6.) The solenoid valve is to be installed a maximum of 2 ft
from indoor coil.
Avoid valve damage while brazing by wrapping valve with a
heat-sinking material such as a wet cloth.
3. Braze valve onto end of liquid tube using silver bearing or
non-silver bearing brazing material. Consult local code re-
quirements.
4. Braze flare adapter onto outlet end of solenoid valve.
5. Wire solenoid coil into system control circuit.
Fig. 6—Solenoid Valve Installation
A87044
ELECTRICAL JUNCTION
ELECTRICAL COIL
VALVE
FLOW ARROW
STRAIGHT
3
/
8
IN. STUD
NOTE: System flow direction
must match arrow on
bottom of body.