background image

F.   Metering Device — Long Line Cooling

 

In  current  equipment,  all  indoor  units  use  a  TXV  with 15 to 30% bleed  for  metering  in  the  cooling  mode.    This  provides  adequate 

refrigerant migration protection  for all cooling applications.

 

G.  Piston Sizing — Heat Pumps Only

 

An AccuRater

TM

 

(fixed  orifice)  is used for refrigerant  metering  in the heating  mode.   This fixed  expansion  device  must be changed  from 

the factory- supplied AccuRater

TM

  based  on indoor/outdoor  vertical  separation  and  system  capacity.   For horizontal  applications  up to

 

200 ft (61 m) linear length and 250 ft (76 m) total equivalent length, no heating piston change is necessary.

 

When  sizing  the  heating  piston  for  installations  where  the  outdoor  unit  is  below  the  indoor  unit,  use  Table  9.  When  outdoor  unit  is 

located above indoor unit, use Table 12.

 

Example:    The  factory  supplied AccuRater

TM

 

for  a  single- stage  3- ton  heat  pump  is  a  number  57.    A  system  is  installed with  200

 

equivalent ft of line set.  Approximately  60 ft (18.3 m) is horizontal and the outdoor unit is 140 ft (42.7 m) above the indoor unit.  Table

 

9 shows  the AccuRater

TM

 

piston  change  to be +6. The new  piston  size is 57 + 6 = 63.   If a 63 is not produced,  round  up to the next

 

larger available piston size.

 

On the same heat pump, if the outdoor unit was located 49 ft (14.9 m) below the indoor unit, Table 10 shows the piston change to be 57

 

-  2 = 55. If a 55 piston is not produced, round up to the next available size.

 

H.  Liquid Line Solenoid — Long Line Heat Pump Heating

 

Since AccuRater

TM

 

do not provide off- cycle refrigerant  migration  protection  in the heating  mode, a liquid line solenoid  is required  for

 

single-stage  and  two- stage  heat  pump  long  line  applications.    Bi-flow  solenoid  valves  provide  flow  control  protection only  in  the 

direction  of  the  arrow  molded  into  the  valve. 

 The

 

arrow

 

must

 

point

 

toward

 

the

 

outdoor

 

unit 

for  off- cycle  refrigerant  control  in  the 

heating  mode.  The  arrow  shows  the  direction  of  flow  control.  The  solenoid  should  be  installed  within  2  ft.  of  the  outdoor  unit.  The 

liquid line solenoid kit number for a heat pump is KHALS0401LLS.

 

NOTE: 

Equivalent  length of the liquid line solenoid should be added to the total equivalent length of the tubing. See Table 2.

 

I.   Charging  Information

 

Use  subcooling  as  the  primary  method  for  charging  longline  applications.  Outdoor  units  are  pre- charged  for  15  ft (4.6  m)  of  3/8  liquid 

line.   When  using  different  length  diameter  liquid  lines,  charge  adjustments  are  required.  See  Table  4  for  charge  adjustments  required. 

The charge adjustment  will depend on the liquid line diameter used. See unit installation  instructions  for proper charging procedure.

 

For all long line applications,  pressure  drop and subcooling  loss become  a concern.  In these applications,  a 

minimum  of 10

°

F (5.6°C) of 

subcooling  

is  required  for  all  liquid  line  diameters   to  ensure  no  refrigerant   flashing   occurs  before  the  TXV  metering   device. 

Systems should be charged to 10°

_

 subcooling or the rating plate subcooling, whichever is greater.

 

The  amount  of  factory- charge  can  be  found  on  the  unit  rating  plate  or  in  the  Product  Data  literature.   Long  line  applications  do  not 

require additional oil charge.

 

 
VAPOR LINE SIZING AND COOLING CAPACITY LOSS

 

Acceptable  vapor line diameters  provide adequate oil return to the compressor  while avoiding excessive capacity loss. The suction line 

diameter shown in Table 3 is acceptable for AC and HP systems w i t h  Puron refrigerant:

 

 

Table 3 -  Vapor Line Sizing and Cooling Capacity Losses — Puron®

 

Refrigerant 1- Stage Air Conditioner Applications

 

 

Unit 

Nominal 

Size (Btuh)

 

Maximum 

Liquid Line 

Diameters 

(In.  OD)

 

Vapor Line 

Diameters 

(In.  OD)

 

Cooling  Capacity  Loss (%)  Total 

Equivalent  Line Length ft. (m)

 

26 --- 50

 

(7.9 --- 15.2)

 

51 --- 80

 

(15.5 --- 24.4)

 

81 --- 100

 

(24.7 --- 30.5)

 

101 --- 125

 

(30.8 --- 38.1)

 

126 --- 150

 

(38.4 --- 45.7)

 

151 --- 175

 

(46.0 --- 53.3)

 

176 --- 200

 

(53.6 --- 61.0)

 

201 --- 225

 

(61.3 --- 68.6)

 

226 --- 250

 

(68.9 --- 76.2)

 

18000

 

1 Stage 

AC with 

Puron

 

 

3/8

 

1/2

 

1

 

2

 

3

 

5

 

6

 

7

 

8

 

9

 

11

 

5/8

 

0

 

1

 

1

 

1

 

2

 

2

 

2

 

3

 

3

 

3/4

 

0

 

0

 

0

 

0

 

1

 

1

 

1

 

1

 

1

 

24000

 

1 Stage 

AC with 

Puron

 

 

3/8

 

5/8

 

0

 

1

 

2

 

2

 

3

 

3

 

4

 

5

 

5

 

3/4

 

0

 

0

 

1

 

1

 

1

 

1

 

1

 

2

 

2

 

7/8

 

0

 

0

 

0

 

0

 

0

 

1

 

1

 

1

 

1

 

30000

 

1 Stage 

AC with 

Puron

 

 

3/8

 

5/8

 

1

 

2

 

3

 

3

 

4

 

5

 

6

 

7

 

8

 

3/4

 

0

 

0

 

1

 

1

 

1

 

2

 

2

 

2

 

3

 

7/8

 

0

 

0

 

0

 

0

 

1

 

1

 

1

 

1

 

1

 

36000

 

1 Stage 

AC with 

Puron

 

 

3/8

 

5/8

 

1

 

2

 

4

 

5

 

6

 

8

 

9

 

10

 

12

 

3/4

 

0

 

1

 

1

 

2

 

2

 

3

 

3

 

4

 

4

 

7/8

 

0

 

0

 

0

 

1

 

1

 

1

 

1

 

2

 

2

 

42000

 

1 Stage 

AC with 

Puron

 

 

3/8

 

3/4

 

0

 

1

 

2

 

2

 

3

 

4

 

4

 

5

 

6

 

7/8

 

0

 

0

 

1

 

1

 

1

 

2

 

2

 

2

 

3

 

1 1/8

 

0

 

0

 

0

 

0

 

0

 

0

 

0

 

0

 

0

 

48000

 

1 Stage 

AC with 

Puron

 

 

3/8

 

3/4

 

0

 

1

 

2

 

3

 

4

 

5

 

5

 

6

 

7

 

7/8

 

0

 

0

 

1

 

1

 

2

 

2

 

2

 

3

 

3

 

1 1/8

 

0

 

0

 

0

 

0

 

0

 

0

 

0

 

1

 

1

 

60000

 

1 Stage 

AC with 

Puron

 

 

3/8

 

3/4

 

1

 

2

 

4

 

5

 

6

 

7

 

9

 

10

 

11

 

7/8

 

0

 

1

 

2

 

2

 

3

 

4

 

4

 

5

 

5

 

1 1/8

 

0

 

0

 

0

 

1

 

1

 

1

 

1

 

1

 

1

 

  

Applications

 

in

 

this

 

area

 

may

 

be

 

long

 

line

 

and

 

may

 

have

 

height

 

restrictions.

  

 

Page 26

Summary of Contents for 38C Series

Page 1: ...ries energy efficient split top discharge condensing units incorporate innovative technology to provide reliable summer cooling performance The units are pre wired pre charged with Puron R 410A refrig...

Page 2: ...the potential for personal injury Understand the signal words DANGER WARNING CAUTION and NOTE These words are used with the safety alert symbol DANGER identifies the most serious hazards which will re...

Page 3: ...frigerant Charge kg 2 31 2 44 3 12 4 05 4 17 4 52 Connection Type Liquid Line Vapour Line Max Length ft Max Lift ft Outdoor Fan Motor Type Motor Voltage RPM CFM Diameter No Blades Motor Horsepower Con...

Page 4: ...393 7 349 2 36 792 2 981 1 98 4 19 0 166 7 627 1 231 8 74 6 15 9 406 4 393 7 393 7 42 792 2 722 3 98 4 22 2 166 7 627 1 231 8 74 6 15 9 406 4 393 7 323 8 48 792 2 722 3 98 4 22 2 166 7 627 1 231 8 74...

Page 5: ...07 4 115 8 929 4 115 5 5 6 5 38CKPS48DS40 42TPM048 11 415 3 50 Ducted 47 500 43 000 12 2 9 0 3 893 4 778 10 511 4 778 6 6 7 8 38CKPS60DS40 42TPM060 11 415 3 50 Ducted 60 000 51 000 11 8 8 3 5 085 6 14...

Page 6: ...Typical Wiring Schematic 38CKP18 24 30 36 230V 240V 1PH 50Hz Ducted 38CKP36 42 48 60 400V 415V 3PH 50Hz Ducted Page 6...

Page 7: ...Typical Wiring Schematic Continued 38CKP36 42 48 60 400V 415V 3PH 50Hz Ducted With Capacitor Bank Page 7...

Page 8: ...nit operation sound may disturb customer 2 Insure that vapor and liquid tube diameters are appropriate to capacity of unit 3 Run refrigerant tubes as directly as possible by avoiding unnecessary turns...

Page 9: ...rovisions are made for water drainage and noise vibration dampening Rigging Keep unit upright Lift unit using sling Use cardboard or padding under sling and spreader bars to prevent sling damage to un...

Page 10: ...nnecessary turns and bends Suspend refrigerant tubes so they do not damage insulation on vapor tube and do not transmit vibration to the structure Also when passing refrigerant tubes through the wall...

Page 11: ...uate above or below permissible limits When making electrical connections provide clearance at unit for refrigerant piping connections NOTE Use copper wires only between disconnect switch and unit NOT...

Page 12: ...the Pre startup and Startup included with the fan coil units for correct start up procedures Be sure that field disconnect is closed Set room thermostat below ambient temperature Operate unit for 15 m...

Page 13: ...nts from drier into the system Loss of Charge Pressure Switch This switch mounted on the suction line has fixed non adjustable settings To check pressure switch attach pressure gage to suction service...

Page 14: ...den hose or other suitable equipment to flush coil from the outside to remove dirt Be sure to flush all dirt and debris from drain holes in the base of unit Fan motors are waterproof Leak Detection Ne...

Page 15: ...4 liquid line What charge adjustment is required Formula 27 oz ft x 25ft 13 5 oz 6 75 oz 8 0 g m x 7 6 m 382 7 g 321 9 g Net result is to remove 6 75 oz of refrigerant from the system Example 2 System...

Page 16: ...9 4 10 6 11 7 12 8 13 9 4 6 1 7 2 8 3 9 4 10 6 11 7 12 8 13 9 15 0 6 7 2 8 3 9 4 10 6 11 7 12 8 13 9 15 0 16 1 7 8 3 9 4 10 6 11 7 12 8 13 9 15 0 16 1 17 2 8 9 4 10 6 11 7 12 8 13 9 15 0 16 1 17 2 18...

Page 17: ...262 86 9 364 110 0 466 128 7 596 148 4 60 8 6 162 57 0 264 87 4 366 110 4 468 129 0 600 149 0 62 10 0 164 57 7 266 87 9 368 110 8 470 129 3 604 149 5 64 11 3 166 58 4 268 88 4 370 111 2 472 129 7 608...

Page 18: ...26 335 90 92 94 96 88 90 92 94 86 88 90 92 84 86 88 90 82 84 86 88 80 82 84 86 345 354 364 374 98 100 102 104 96 98 100 102 94 96 98 100 92 94 96 98 90 92 94 96 88 90 92 94 384 395 406 416 106 108 110...

Page 19: ...filter driers in line longer than 72 hours Do not install a suction line filter drier in liquid line POE oils absorb moisture rapidly Do not expose oil to atmosphere POE oils may cause damage to certa...

Page 20: ...OR NON CONDENSABLES IN SYSTEM LOW REFRIGERANT CHARGE LINE VOLTAGE TOO HIGH OR LOW DEFECTIVE RUN CAPACITOR COMPRESSOR BEARINGS HIGH SUPERHEAT LOOSE LEAD AT FAN MOTOR MOTOR DEFECTIVE LOW SUCTION PRESSU...

Page 21: ...control wires connected to the same circuit as associated refrigerant lines Check to make sure the subbase mounting to wall is secure Don t apply excessive force to mounting screw Are the refrigerant...

Page 22: ...NOTES Page 22...

Page 23: ...used to highlight suggestions which will result in enhanced installation reliability or operation WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or deat...

Page 24: ...mode thus in some cases heat pumps have additional line set limitations from air conditioning units Table 3 in this guideline can be used to properly size suction lines Follow all suction line sizing...

Page 25: ...tdoor units Equivalent length takes into account pressure losses from both tubing length and losses due to fittings and accessories such as elbows liquid line solenoid and filter drier Losses from fit...

Page 26: ...nformation Use subcooling as the primary method for charging longline applications Outdoor units are pre charged for 15 ft 4 6 m of 3 8 liquid line When using different length diameter liquid lines ch...

Page 27: ...le 6 Vapor line should slope towards indoor unit Maximum actual liquid line is up to 100 61 m See Table 5 Maximum total equivalent length is up to 120 76 2 m See Table 5 Heat pump only Bi flow liquid...

Page 28: ...150 150 150 150 150 150 AC HP 3 8 150 150 150 150 150 150 150 150 150 24000 AC Only 1 4 75 75 75 50 50 AC Only 5 16 150 150 150 150 150 150 150 125 100 AC HP 3 8 150 150 150 150 150 150 150 150 150 30...

Page 29: ...9 15 2 51 75 15 5 22 9 76 100 23 2 30 5 101 125 30 8 38 1 18000 AC Only 1 4 150 150 150 150 150 AC Only 5 16 150 150 150 150 150 AC HP 3 8 150 150 150 150 150 24000 AC Only 1 4 100 125 150 150 150 AC...

Page 30: ...ss than 20 ft 6 1 m vertical separation Outdoor unit BELOW indoor unit See Tables 6 8 and 11 for longline thresholds An inverted vapor line trap must be installed at indoor unit The top peak of trap m...

Page 31: ...Page 31...

Page 32: ...ts to discontinue or change at any time specifications or designs without notice and without incurring any obligations Supersedes Version 38C 50Hz IOM 01 Catalog Number 38C 50 EN IOM 02 Effective Date...

Reviews: