background image

Assuming that a system is pressurized with either all refrigerant or a mixture of nitrogen and refrigerant, leaks in the 

system can be found with an electronic leak detector that is capable of detecting HFC refrigerant. If system has been 
operating for some time, make first check for a leak visually. Since refrigerant carries a small quantity of oil, traces of 

oil at any joint or connection is an indication that refrigerant is leaking at that point. A simple and inexpensive method 

of testing for leaks is to use soap bubbles. Any solution of water and soap may be used.  Soap solution is applied to 

all joints and connections in system. A small pinhole leak is located by tracing bubbles in soap solution around leak. 

If the leak is very small, several minutes may pass before a bubble will form.  

R-410A Refrigerant Charging — Refer to unit information plate for superheat charging procedure. 

R-410A 

refrigerant cylinders contain a dip tube which allows liquid refrigerant to flow from cylinder in upright 

position

. Charge R-410A units with cylinder in upright position and a commercial type metering device in the 

manifold hose. Charge refrigerant into suction-line. For all approved combinations, system must be charged correctly 

for normal system operation and reliable operation of components. If system has lost all charge, weigh in charge 

using dial-a-charge designed for R-410A refrigerant or digital scale. System charge should be fine-tuned by using 

superheat method. 

 

CHECK CHARGE 

Factory charge amount is shown on unit rating plate. 

Cooling Only Procedure 

NOTE: If superheat or subcooling charging conditions are not favorable, charge must be weighed in accordance with 

unit rating plate ±0.6 oz/ft of 3/8-in. (56g/m of 9.5 mm) liquid line above or below 25 ft (7.6 m) respectively. 

 

EXAMPLE: 

Charging Formula: 

 

[(Lineset oz/ft x total length) – (factory charge for lineset)] = charge adjustment  

Example 1: 

System has 25ft of line set using existing 1/4“liquid line. What charge adjustment is required?  

Formula: (.27 oz/ft x 25ft) – (13.5 oz) = -6.75 oz; (8.0 g/m x 7.6 m) – (382.7 g) = -321.9 g  

Net result is to remove 6.75 oz of refrigerant from the system  

Example 2: 

System has 45 ft of existing 5/16” liquid line. What is the charge adjustment?  

Formula: (.40 oz/ft. x 45ft) – (13.5 oz.) = 9 oz; (11.8 g/m x 13.7m) – (382.7 g) = -221.0 g  

Net result is to add 4.5 oz of refrigerant to the system  

The following procedure is valid when indoor airflow is within ±21 percent of its rated CFM: 

1. Operate unit a minimum of 10 minutes before checking charge. 

2. Measure suction pressure by attaching an accurate gage to suction valve service port. 

3. Measure suction temperature by attaching an accurate thermistor type or electronic thermometer to suction line 
near service valve. 

4. Measure outdoor air dry bulb temperature with thermometer. 

5. Measure indoor air (entering indoor coil) wet bulb temperature with a sling psychrometer. 

6. Refer to “Super Heat Charging Table”. Find outdoor temperature and evaporator entering air web bulb 

temperature. At this intersection, note superheat. 
7. Refer to “Required Suction Tube Temperature”. Find superheat temperature and suction pressure. At this 

intersection note suction line temperature. 

8. If a unit has a higher suction line temperature than charted temperature, add refrigerant until charted temperature 

is reached. 

9. If unit has a lower suction line temperature than charted temperature, reclaim refrigerant until charted temperature 
is reached. 

10. When adding refrigerant, charge in liquid form into suction service port using a flow--restricting device. 

11. If outdoor air temperature or pressure at suction valve changes, charge to new suction line temperature indicated 

on chart. 

 

NOTE: 

If line length is beyond 80 ft (24.38 m) or greater than 20 ft (6.10 m) vertical separation, See Long Line 

Guideline for special charging requirements. 

 

R410a refrigerant must be added to a system as a liquid since it is a blend. Adding liquid into suction service 
port using a flow metering device for throttling it in slowly to avoid slugging the compressor or diluting and 

washing out the compressor oil. 

Caution 

Page 15

Summary of Contents for 38C Series

Page 1: ...ries energy efficient split top discharge condensing units incorporate innovative technology to provide reliable summer cooling performance The units are pre wired pre charged with Puron R 410A refrig...

Page 2: ...the potential for personal injury Understand the signal words DANGER WARNING CAUTION and NOTE These words are used with the safety alert symbol DANGER identifies the most serious hazards which will re...

Page 3: ...frigerant Charge kg 2 31 2 44 3 12 4 05 4 17 4 52 Connection Type Liquid Line Vapour Line Max Length ft Max Lift ft Outdoor Fan Motor Type Motor Voltage RPM CFM Diameter No Blades Motor Horsepower Con...

Page 4: ...393 7 349 2 36 792 2 981 1 98 4 19 0 166 7 627 1 231 8 74 6 15 9 406 4 393 7 393 7 42 792 2 722 3 98 4 22 2 166 7 627 1 231 8 74 6 15 9 406 4 393 7 323 8 48 792 2 722 3 98 4 22 2 166 7 627 1 231 8 74...

Page 5: ...07 4 115 8 929 4 115 5 5 6 5 38CKPS48DS40 42TPM048 11 415 3 50 Ducted 47 500 43 000 12 2 9 0 3 893 4 778 10 511 4 778 6 6 7 8 38CKPS60DS40 42TPM060 11 415 3 50 Ducted 60 000 51 000 11 8 8 3 5 085 6 14...

Page 6: ...Typical Wiring Schematic 38CKP18 24 30 36 230V 240V 1PH 50Hz Ducted 38CKP36 42 48 60 400V 415V 3PH 50Hz Ducted Page 6...

Page 7: ...Typical Wiring Schematic Continued 38CKP36 42 48 60 400V 415V 3PH 50Hz Ducted With Capacitor Bank Page 7...

Page 8: ...nit operation sound may disturb customer 2 Insure that vapor and liquid tube diameters are appropriate to capacity of unit 3 Run refrigerant tubes as directly as possible by avoiding unnecessary turns...

Page 9: ...rovisions are made for water drainage and noise vibration dampening Rigging Keep unit upright Lift unit using sling Use cardboard or padding under sling and spreader bars to prevent sling damage to un...

Page 10: ...nnecessary turns and bends Suspend refrigerant tubes so they do not damage insulation on vapor tube and do not transmit vibration to the structure Also when passing refrigerant tubes through the wall...

Page 11: ...uate above or below permissible limits When making electrical connections provide clearance at unit for refrigerant piping connections NOTE Use copper wires only between disconnect switch and unit NOT...

Page 12: ...the Pre startup and Startup included with the fan coil units for correct start up procedures Be sure that field disconnect is closed Set room thermostat below ambient temperature Operate unit for 15 m...

Page 13: ...nts from drier into the system Loss of Charge Pressure Switch This switch mounted on the suction line has fixed non adjustable settings To check pressure switch attach pressure gage to suction service...

Page 14: ...den hose or other suitable equipment to flush coil from the outside to remove dirt Be sure to flush all dirt and debris from drain holes in the base of unit Fan motors are waterproof Leak Detection Ne...

Page 15: ...4 liquid line What charge adjustment is required Formula 27 oz ft x 25ft 13 5 oz 6 75 oz 8 0 g m x 7 6 m 382 7 g 321 9 g Net result is to remove 6 75 oz of refrigerant from the system Example 2 System...

Page 16: ...9 4 10 6 11 7 12 8 13 9 4 6 1 7 2 8 3 9 4 10 6 11 7 12 8 13 9 15 0 6 7 2 8 3 9 4 10 6 11 7 12 8 13 9 15 0 16 1 7 8 3 9 4 10 6 11 7 12 8 13 9 15 0 16 1 17 2 8 9 4 10 6 11 7 12 8 13 9 15 0 16 1 17 2 18...

Page 17: ...262 86 9 364 110 0 466 128 7 596 148 4 60 8 6 162 57 0 264 87 4 366 110 4 468 129 0 600 149 0 62 10 0 164 57 7 266 87 9 368 110 8 470 129 3 604 149 5 64 11 3 166 58 4 268 88 4 370 111 2 472 129 7 608...

Page 18: ...26 335 90 92 94 96 88 90 92 94 86 88 90 92 84 86 88 90 82 84 86 88 80 82 84 86 345 354 364 374 98 100 102 104 96 98 100 102 94 96 98 100 92 94 96 98 90 92 94 96 88 90 92 94 384 395 406 416 106 108 110...

Page 19: ...filter driers in line longer than 72 hours Do not install a suction line filter drier in liquid line POE oils absorb moisture rapidly Do not expose oil to atmosphere POE oils may cause damage to certa...

Page 20: ...OR NON CONDENSABLES IN SYSTEM LOW REFRIGERANT CHARGE LINE VOLTAGE TOO HIGH OR LOW DEFECTIVE RUN CAPACITOR COMPRESSOR BEARINGS HIGH SUPERHEAT LOOSE LEAD AT FAN MOTOR MOTOR DEFECTIVE LOW SUCTION PRESSU...

Page 21: ...control wires connected to the same circuit as associated refrigerant lines Check to make sure the subbase mounting to wall is secure Don t apply excessive force to mounting screw Are the refrigerant...

Page 22: ...NOTES Page 22...

Page 23: ...used to highlight suggestions which will result in enhanced installation reliability or operation WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or deat...

Page 24: ...mode thus in some cases heat pumps have additional line set limitations from air conditioning units Table 3 in this guideline can be used to properly size suction lines Follow all suction line sizing...

Page 25: ...tdoor units Equivalent length takes into account pressure losses from both tubing length and losses due to fittings and accessories such as elbows liquid line solenoid and filter drier Losses from fit...

Page 26: ...nformation Use subcooling as the primary method for charging longline applications Outdoor units are pre charged for 15 ft 4 6 m of 3 8 liquid line When using different length diameter liquid lines ch...

Page 27: ...le 6 Vapor line should slope towards indoor unit Maximum actual liquid line is up to 100 61 m See Table 5 Maximum total equivalent length is up to 120 76 2 m See Table 5 Heat pump only Bi flow liquid...

Page 28: ...150 150 150 150 150 150 AC HP 3 8 150 150 150 150 150 150 150 150 150 24000 AC Only 1 4 75 75 75 50 50 AC Only 5 16 150 150 150 150 150 150 150 125 100 AC HP 3 8 150 150 150 150 150 150 150 150 150 30...

Page 29: ...9 15 2 51 75 15 5 22 9 76 100 23 2 30 5 101 125 30 8 38 1 18000 AC Only 1 4 150 150 150 150 150 AC Only 5 16 150 150 150 150 150 AC HP 3 8 150 150 150 150 150 24000 AC Only 1 4 100 125 150 150 150 AC...

Page 30: ...ss than 20 ft 6 1 m vertical separation Outdoor unit BELOW indoor unit See Tables 6 8 and 11 for longline thresholds An inverted vapor line trap must be installed at indoor unit The top peak of trap m...

Page 31: ...Page 31...

Page 32: ...ts to discontinue or change at any time specifications or designs without notice and without incurring any obligations Supersedes Version 38C 50Hz IOM 01 Catalog Number 38C 50 EN IOM 02 Effective Date...

Reviews: