Installation instructions supplement

SENSOR

SENSOR

CONTROL

N.   OUT

NEUTRAL

OUT

LINE   OUT

LINE   IN

NEUTRAL

IN

HP   SELECT

SENSOR

Cooling only

Head pressure controller:

wiring from temperature sensor to printed circuit board

 Outdoor unit

 Indoor unit

 Head pressure sensor

 Loss of refrigerant

pressure switch

38BCS...G

 High pressure cut-out

 Anti freeze thermostat

38BCS…G units are designed to work in North European climates.

These versions are identified on the 5th digit, "S" of their code
number.

R-410A versions are identified on the 8th digit “G” of their code
number.

They differ from the standard ones for the following factory fitted
accessories: head pressure controller (HPC), loss of refrigerant
pressure switch (LRPS) and high pressure cut-out.

Operating range

Minimum ambient temperature:

min. –5

°

C

max. +43

°

C (mod. 009)

min. –10

°

C

max. +43

°

C (mod. 012, 014)

Power supply
Nominal single-phase voltage:

230V ~ 50Hz

Operating voltage limits

min.

198V

max.

264V

Features

 HPC

and HIP Remote Manual Reset.
The head pressure controller allows operation in cooling
mode up to –5

°

C (mod. 009) and –10

°

C (mod. 012,

014) ambient temperature keeping the condensing
temperature always above 41

°

C - 42

°

C.

 LRPS Loss of refrigerant pressure switch: brazed between

outdoor coil and expansion device. When unit is
working, the pressure “high side” drops below 345kPa
(3.45 bar; 50 psig) for refrigerant losses, the
compressor cannot restart.

Set point
– open at 345 kPa (3.45 bar; 50 psig) pressure
– close at 650 kPa (6.5 bar; 95 psig) pressure

Head pressure controller and HIP remote
manual reset

Configuration
The Head Pressure Control “HPC” is made of two parts:
• Printed circuit board, with electronic components and quick

connector terminals.

• Temperature sensor, complete with 500 mm wiring.

For the user convenience “HIP” has been selected at automatic reset.
If “HIP” trips, cycle the power supply OFF and ON to reset the system,
because the electrical box is equipped with relais that prevent the unit
from starting, till the indoor control is switched OFF.
When head pressure drops below 3000 kPa (30 bar; 420 psig) it is
possible to restart the unit switching the indoor control ON.

Operations mode

Full voltage:
When the liquid line temperature is over the setpoint value plus half
proportional band (factory set by supplier), the output voltage to the
motor is 97% or more of supply voltage.

Low voltage:
When the liquid line temperature is below set point  minus half
proportional band, the output voltage to the motor is fixed to 95V.

Hard start:
At each compressor starting the full voltage output to the fan motor
is provided for 3 seconds.

Proportional band:
The controller directly senses the changes in liquid line temperature
and varies the output voltage which causes the fan motor speed
increase or decrease.

Temperature setting

Proportional band

set point +11 / –11

°

C

Minimum speed output voltage:

95V

Setting:

the head pressure controller is
supplied  factory set at 42

°

C

Hard start time

3 seconds.

Note:
In case of first start after a pause of several hours at –10

°

C, with

low voltage supply (198V) high pressure switch HIP may trip off the
unit. In this case, the remote reset by indoor control (infrared) can
be done for unit restarting.

Summary of Contents for 38BC

Page 1: ...38BC 38BCS 38BH L L O Y D S R E G I S TER QUALIT Y A S S U R A N C E IS O 900 1 R 410A INSTALLATION MANUAL...

Page 2: ...ow out with the cylinder in a vertical position with the valve at the top R 410A systems should be charged with liquid refrigerant Use a commercial type metering device in the manifold hose in order t...

Page 3: ...5 m 15 m 15 m Table II Connections Mod 38BC 38BH 07 09 12 14 07 09 12 14 A mm 750 750 B mm 590 590 C mm 280 280 D mm 470 470 E mm 140 140 F mm 310 310 kg 26 5 30 33 35 28 5 33 36 37 Outdoor unit Indoo...

Page 4: ...r unit in very low ambient temperatures In these cycles fan speed will automatically reduce and cannot be varied until defrost cycle is completed Notes 1 Data referred to the outdoor unit only 2 Accor...

Page 5: ...ed to the same line Also ensure that national safety code requirements have been followed for the mains supply circuit The mains supply must be connected as follows Models 38BC and 38BH to the indoor...

Page 6: ...the refrigerant connections after installation this will cause refrigerant leaks Loosening the liquid line connection may cause the loss of the expansion device Connecting the condensate drain pipe t...

Page 7: ...UNF R 22 Refrigerant connections Charge liquid no gas Copper tubes during storage Use tools designed for R 410A higher pressure Keep inside clean 2 stage vacuum pump Replace oil regularly No moisture...

Page 8: ...longer than minimum required for installation Oil in the compressor is extremely susceptible to moisture absorption Always keep ends of tubing sealed during installation Remove flare nuts from the un...

Page 9: ...hree way valves Create a vacuum with a vacuum pump connected to the service connection of the suction shut off valve gas as shown keeping the shut off valves completely shut until a 50 Pa 0 5 mbar vac...

Page 10: ...p only Cooling only Cooling only unit system 38BC 007 009 012 014 38BH 007 009 012 014 38BCS 007 009 012 014 Heat pump Heat pump unit system Cooling only unit Cooling only system Power supply cable H0...

Page 11: ...rene coating according to EN 60335 2 40 codes The mains supply connecting cable for 38BCS units must be H07 RN F type 245 IEC 57 or higher with synthetic rubber insulation with Neoprene coating accord...

Page 12: ...any refrigerant leak due to incorrect connection or after replacement of the compressor The best method to correctly charge refrigerant is to completely empty the refrigerant circuit using refrigerant...

Page 13: ...w Refrigerant charge too low add refrigerant Outdoor coil dirty or obstructed clean or remove obstructions Indoor unit air filter dirty clean filter Suction pressure too high Refrigerant charge too hi...

Page 14: ...essure Head pressure controller and HIP remote manual reset Configuration The Head Pressure Control HPC is made of two parts Printed circuit board with electronic components and quick connector termin...

Page 15: ...zio 9 20058 Villasanta MI Italy Tel 039 3636 1 The manufacturer reserves the right to change any product specifications without notice Order No 13851 74M10 May 2003 Supersedes Order No 13851 74M10 Apr...

Reviews: