Table 16 — 38AUD 12, 14 Electrical Data without Powered Convenience Outlet
Table 17 — 38AUD 12, 14 Electrical Data with Powered Convenience Outlet
LEGEND
* Units are suitable for use on electrical systems where voltage sup-
plied to the unit terminals is not below or above the listed limits.
1. The MCA and Fuse values are calculated in accordance with the
NEC Article 440.
2. Motor RLA and LRA values are established in accordance with
Underwriters Laboratories (UL) Standard 1995.
3. The 575-v units are UL, Canada-listed only.
4. Unbalanced 3-Phase Supply Voltage. Never operate a motor
where a phase imbalance in supply voltage is greater than 2%.
Use the following formula to determine the percentage of voltage
imbalance.
Example: Supply voltage is 230-3-60
Determine maximum deviation from average voltage.
(AB) 227-224 = 3 v
(BC) 231-227 = 4 v
(AC) 227-226 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.
This amount of phase imbalance is satisfactory as it is below the maxi-
mum allowable 2%.
UNIT
SIZE
V-Ph-Hz
VOLTAGE
RANGE*
COMPRESSOR
No. 1
COMPRESSOR
No. 2
OFM
POWER SUPPLY
DISCONNECT
SIZE
Min
Max
RLA
LRA
RLA
LRA
Qty
FLA
(ea)
MCA
Fuse or
HACR
Brkr
FLA
LRA
12
575-3-60
518
633
5.7
39
5.7
39
2
0.7
15
20
15
82
208/230-3-60
187
253
15.9
110
15.9
110
2
1.5
39/39
50/50
40/40
226/226
460-3-60
414
506
7.7
52
7.7
52
2
0.8
19
25
20
108
14
575-3-60
518
633
7.7
54
7.7
54
2
0.7
19
25
19
112
208/230-3-60
187
253
22.4
149
22.4
149
2
1.5
54/54
60/60
55/55
304/304
460-3-60
414
506
10.6
75
10.6
75
2
0.8
26
30
26
154
UNIT
SIZE
V-Ph-Hz
VOLTAGE
RANGE*
COMPRESSOR
No. 1
COMPRESSOR
No. 2
OFM
POWER SUPPLY
DISCONNECT
SIZE
Min
Max
RLA
LRA
RLA
LRA
Qty
FLA
(ea)
MCA
Fuse or
HACR
Brkr
FLA
LRA
12
575-3-60
518
633
5.7
39
5.7
39
2
0.7
16
20
17
84
208/230-3-60
187
253
15.9
110
15.9
110
2
1.5
44/44
50/50
46/46
231/231
460-3-60
414
506
7.7
52
7.7
52
2
0.8
22
25
22
110
14
575-3-60
518
633
7.7
54
7.7
54
2
0.7
21
25
21
114
208/230-3-60
187
253
22.4
149
22.4
149
2
1.5
59/59
80/80
60/60
309/309
460-3-60
414
506
10.6
75
10.6
75
2
0.8
28
35
29
156
FLA
— Full Load Amps
LRA
— Locked Rotor Amps
MOCP
— Maximum Over Current Protection
NEC
— National Electrical Code
RLA
— Rated Load Amps
% Voltage
Imbalance
= 100 x
max voltage deviation from average voltage
average voltage
AB = 224 v
BC = 231 v
AC = 226 v
Average Voltage
=
(224 + 231 + 226)
=
681
=
227
3
3
% Voltage Imbalance = 100x
4
= 1.78%
227
A
B
C
MOTOR
IMPORTANT: If the supply voltage phase imbalance is more than 2%,
contact your local electric utility company immediately.