Electrical data

* Permissible limits of the voltage range at which unit will operate satisfactorily. Operation outside these limits may result in unit failure.

† If wire is applied at ambient greater than 30°C (86°F), consult Table 310-16 of the NEC (ANSI/NFPA 70).

The ampacity of nonmetallic-sheathed cable (NM), trade name ROMEX, shall be that of 60°C (140°F) conductors, per the NEC (ANSI/NFPA 70)
Article 336-26. If other than uncoated (non-plated), 60° or 75°C (140° or 167°F) insulation, copper wire (solid wire for 10 AWG and smaller,
stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (ANSI/NFPA 70).

‡ Length shown is as measured 1 way along wire path between the unit and service panel for a voltage drop not to exceed 2%.

** Time-delay fuse.
FLA  — Full Load Amps
LRA  — Locked Rotor Amps
MCA  — Minimum Circuit Amps
RLA  — Rated Load Amps
NOTES: 
1. Control circuit is 24v on all units and requires external power source.
2. Copper wire must be used from service disconnect to unit.
3. All motors/compressors contain internal overload protection.

Sound power (dBA)

UNIT

SIZE–SERIES

V/PH

OPER VOLTS*

COMPRESSOR

FAN
FLA

MCA

60°C

MIN

WIRE

SIZE†

75°C

MIN

WIRE

SIZE†

60°C
MAX

LENGTH

(Ft)‡

75°C
MAX

LENGTH

(Ft)‡

MAX FUSE**

CKT BKR AMPS

Max

Min

LRA

RLA

024-31

208/230/1

253

187

56.0

11.4

0.5

14.8

14

14

53

50

25

030-31

72.5

15.0

0.8

19.6

14

14

39

37

30

036-33

97.0

16.7

1.1

22.0

12

12

55

52

30

036-32

88.0

16.0

1.1

21.1

12

12

57

54

30

042-33

115.0

18.6

1.1

24.5

10

10

80

76

40

042-32

104.0

20.0

1.1

26.1

10

10

74

70

40

048-35

140.0

24.4

1.4

31.9

8

8

97

59

50

048-34

137.0

20.2

1.1

26.4

10

10

74

70

40

060-34

169.0

28.8

1.4

37.4

8

8

82

78

60

060-35

175.0

28.8

1.4

37.4

8

8

82

78

60

036-53

208/230/3

253

187

75.0

10.6

1.4

14.7

14

14

53

50

20

036-52

77.0

11.4

1.4

15.7

14

14

49

47

20

042-53

90.0

13.4

1.4

18.2

14

14

41

39

25

042-52

88.0

13.9

1.4

18.8

14

14

41

39

25

048-54

91.0

15.1

1.4

20.2

12

12

60

57

30

060-54

123.0

17.3

1.4

23.0

12

12

55

52

40

UNIT

SIZE

SOUND

Level (dBA)

OCTAVE BAND CENTER FREQUENCY (Hz)

125

250

500

1000

2000

4000

8000

024-31

78

49.5

58.0

64.0

71.0

64.5

60.5

56.5

030-31

78

54.0

61.0

66.0

70.5

66.0

62.5

58.0

036-33

82

54.5

66.5

68.0

71.0

77.0

70.5

61.5

036-53

82

49.5

61.0

70.5

73.5

65.5

62.5

54.0

036-32, 52

82

52.0

58.5

68.0

78.0

68.0

64.0

58.0

042-33

82

55.0

69.0

67.0

70.5

76.5

68.5

61.5

042-53

82

49.5

60.5

67.5

72.0

66.0

63.0

56.0

042-32, 52

82

54.0

61.0

67.5

73.5

71.0

63.5

58.5

048-35

82

52.5

62.5

67.0

70.0

64.5

63.5

58.5

048-34, 54

82

51.5

58.5

65.5

66.5

64.0

64.5

61.5

060-35

82

58.5

66.0

71.5

75.0

68.5

68.0

60.5

060-34, 54

82

58.0

69.0

72.0

75.0

69.5

70.0

64.5

Summary of Contents for 38BRC

Page 1: ...in 208 230v 3 phase Wide Range of Sizes Available in 6 nominal sizes from 024 through 060 to meet the needs of residential and light commercial applications Compressor This unit features a scroll com...

Page 2: ...at transfer Vertical air discharge carries sound and hot condenser air up and away from adjacent patio areas and foliage Heat pump style drain pan for easy removal of water dirt and leaves Application...

Page 3: ...6 75 6 75 8 38 10 45 12 88 CONDENSER FAN Air Discharge Air Qty CFM Motor HP Motor RPM Propeller Type Direct Drive Vertical 1800 2500 2800 2800 3300 2800 3300 3300 1 15 1 8 1 5 1 5 1 4 1 5 1 4 1 4 820...

Page 4: ...5 54 KAATX0301RPB TXV Kit RPB Size 024 KAATX0401RPB TXV Kit RPB Size 030 KAATX0501RPB TXV Kit RPB Sizes 036 042 KAATX0601RPB TXV Kit RPB Size 048 KAATX0701RPB TXV Kit RPB Size 060 KSATX0601HSO TXV Kit...

Page 5: ...standard on 048 and 060 sizes SUGGESTED USE When interconnecting tube length exceeds 50 ft When unit will be operated below 55 F 12 8 C outdoor air temperature Use with Low Ambient Controller All com...

Page 6: ...rigerant pressure on low side of refrigerant circuit Cycles compressor off if refrigerant pressure drops to about 27 psig Prevents indoor coil freeze up due to loss of indoor airflow Also provides add...

Page 7: ...Ft MAX FUSE CKT BKR AMPS Max Min LRA RLA 024 31 208 230 1 253 187 56 0 11 4 0 5 14 8 14 14 53 50 25 030 31 72 5 15 0 0 8 19 6 14 14 39 37 30 036 33 97 0 16 7 1 1 22 0 12 12 55 52 30 036 32 88 0 16 0 1...

Page 8: ...low 2 Minimum outdoor operating ambient in cooling mode is 55 F max 125 F 3 Series designation is the 13th position of the unit model number 4 Center of gravity DIMENSIONS IN UNIT SIZE SERIES B C D M...

Page 9: ...0 11 95 CC5A CD5AW024 23 200 TDR 13 00 13 00 11 65 CC5A CD5AW030 23 400 TDR 13 00 13 00 11 95 CK3BA024 23 200 TDR 13 00 13 00 11 65 CK3BA030 23 400 TDR 13 00 13 00 11 95 CK5A CK5BW024 23 200 TDR 13 00...

Page 10: ...R 13 00 13 00 11 95 COILS 58MVP080 20 VARIABLE SPEED FURNACE CK3BA030 29 000 TDR 12 50 12 50 11 20 CK3BA036 29 600 TDR 13 00 13 00 11 80 CK5A CK5BW030 29 000 TDR 12 50 12 50 11 20 CK5A CK5BW036 29 600...

Page 11: ...00 CK5A CK5BN042 34 000 TDR 12 50 12 50 11 15 CK5A CK5BT036 35 000 TDR 12 50 12 50 11 00 COILS 58MVP080 14 VARIABLE SPEED FURNACE CC5A CD5AA036 35 000 TDR 12 80 12 80 11 20 CC5A CD5AA042 35 000 TDR 12...

Page 12: ...NONE 12 00 12 00 12 00 10 45 CD5AA048 40 500 NONE 12 00 12 00 12 00 10 45 CE3AA042 40 000 NONE 12 00 12 00 12 00 10 50 CE3AA048 40 500 NONE 12 00 12 00 12 00 10 55 CF5AA048 40 500 NONE 12 00 12 00 12...

Page 13: ...0 13 00 11 30 048 34 35 54 CD5AA048 47 000 NONE 12 00 12 00 12 00 10 50 CC5A CD5AA060 47 500 NONE 12 10 12 10 12 10 10 55 CC5A CD5AC048 46 000 NONE 11 80 11 80 11 80 10 30 CC5A CD5AW048 47 000 NONE 12...

Page 14: ...80 16 VARIABLE SPEED FURNACE CC5A CD5AC048 47 000 TDR 12 00 12 00 10 50 CD5AA048 47 000 TDR 12 00 12 00 10 65 CK3BA048 47 000 TDR 12 00 12 00 10 75 CK5A CK5BA048 47 000 TDR 12 00 12 00 10 75 COILS 58U...

Page 15: ...2 70 22 8 20 7 19 1 19 1 12 3 16 3 19 1 19 1 3 02 3 01 3 00 3 03 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity...

Page 16: ...00 CK3BA 030 1 00 0 96 CD5AW 036 1 02 1 00 036 1 02 0 94 CE3AA 030 1 00 1 00 CK5A CK5BW 030 1 00 0 96 036 1 02 1 00 036 1 02 0 94 CF5AA 036 1 02 1 00 COILS 58MVP080 20 VARIABLE SPEED FURNACE CK3BA 030...

Page 17: ...CD5AW 036 1 00 1 00 042 1 00 0 97 042 1 00 1 00 CK5A CK5BA 042 1 00 0 97 CE3AA 036 1 00 1 00 CK5A CK5BT 042 1 00 0 97 042 1 01 1 00 CK5A CK5BW 036 1 00 0 98 CF5AA 036 1 00 1 00 COILS 58MVP100 20 VARI...

Page 18: ...8 36 5 33 5 30 7 30 4 19 0 24 9 30 0 30 4 3 55 3 52 3 49 3 48 34 8 31 9 29 3 29 2 18 5 24 2 29 1 29 2 3 90 3 85 3 82 3 81 33 1 30 2 27 9 27 9 17 9 23 6 27 9 27 9 4 28 4 21 4 17 4 18 1350 72 67 62 57 4...

Page 19: ...CC5A CD5AC 048 1 00 0 99 048 1 00 0 93 CC5A CD5AW 042 1 00 1 00 CD5AA 048 1 00 0 93 048 1 01 1 00 CK3BA 048 1 01 0 93 CD5AA 048 1 01 1 00 CK5A CK5BA 048 1 01 0 97 CE3AA 042 1 00 1 00 CK5A CK5BT 048 1...

Page 20: ...MVP100 20 VARIABLE SPEED FURNACE CC5A CD5AC 048 0 98 1 00 CC5A CD5AA 060 1 01 0 96 CC5A CD5AW 048 1 00 1 00 CC5A CD5AC 048 1 00 0 97 CC5A CD5AW 060 1 01 1 00 CC5A CD5AW 060 1 00 0 96 CE3AA 048 1 00 1...

Page 21: ...1 50 8 50 9 6 36 6 26 6 14 6 12 57 3 53 2 48 9 48 6 30 8 41 0 48 9 48 6 6 95 6 85 6 73 6 71 54 0 49 8 46 2 46 3 29 6 39 6 46 2 46 3 7 60 7 47 7 35 7 35 Multipliers for Determining the Performance With...

Page 22: ...1 33 1 56 1 82 2 11 2 43 2 77 3 13 40 TCG 33 2 31 9 30 5 29 0 27 5 25 9 24 2 SDT 75 6 85 5 95 4 105 0 115 0 125 0 135 0 KW 1 29 1 52 1 78 2 06 2 38 2 73 3 10 45 TCG 36 3 34 9 33 4 31 9 30 2 28 6 26 8...

Page 23: ...12 3 49 3 88 4 30 4 74 35 TCG 49 6 47 5 45 3 43 0 40 6 38 1 35 5 SDT 76 3 86 2 95 9 106 0 116 0 126 0 135 0 KW 2 47 2 77 3 11 3 49 3 89 4 32 4 76 40 TCG 54 2 52 0 49 7 47 2 44 7 42 1 39 4 SDT 77 7 87...

Page 24: ...to field start up Unit Cabinet Unit cabinet will be constructed of galvanized steel bonderized and coated with a powder coat paint Fans Condenser fan will be direct drive propeller type discharging a...

Reviews: