Accessory usage guideline

 

* For tubing lines sets between 50 and 175 ft, refer to the Residential Split-System Long-Line Application Guideline.

† Only when low-pressure switch is used.
‡ Required for Low-Ambient Controller (full modulation feature) and MotorMaster® Control only.

 

Accessory description and usage (Listed alphabetically)

 

1.

Ball Bearing Fan Motor

 

A fan motor with ball bearings which permits speed reduction while maintaining bearing lubrication.

SUGGESTED USE: Required on all units where Low-Ambient Controller (full modulation feature) or MotorMaster® Control has been added.

 

2.

Coastal Filter

 

A mesh screen inserted under the top cover and inside the base pan to protect the condenser coil from salt damage without restricting airflow.

SUGGESTED USE: In geographic areas where salt damage could occur.

 

3.

Compressor Start Assist — Capacitor and Relay

 

Start capacitor and start relay gives “hard” boost to compressor motor at each start-up.

SUGGESTED USE: Installations where interconnecting tube length exceeds 50 ft.

Installations where outdoor design temperature exceeds 105°F (40.6°C).
Installations where Liquid-Line Solenoid Valve has been added.

 

4.

Compressor Start Assist — PTC

 

Solid state electrical device which gives a “soft” boost to compressor at each start-up.

SUGGESTED USE: Installations with marginal power supply.

Replacement installations with rapid pressure balance (RPB) expansion valve on indoor coil.
Replacement installations with undersized interconnecting refrigerant tubes.

 

5.

Crankcase Heater

 

An electric resistance heater which mounts to the base of the compressor to keep the lubricant warm during off cycles. Improves compressor lubrication on 
restart and minimizes chance of refrigerant slugging. May or may not include a thermostat control. (Thermostat control standard on 048 and 060 sizes.)

SUGGESTED USE: When interconnecting tube length exceeds 50 ft.

When unit will be operated below 55°F (12.8°C) outdoor air temperature. (Use with Low-Ambient Controller.)
All commercial installations.

 

6.

Cycle Protector

 

Solid-state timing device which prevents compressor rapid recycling. Control provides an approximate 5-minute delay after power to the compressor has been 
interrupted for any reason, including normal room thermostat cycling.

SUGGESTED USE: Installations in areas where power interruptions are frequent.

Where user is likely to “play” with the room thermostat.
All commercial installations.
Installations where interconnecting tube length exceeds 50 ft.
High-rise applications.

 

7.

Evaporator Freeze Thermostat

 

An SPST temperature actuated switch which stops unit operation when evaporator reaches freeze-up conditions.

SUGGESTED USE: All units where Winter Start Control has been added.

 

8.

Filter Drier

 

A device for removing contaminants from refrigerant circulating in an air conditioner: 1-direction flow. (Filter drier standard on 048 and 060 sizes.)

 

9.

Inlet Grille Kit

 

A field-installed enhanced inlet grille to replace the standard inlet grille on residential air conditioners and heat pumps. 

SUGGESTED USE: For greater protection against inclement weather, incidental damage, and vandalism.

 

ACCESSORY

REQUIRED FOR

LOW-AMBIENT

APPLICATIONS

(Below 55°F)

REQUIRED FOR

LONG-LINE

APPLICATIONS*

(Over 50 Ft)

REQUIRED FOR

SEA COAST

APPLICATIONS
(Within 2 Miles)

Crankcase Heater

 

Yes

Yes

No

 

Evaporator Freeze Thermostat

 

Yes

No

No

 

Winter Start Control

 

Yes†

No

No

 

Accumulator

 

No

No

No

 

Compressor Start Assist

Capacitor and Relay

 

Yes

Yes

No

 

Low-Ambient Controller,

MotorMaster® Control

or

Low-Ambient Pressure Switch

 

Yes

No

No

 

Wind Baffle

 

See Low-Ambient Instructions

No

No

 

Coastal Filter

 

No

No

Yes

 

Support Feet

 

Recommended

No

Recommended

 

Liquid-Line Solenoid Valve

or

Hard Shutoff TXV

 

No

See Long-Line

Application

Guideline

No

 

Ball Bearing Fan Motor

 

Yes‡

No

No

Summary of Contents for 38BRC

Page 1: ...in 208 230v 3 phase Wide Range of Sizes Available in 6 nominal sizes from 024 through 060 to meet the needs of residential and light commercial applications Compressor This unit features a scroll com...

Page 2: ...at transfer Vertical air discharge carries sound and hot condenser air up and away from adjacent patio areas and foliage Heat pump style drain pan for easy removal of water dirt and leaves Application...

Page 3: ...6 75 6 75 8 38 10 45 12 88 CONDENSER FAN Air Discharge Air Qty CFM Motor HP Motor RPM Propeller Type Direct Drive Vertical 1800 2500 2800 2800 3300 2800 3300 3300 1 15 1 8 1 5 1 5 1 4 1 5 1 4 1 4 820...

Page 4: ...5 54 KAATX0301RPB TXV Kit RPB Size 024 KAATX0401RPB TXV Kit RPB Size 030 KAATX0501RPB TXV Kit RPB Sizes 036 042 KAATX0601RPB TXV Kit RPB Size 048 KAATX0701RPB TXV Kit RPB Size 060 KSATX0601HSO TXV Kit...

Page 5: ...standard on 048 and 060 sizes SUGGESTED USE When interconnecting tube length exceeds 50 ft When unit will be operated below 55 F 12 8 C outdoor air temperature Use with Low Ambient Controller All com...

Page 6: ...rigerant pressure on low side of refrigerant circuit Cycles compressor off if refrigerant pressure drops to about 27 psig Prevents indoor coil freeze up due to loss of indoor airflow Also provides add...

Page 7: ...Ft MAX FUSE CKT BKR AMPS Max Min LRA RLA 024 31 208 230 1 253 187 56 0 11 4 0 5 14 8 14 14 53 50 25 030 31 72 5 15 0 0 8 19 6 14 14 39 37 30 036 33 97 0 16 7 1 1 22 0 12 12 55 52 30 036 32 88 0 16 0 1...

Page 8: ...low 2 Minimum outdoor operating ambient in cooling mode is 55 F max 125 F 3 Series designation is the 13th position of the unit model number 4 Center of gravity DIMENSIONS IN UNIT SIZE SERIES B C D M...

Page 9: ...0 11 95 CC5A CD5AW024 23 200 TDR 13 00 13 00 11 65 CC5A CD5AW030 23 400 TDR 13 00 13 00 11 95 CK3BA024 23 200 TDR 13 00 13 00 11 65 CK3BA030 23 400 TDR 13 00 13 00 11 95 CK5A CK5BW024 23 200 TDR 13 00...

Page 10: ...R 13 00 13 00 11 95 COILS 58MVP080 20 VARIABLE SPEED FURNACE CK3BA030 29 000 TDR 12 50 12 50 11 20 CK3BA036 29 600 TDR 13 00 13 00 11 80 CK5A CK5BW030 29 000 TDR 12 50 12 50 11 20 CK5A CK5BW036 29 600...

Page 11: ...00 CK5A CK5BN042 34 000 TDR 12 50 12 50 11 15 CK5A CK5BT036 35 000 TDR 12 50 12 50 11 00 COILS 58MVP080 14 VARIABLE SPEED FURNACE CC5A CD5AA036 35 000 TDR 12 80 12 80 11 20 CC5A CD5AA042 35 000 TDR 12...

Page 12: ...NONE 12 00 12 00 12 00 10 45 CD5AA048 40 500 NONE 12 00 12 00 12 00 10 45 CE3AA042 40 000 NONE 12 00 12 00 12 00 10 50 CE3AA048 40 500 NONE 12 00 12 00 12 00 10 55 CF5AA048 40 500 NONE 12 00 12 00 12...

Page 13: ...0 13 00 11 30 048 34 35 54 CD5AA048 47 000 NONE 12 00 12 00 12 00 10 50 CC5A CD5AA060 47 500 NONE 12 10 12 10 12 10 10 55 CC5A CD5AC048 46 000 NONE 11 80 11 80 11 80 10 30 CC5A CD5AW048 47 000 NONE 12...

Page 14: ...80 16 VARIABLE SPEED FURNACE CC5A CD5AC048 47 000 TDR 12 00 12 00 10 50 CD5AA048 47 000 TDR 12 00 12 00 10 65 CK3BA048 47 000 TDR 12 00 12 00 10 75 CK5A CK5BA048 47 000 TDR 12 00 12 00 10 75 COILS 58U...

Page 15: ...2 70 22 8 20 7 19 1 19 1 12 3 16 3 19 1 19 1 3 02 3 01 3 00 3 03 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity...

Page 16: ...00 CK3BA 030 1 00 0 96 CD5AW 036 1 02 1 00 036 1 02 0 94 CE3AA 030 1 00 1 00 CK5A CK5BW 030 1 00 0 96 036 1 02 1 00 036 1 02 0 94 CF5AA 036 1 02 1 00 COILS 58MVP080 20 VARIABLE SPEED FURNACE CK3BA 030...

Page 17: ...CD5AW 036 1 00 1 00 042 1 00 0 97 042 1 00 1 00 CK5A CK5BA 042 1 00 0 97 CE3AA 036 1 00 1 00 CK5A CK5BT 042 1 00 0 97 042 1 01 1 00 CK5A CK5BW 036 1 00 0 98 CF5AA 036 1 00 1 00 COILS 58MVP100 20 VARI...

Page 18: ...8 36 5 33 5 30 7 30 4 19 0 24 9 30 0 30 4 3 55 3 52 3 49 3 48 34 8 31 9 29 3 29 2 18 5 24 2 29 1 29 2 3 90 3 85 3 82 3 81 33 1 30 2 27 9 27 9 17 9 23 6 27 9 27 9 4 28 4 21 4 17 4 18 1350 72 67 62 57 4...

Page 19: ...CC5A CD5AC 048 1 00 0 99 048 1 00 0 93 CC5A CD5AW 042 1 00 1 00 CD5AA 048 1 00 0 93 048 1 01 1 00 CK3BA 048 1 01 0 93 CD5AA 048 1 01 1 00 CK5A CK5BA 048 1 01 0 97 CE3AA 042 1 00 1 00 CK5A CK5BT 048 1...

Page 20: ...MVP100 20 VARIABLE SPEED FURNACE CC5A CD5AC 048 0 98 1 00 CC5A CD5AA 060 1 01 0 96 CC5A CD5AW 048 1 00 1 00 CC5A CD5AC 048 1 00 0 97 CC5A CD5AW 060 1 01 1 00 CC5A CD5AW 060 1 00 0 96 CE3AA 048 1 00 1...

Page 21: ...1 50 8 50 9 6 36 6 26 6 14 6 12 57 3 53 2 48 9 48 6 30 8 41 0 48 9 48 6 6 95 6 85 6 73 6 71 54 0 49 8 46 2 46 3 29 6 39 6 46 2 46 3 7 60 7 47 7 35 7 35 Multipliers for Determining the Performance With...

Page 22: ...1 33 1 56 1 82 2 11 2 43 2 77 3 13 40 TCG 33 2 31 9 30 5 29 0 27 5 25 9 24 2 SDT 75 6 85 5 95 4 105 0 115 0 125 0 135 0 KW 1 29 1 52 1 78 2 06 2 38 2 73 3 10 45 TCG 36 3 34 9 33 4 31 9 30 2 28 6 26 8...

Page 23: ...12 3 49 3 88 4 30 4 74 35 TCG 49 6 47 5 45 3 43 0 40 6 38 1 35 5 SDT 76 3 86 2 95 9 106 0 116 0 126 0 135 0 KW 2 47 2 77 3 11 3 49 3 89 4 32 4 76 40 TCG 54 2 52 0 49 7 47 2 44 7 42 1 39 4 SDT 77 7 87...

Page 24: ...to field start up Unit Cabinet Unit cabinet will be constructed of galvanized steel bonderized and coated with a powder coat paint Fans Condenser fan will be direct drive propeller type discharging a...

Reviews: