable Read these instructions thoroughly Consult local building codes and National Electrical Code NEC for special installation requirements 38HK 18 70 50 60 Hz 1 6 Nomin Condensing Units 38HQ 18 2...

Page 2: ...Base Unit Dimensions 38H 018 036 6...

Page 3: ...Ft in mm 048 070 3 13 16 944 6 3 89 16 1131 9 1 51 16 433 4 1 67 16 468 3 2 61 2 774 7 1 75 8 498 5 1 75 8 498 5 2 55 8 752 5 NOTES 1 Required clearances with coil facing wall allow 8 in minimum clear...

Page 4: ...r 7 8 tube size 70 6 0 253 Scroll Matching Matrix 38HD SINGLE PHASE THREE PHASE FREQUENCY INDOOR UNIT SIZE 48 SIZE 60 SIZE 48 SIZE 60 FB4A 38HD48 3 CF 38HD60 3 CF 38HD48 5 CF 38HD60 5 CF FREE STAND 38...

Page 5: ...9 6 55 0 0 9 38HKC018DS30 220 1 60 9 6 55 0 0 9 24 38HKC024US30 220 1 60 12 5 60 0 0 9 38HKR024US30 220 1 60 10 1 53 0 0 9 38HKC024UP30 220 1 60 12 5 60 0 0 9 38HKC024DS30 220 1 60 12 5 60 0 0 9 30 38...

Page 6: ...units should be arranged in a way that no exhausted air will be sucked in as an intake for another unit Enough space should be kept Fig 3 lifting unit with sling Fig 5 Ground Mounting Fig 4 Wall Mount...

Page 7: ...rrupted unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur This ground may consist of electrical wire connected to the unit ground lug in con...

Page 8: ...ly in place Compressor Pressure Relief Valve Valve is located in compressor Relief valve opens at a pressure differential of approximately 450 50 psig between suction low side and discharge high side...

Page 9: ...be sureunit main power is off Failure to do so may result inelectrical shock or injury from rotating fan blades Lubrication COMPRESSOR Compressor contains factory oil charges replace oil when lost Se...

Page 10: ...16 Typical Wiring Schematic 38HK 18 36 50Hz 220 240V 1Ph 24V Control 220 240V 1Ph 220V Control...

Page 11: ...17 400V 3Ph 24V Control 400V 3Ph 220V Control Typical Wiring Schematic 38HK 48 60 50Hz...

Page 12: ...18 Typical Wiring Schematic 38HK 70 50Hz 400V 3Ph 24V Control...

Page 13: ...19 Typical Wiring Schematic Heat Pump 38HQ18 24...

Page 14: ...38HK HQ Typical Wiring Schematic 38HK 18 36 60Hz 220 240V 1Ph 24V Control 220 240V 1Ph 220V Control 16...

Page 15: ...Typical Wiring Schematic 38HK 48 70 60Hz 220V 1Ph 24V Control 220V 1Ph 220V Control 38HK HQ 17...

Page 16: ...38HK HQ Typical Wiring Schematic 38HK 48 70 60Hz Cont 220V 3Ph 24V Control 220V 3Ph 220V Control 18...

Page 17: ...Typical Wiring Schematic Heat Pump 38HQ18 24 38HK HQ 19...

Page 18: ...12 START UP CHECKLIST...

Page 19: ...SURE ACCURATER DEVICE IS INSTALLED IN FAN COIL UNIT _____ HAVE REFRIGERANT CONNECTIONS BEEN CHECKED FOR LEAKS Y N _____ IS CONDENSATE LINE CONNECTED Y N _____ DOES CONDENSATE LINE DRAIN FREELY Y N ___...

Page 20: ...CONDENSING UNIT DOES COMPRESSOR START AFTER INITIAL TIME DELAY AND RUN Y N _____ DOES OUTDOOR FAN RUN OR CYCLE ACCORDING TO SPACE REQUIREMENTS Y N _____ DE SELECT COOLING MODE AT INDOOR FAN COIL UNIT...

Page 21: ...15 Appendix...

Page 22: ...e the standard Installation Instructions This guideline is for standard single speed products For applications involving 2 speed products refer to Step 6 first NOTE The presale literature for outdoor...

Page 23: ...p to nearest common piston number found in Table 6 Step 4 Liquid Line Solenoid And Tubing Configuration There are 2 types of liquid line solenoids 1 for single flow applications and the other for bi f...

Page 24: ...14 18 22 NR NR 7 8 4 6 7 9 11 13 48 000 1 1 8 0 0 1 1 2 2 7 8 7 9 11 14 16 19 60 000 1 1 8 1 2 2 3 3 4 The estimated percentage of cooling capacity that must be subtracted from the Detailed Cooling C...

Page 25: ...19 Fig 1 Tube Bend Losses Table 3 Fitting Losses in Equivalent Ft REFERENCE DIAGRAM IN FIG 1 TUBE SIZE OD IN A B C 5 8 1 6 1 0 0 8 3 4 1 8 1 2 0 9 7 8 2 0 1 4 1 0 1 1 8 2 6 1 7 1 3 B 90 STD A 45 STD C...

Page 26: ...76 100 6 101 125 8 126 150 10 OUTDOOR UNIT BELOW INDOOR FT PISTON CHANGE 0 50 0 Table 6 Common Piston Sizes ACCURATER CHATLEFF ACCURATER CHATLEFF 32 65 65 33 67 67 35 35 68 36 70 70 37 71 38 38 73 73...

Page 27: ...sor maximum length is 105 Fig 2 Application with Air Conditioner Installed in a Horizontal Configuration 175 MAX GROUND LEVEL BASEMENT Note For Rotary Compressor maximum length is 105 Fig 3 Applicatio...

Page 28: ...22 HEAT PUMP ONLY 50 MAX GROUND LEVEL TRAP Note For Rotary Compressor maximum height is 30 Fig 4 Application with Air Conditioner or Heat Pump Installed with Indoor Unit above Outdoor Unit...

Page 29: ...23 HEAT PUMP ONLY 150 MAX Note For Rotary Compressor maximum height is 90 Fig 5 Application with Air Conditioner or Heat Pump Installed Above Indoor Unit...

Page 30: ...38HK 02 IOM 2011 Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations...

Reviews: