background image

5

microns to eliminate contamination and 
moisture in the system. 
Run refrigerant tubes as directly as possible, 
avoiding unnecessary turns and bends. Suspend 
refrigerant tubes so they do not damage 
insulation on vapor tube and do not transmit 
vibration to the structure. Also, when passing 
refrigerant tubes through the wall, seal opening 
so that vibration is not transmitted to structure. 
Leave some slack in refrigerant tubes between 
structure and outdoor unit to absorb vibration. 
Refer to separate indoor unit installation 
instructions for additional information. 

MAKE PIPING SWEAT CONNECTIONS—
Remove plastic caps from liquid and suction 
service valves. Use refrigerant grade tubing. 
Service valves are closed from the factory and 
ready for brazing. After wrapping the service 
valve with a wet cloth, the tubing set can be 
brazed to the service valve using either silver 
bearing or non-silver bearing brazing material. 
Consult local code requirements. Refrigerant 
tubing and indoor coil are ready for leak testing. 
NOTE: Unit is shipped with R-22 Holding 
factory charge indicated on nameplate. Pass 
nitrogen or other inert gas through piping while 
brazing to prevent formation of copper oxide. 

CAUTION 

To avoid damage while brazing, service valves 
should be wrapped in a heat-sinking material 
such as a wet cloth. 

CAUTION 

When brazing tubing sets to the service valves, a 
brazing shield must be used to prevent damage 
to the painted unit surface. 

PROVIDE SAFETY RELIEF—A fusible plug 
is located in unit suction line; do not cap this 
plug. If local code requires additional safety 
devices, install as directed. 

Step 4 — Make Electrical 
Connections

CAUTION 

Unit failure as a result of operation on improper 
line voltage or excessive phase imbalance 
constitutes abuse and may cause damage to 
electrical components. Such operation will 
invalidate any applicable Carrier warranty. 

WARNING 

Unit cabinet must have an uninterrupted, 
unbroken electrical ground to minimize the 
possibility of personal injury if an electrical fault 
should occur. This ground may consist of 
electrical wire connected to the unit ground lug 
in control compartment, or conduit approved for 
electrical ground when installed in accordance 
with NEC, ANSI/NFPA (American National 
Standards Institute/National Fire Protection 
Association) 70, and local electrical codes. 
Failure to follow this warning could result in the 
installer being liable for personal injury to others. 

POWER WIRING—Unit is factory-wired for 
voltage shown on nameplate. Provide adequate, 
fused disconnect switch within sight of unit, 
readily accessible but out of reach of children. 
Provision for locking the switch open (off) is 
advisable to prevent power from being turned on 
while unit is being serviced. Disconnect switch, 
fuses, and field wiring must be in compliance 
with NEC and applicable local codes. Use 
minimum 60 C wire for field power connection. 
Route power wires through opening in the unit 
side panel and connect in unit control box. Unit 
must be grounded. 
CONTROL CIRCUIT WIRING — See 
Electrical Data Table and unit label diagram for 
field-supplied wiring details. Route control wire 
through opening in the unit side panel to 
connection in unit control box. 
NOTE: Use no. 10 AWG (American Wire Gage) 
insulated wire 
NOTE: Operation of unit on improper line 
voltage constitutes abuse and could affect 
Carrier warranty. See Table7. 
Do not install unit in system where voltage may 
fluctuate above or below permissible limits. 
See Table 7 for recommended fuse sizes. When 
making electrical connections, provide clearance 
at unit for refrigerant piping connections. 

WARNING 

Before performing service or maintenance, be 
sure the indoor unit main power switch is off 
and indoor blower has completely stopped. 
Failure to do so may result in electrical shock or 
injury from rotating fan blades. 

CONNECTIONS TO DUCT-FREE FAN COIL 
UNITS —  
The 38HD units are designed for easy match-up 
to FB4A Fan Coil, 42TX Fan Coil,40GKX 
Cealling Cassette and 42S/HD Free Standing fan 
coils. See wiring diagrams page 9 – 11. 

Summary of Contents for 38HQ 18-24

Page 1: ...vailable Read these instructions thoroughly Consult local building codes and National Electrical Code NEC for special installation requirements 38HK 18 70 50 60 Hz 1 6 Nomin Condensing Units 38HQ 18 2...

Page 2: ...Base Unit Dimensions 38H 018 036 6...

Page 3: ...Ft in mm 048 070 3 13 16 944 6 3 89 16 1131 9 1 51 16 433 4 1 67 16 468 3 2 61 2 774 7 1 75 8 498 5 1 75 8 498 5 2 55 8 752 5 NOTES 1 Required clearances with coil facing wall allow 8 in minimum clear...

Page 4: ...r 7 8 tube size 70 6 0 253 Scroll Matching Matrix 38HD SINGLE PHASE THREE PHASE FREQUENCY INDOOR UNIT SIZE 48 SIZE 60 SIZE 48 SIZE 60 FB4A 38HD48 3 CF 38HD60 3 CF 38HD48 5 CF 38HD60 5 CF FREE STAND 38...

Page 5: ...9 6 55 0 0 9 38HKC018DS30 220 1 60 9 6 55 0 0 9 24 38HKC024US30 220 1 60 12 5 60 0 0 9 38HKR024US30 220 1 60 10 1 53 0 0 9 38HKC024UP30 220 1 60 12 5 60 0 0 9 38HKC024DS30 220 1 60 12 5 60 0 0 9 30 38...

Page 6: ...units should be arranged in a way that no exhausted air will be sucked in as an intake for another unit Enough space should be kept Fig 3 lifting unit with sling Fig 5 Ground Mounting Fig 4 Wall Mount...

Page 7: ...rrupted unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur This ground may consist of electrical wire connected to the unit ground lug in con...

Page 8: ...ly in place Compressor Pressure Relief Valve Valve is located in compressor Relief valve opens at a pressure differential of approximately 450 50 psig between suction low side and discharge high side...

Page 9: ...be sureunit main power is off Failure to do so may result inelectrical shock or injury from rotating fan blades Lubrication COMPRESSOR Compressor contains factory oil charges replace oil when lost Se...

Page 10: ...16 Typical Wiring Schematic 38HK 18 36 50Hz 220 240V 1Ph 24V Control 220 240V 1Ph 220V Control...

Page 11: ...17 400V 3Ph 24V Control 400V 3Ph 220V Control Typical Wiring Schematic 38HK 48 60 50Hz...

Page 12: ...18 Typical Wiring Schematic 38HK 70 50Hz 400V 3Ph 24V Control...

Page 13: ...19 Typical Wiring Schematic Heat Pump 38HQ18 24...

Page 14: ...38HK HQ Typical Wiring Schematic 38HK 18 36 60Hz 220 240V 1Ph 24V Control 220 240V 1Ph 220V Control 16...

Page 15: ...Typical Wiring Schematic 38HK 48 70 60Hz 220V 1Ph 24V Control 220V 1Ph 220V Control 38HK HQ 17...

Page 16: ...38HK HQ Typical Wiring Schematic 38HK 48 70 60Hz Cont 220V 3Ph 24V Control 220V 3Ph 220V Control 18...

Page 17: ...Typical Wiring Schematic Heat Pump 38HQ18 24 38HK HQ 19...

Page 18: ...12 START UP CHECKLIST...

Page 19: ...SURE ACCURATER DEVICE IS INSTALLED IN FAN COIL UNIT _____ HAVE REFRIGERANT CONNECTIONS BEEN CHECKED FOR LEAKS Y N _____ IS CONDENSATE LINE CONNECTED Y N _____ DOES CONDENSATE LINE DRAIN FREELY Y N ___...

Page 20: ...CONDENSING UNIT DOES COMPRESSOR START AFTER INITIAL TIME DELAY AND RUN Y N _____ DOES OUTDOOR FAN RUN OR CYCLE ACCORDING TO SPACE REQUIREMENTS Y N _____ DE SELECT COOLING MODE AT INDOOR FAN COIL UNIT...

Page 21: ...15 Appendix...

Page 22: ...e the standard Installation Instructions This guideline is for standard single speed products For applications involving 2 speed products refer to Step 6 first NOTE The presale literature for outdoor...

Page 23: ...p to nearest common piston number found in Table 6 Step 4 Liquid Line Solenoid And Tubing Configuration There are 2 types of liquid line solenoids 1 for single flow applications and the other for bi f...

Page 24: ...14 18 22 NR NR 7 8 4 6 7 9 11 13 48 000 1 1 8 0 0 1 1 2 2 7 8 7 9 11 14 16 19 60 000 1 1 8 1 2 2 3 3 4 The estimated percentage of cooling capacity that must be subtracted from the Detailed Cooling C...

Page 25: ...19 Fig 1 Tube Bend Losses Table 3 Fitting Losses in Equivalent Ft REFERENCE DIAGRAM IN FIG 1 TUBE SIZE OD IN A B C 5 8 1 6 1 0 0 8 3 4 1 8 1 2 0 9 7 8 2 0 1 4 1 0 1 1 8 2 6 1 7 1 3 B 90 STD A 45 STD C...

Page 26: ...76 100 6 101 125 8 126 150 10 OUTDOOR UNIT BELOW INDOOR FT PISTON CHANGE 0 50 0 Table 6 Common Piston Sizes ACCURATER CHATLEFF ACCURATER CHATLEFF 32 65 65 33 67 67 35 35 68 36 70 70 37 71 38 38 73 73...

Page 27: ...sor maximum length is 105 Fig 2 Application with Air Conditioner Installed in a Horizontal Configuration 175 MAX GROUND LEVEL BASEMENT Note For Rotary Compressor maximum length is 105 Fig 3 Applicatio...

Page 28: ...22 HEAT PUMP ONLY 50 MAX GROUND LEVEL TRAP Note For Rotary Compressor maximum height is 30 Fig 4 Application with Air Conditioner or Heat Pump Installed with Indoor Unit above Outdoor Unit...

Page 29: ...23 HEAT PUMP ONLY 150 MAX Note For Rotary Compressor maximum height is 90 Fig 5 Application with Air Conditioner or Heat Pump Installed Above Indoor Unit...

Page 30: ...38HK 02 IOM 2011 Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations...

Reviews: