background image

MANDATORY START-UP CHECK LIST AND RECORD

Yes

No

NA

Yes

No

NA

Indoor Entering Air dB(Dry Bulb) Temp
Indoor Leaving Air dB(Dry Bulb) Temp
Indoor Entering Air wB(Wet Bulb) Temp
Indoor Leaving Air wB(Wet Bulb) Temp

Fan System

Does the power supply match the fan coil unit data plate?
Is ground wire connected?

Are air filters in place and clean?

Technician Name, Signature and Date:

Leaving  Outdoor Air Temp

Unit Amps(L1/L2/L3)

Vapor Line Pressure
Vapor Line Temp

Voltage (L1/L2/L3)

Does fan rotate freely?

Startup Date:

Indoor Model Number:

Liquid Line Temp
Entering Outdoor Air Temp

Outdoor Unit

Select cooling mode and adjust set point, it must be below current room temperature then observe unit operation.

After atleast 15 minutes of running time, record all the information below:

Select fan mode, then initiate test sequence. Does the  fan motor start at low speed , then shift to medium then to high?

Start System Operation at the Fan Coil Unit

Does compressor start (After Initial Time Delay) and Run?
Does outdoor fan run properly?

Fan Coil Unit

                             Start-Up Checklist

Indoor Power Supply

Check Indoor Fan Operation Under Ceiling Fan Coil Units

Outdoor Serial Number:

Are control power lines connected to there control power terminal block?
Are terminal snug in the housing?

Are fresh batteries installed in the fan coil remote controller?
Does remote controller backlight illuminate when the button is pressed?

Are control power lines and control cables routed separately (Not in the same conduit and not in same multi-conductor cable?
Are control wires connected to the same circuit as associated refrigerant lines?
Check to make sure the subbase mounting to wall is secure? ( Don’t apply excessive force to mounting screw)

Are the refrigerant connections properly connected and have been checked for leakages?

Controls

TE

AR A

LO

NG

 T

HE

 DO

TT

ED L

INE

Have all the refrigerant connections and piping joints checked for leaks and vacuum test conducted to 500 micron?

                                    Pre-Start-Up Checklist

Is there any shipping damage?

Has the ground wire been properly connected?
Are the circuit protection matched with the unit size and installed properly?
Are the power wire guage matched with the unit size and installed properly?

Are both refrigerant lines flushed / cleaned, connected to service valve sets and properly tightend?

Outdoor Unit

Check power supply to see if it matches the unit data plate?

Are all the service valves open and backseated ?
Are the Stem Valves Installed and snug?

Check accurater device size is matched and installed in fan coil unit? (If Applicable)

IMPORTANT!

This page is a mandatory checklist & record – the check to be executed and data to be recorded for future reference incase of failure.

A copy of this checklist data has to be submitted to carrier representative. Completion of this checklist is a must for any field claim, no field support will be provided for 

incomplete or blank checklists.

Is condensate line connected?
Is the condensate line free from obstacle and drains freely?

Will this damage prevent the unit start-up?

If the unit is damaged, Please specifiy where:

                   Preliminary Information

Piping

Indoor Fan Coil Unit Piping

Indoor Serial Number:

Technician Name:

Additional Accessories:

Customer Name/Address:

Project Name:

Outdoor Model Number:

Page 19 of 20

Summary of Contents for 38CKPC18DS70

Page 1: ...nominal cooling capacity range from 1 5 to 5 0 Tons Each unit is designed to occupy a minimum space No complex system controls are required for Carrier fan coil units Piping drain and wiring connecti...

Page 2: ...lt in severe personal injury of death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or...

Page 3: ...8CKPC24DS70 FB4PSSF024000E 38PKC24DS70 FB4PSSF030000E 38CKPS30DS70 FB4PSSF030000E 38PKS30DS70 FB4PSSF036000E 38CKPC36DS70 FB4PSSF036000E 38PKS36DS90 FB4PSSF036000E 38CKPC36DS90 FB4PSSF048000E 38PKS48D...

Page 4: ...5 16 312 7 10 7 16 265 1 024 Slope 42 11 16 1084 3 14 5 16 363 5 12 7 16 316 0 12 5 16 312 7 10 7 16 265 1 030 Slope 47 11 16 1211 5 17 5 8 447 5 15 3 4 400 1 15 5 8 396 9 15 3 8 390 5 036 Slope 49 5...

Page 5: ...site Check all critical dimensions such as pipe wire and duct connection requirements Refer to job drawings and product dimension drawings as required Instruct all trades in their part of the installa...

Page 6: ...low Installation In this application field conversion of the evaporator coil is required using accessory downflow kit Along with an accessory base kit See installation instructions packaged with acces...

Page 7: ...support rail on right side of unit 6 Convert air seal assembly for horizontal right a Remove air seal assembly from coil by removing 4 screws b Remove air splitter B from coil seal assembly by removi...

Page 8: ...Fig 3 Removal of Brackets on Modular Unit Fig 4 Conversion for Horizontal Right Applications Using a Slope Coil Page 8 of 20...

Page 9: ...ibrous glass ducts Both acoustical lining and fibrous ductwork shall comply with National Fire Protection Association as tested by UL Standard IK I for Class I air ducts Make Electrical Connections Re...

Page 10: ...ant Flow Control Device Fig 7 Recommended Condensate Trap Wiring diagrams shown depict typical control functions Refer to unit wiring label for specific functions IMPORTANT If a disconnect switch is t...

Page 11: ...living space where damage may result from condensate overflow a field supplied external condensate pan should be installed underneath the entire unit and a secondary condensate line with appropriate...

Page 12: ...rature as set Upon setting the desired room temperature the system will maintain the room temperature Cool Mode If the room temperature is higher than the setting the compressor will automatically tur...

Page 13: ...p automatically the air conditioner after certain set OFF time ON Timer Function to start automatically the air conditioner after certain set ON time Timer setting is 1 Hour to 24 Hour The timer led w...

Page 14: ...ere is power to the system regardless of a demand call Applying incorrect high voltage to the X13 motor may cause the motor to not operate or even damage the motor If this voltage is missing fix the p...

Page 15: ...ges All units are not equipped with electric heater package A factory approved field installed UL listed heater package is available from your equipment supplier See unit rating plate for a list of fa...

Page 16: ...cloth Clean or Replace Air Filters Lock open and tag unit electrical service switch At the start of each cooling season and after each month of operation more or less depending on operating condition...

Page 17: ...e filter driers with rated working pressures less than 600 psig Do not leave R 410A refrigerant suction line filter driers in line longer than 72 hours Do not install a suction line filter drier in li...

Page 18: ...NON CONDENSABLES IN SYSTEM LOW REFRIGERANT CHARGE LINE VOLTAGE TOO HIGH OR LOW DEFECTIVE RUN CAPACITOR COMPRESSOR BEARINGS HIGH SUPERHEAT LOOSE LEAD AT FAN MOTOR MOTOR DEFECTIVE LOW SUCTION PRESSURE...

Page 19: ...trol wires connected to the same circuit as associated refrigerant lines Check to make sure the subbase mounting to wall is secure Don t apply excessive force to mounting screw Are the refrigerant con...

Page 20: ...to discontinue or change at any time specifications or designs without notice and without incurring any obligations Supersedes Version FB4P 50HZ IOM09 Catalog Number FB4P 50HZ IOM10 Effective Date 26...

Reviews: