34SCA5: Installation Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

6

Notes:

- Optimum performance point, 95°F (35°C) outdoor ambient and (80°F / 27°C dry bulb), (67°F / 19°C wet bulb) indoor conditions. (DOE A Test Conditions)

- Where a dash (—) appears do not attempt to charge system under these conditions or refrigerant slugging may occur. Charge must be weighed in.

- Superheat °F is at low-side service port, Allow a tolerance of ±3°F (±1.7°C)

- Indoor dry bulb between 70°F and 80°F (21°C and 27°C)

Table 2 – Rating Plate (required) Subcooling Temperatures

Measure

 Liquid Pressure 

(psig)

R-410A Required Liquid Line Temperature °F (°C)

°F

(°C)

°F

(°C)

°F

(°C)

°F

(°C)

°F

(°C)

°F

(°C)

6

3

8

4

10

6

12

7

14

8

16

9

251 

78 

26 

76 

24 

74 

23 

72 

22 

70 

21 

68 

20 

259 

80 

27 

78 

26 

76 

24 

74 

23 

72 

22 

70 

21 

266 

82 

28 

80 

27 

78 

26 

76 

24 

74 

23 

72 

22 

274 

84 

29 

82 

28 

80 

27 

78 

26 

76 

24 

74 

23 

283 

86 

30 

84 

29 

82 

28 

80 

27 

78 

26 

76 

24 

291 

88 

31 

86 

30 

84 

29 

82 

28 

80 

27 

78 

26 

299 

90 

32 

88 

31 

86 

30 

84 

29 

82 

28 

80 

27 

308 

92 

33 

90 

32 

88 

31 

86 

30 

84 

29 

82 

28 

317 

94 

34 

92 

33 

90 

32 

88 

31 

86 

30 

84 

29 

326 

96 

36 

94 

34 

92 

33 

90 

32 

88 

31 

86 

30 

335 

98 

37 

96 

36 

94 

34 

92 

33 

90 

32 

88 

31 

345 

100

38 

98 

37 

96 

36 

94 

34 

92 

33 

90 

32 

364 

104

40 

102 

39 

100 

38 

98 

37 

96 

36 

94 

34 

374 

106

41 

104 

40 

102 

39 

100 

38 

98 

37 

96 

36 

384 

108

42 

106 

41 

104 

40 

102 

39 

100 

38 

98 

37 

395 

110

43 

108 

42 

106 

41 

104 

40 

102 

39 

100 

38 

406 

112

44 

110 

43 

108 

42 

106 

41 

104 

40 

102 

39 

416 

114

46 

112 

44 

110 

43 

108 

42 

106 

41 

104 

40 

427 

116

47 

114 

46 

112 

44 

110 

43 

108 

42 

106 

41 

439 

118

48 

116 

47 

114 

46 

112 

44 

110 

43 

108 

42 

450 

120

49 

118 

48 

116 

47 

114 

46 

112 

44 

110 

43 

462 

122

50 

120 

49 

118 

48 

116 

47 

114 

46 

112 

44 

474 

124

51 

122 

50 

120 

49 

118 

48 

116 

47 

114 

46 

Table 3 – Superheat Charging - AC Only

OUTDOOR TEMP (°F) 

EVAPORATOR ENTERING AIR TEMPERATURE (°F WB) 

50 

52 

54 

56 

58 

60 

62 

64 

67 

68 

70 

72 

74 

76 

55 

12 

14 

17 

20 

23 

26 

29 

32 

35 

37 

40 

42 

45 

60 

10 

12 

15 

18 

21 

24 

27 

30 

33 

35 

38 

40 

43 

65 

— 

10 

13 

16 

19 

21 

24 

27 

30 

33 

36 

38 

41 

70 

— 

— 

10 

13 

16 

19 

21 

24 

27 

30 

33 

36 

39 

75 

— 

— 

— 

12 

15 

18 

21 

24 

28 

31 

34 

37 

80 

— 

— 

— 

— 

12 

15 

18 

21 

25 

28 

31 

35 

85 

— 

— 

— 

— 

— 

— 

11 

15 

19 

22 

26 

30 

33 

90 

— 

— 

— 

— 

— 

— 

13 

16 

20 

24 

27 

31 

95 

— 

— 

— 

— 

— 

— 

— 

10 

14 

18 

22 

25 

29 

100 

— 

— 

— 

— 

— 

— 

— 

— 

12 

15 

20 

23 

27 

105 

— 

— 

— 

— 

— 

— 

— 

— 

13 

17 

22 

26 

110 

— 

— 

— 

— 

— 

— 

— 

— 

— 

11 

15 

20 

25 

115 

— 

— 

— 

— 

— 

— 

— 

— 

— 

— 

14 

18 

23 

Table 4 – Required Suction-Line Temperature

SUPERHEAT TEMP (°F) 

SUCTION PRESSURE AT SERVICE PORT (PSIG) 

107.8 

112.2 

116.8 

121.2 

126 

130.8 

138.8 

140.8 

145.8 

35 

37 

39 

41 

43 

45 

47 

49 

51 

37 

39 

41 

43 

45 

47 

49 

51 

53 

39 

41 

43 

45 

47 

49 

51 

53 

55 

41 

43 

45 

47 

49 

51 

53 

55 

57 

43 

45 

47 

49 

51 

53 

55 

57 

59 

10 

45 

47 

49 

51 

53 

55 

57 

59 

61 

12 

47 

49 

51 

53 

55 

57 

59 

61 

63 

14 

49 

51 

53 

55 

57 

59 

61 

63 

65 

16 

51 

53 

55 

57 

59 

61 

63 

65 

67 

18 

53 

55 

57 

59 

61 

63 

65 

67 

69 

20 

55 

57 

59 

61 

63 

65 

67 

69 

71 

22 

57 

59 

61 

63 

65 

67 

69 

71 

73 

24 

59 

61 

63 

65 

67 

69 

71 

73 

75 

26 

61 

63 

65 

67 

69 

71 

73 

75 

77 

28 

63 

65 

67 

69 

71 

73 

75 

77 

79 

30 

65 

67 

69 

71 

73 

75 

77 

79 

81 

32 

67 

69 

71 

73 

75 

77 

79 

81 

83 

34 

69 

71 

73 

75 

77 

79 

81 

83 

85 

36 

71 

73 

75 

77 

79 

81 

83 

85 

87 

38 

73 

75 

77 

79 

81 

83 

85 

87 

89 

40 

75 

77 

79 

81 

83 

85 

87 

89 

91 

Summary of Contents for 34SCA5

Page 1: ...windows patios decks etc where unit operation sound may disturb customer 3 Ensure that vapor and liquid tube diameters are appropriate for unit capacity 4 Run refrigerant tubes with no bends with cent...

Page 2: ...the accessory kit NOTE Accessory wind baffles should be used on all units with accessory low ambient temperature control A07396 Fig 2 Lifting Unit with Sling Clearance Requirements Single Unit Applic...

Page 3: ...joint Wrap service valves with a heat sinking material such as a wet cloth Braze joints using a Sil Fos or Phos copper alloy Consult local code requirements Refrigerant tubing and indoor coil are now...

Page 4: ...apable of accurately measuring this vacuum depth 1 Vacuum unit to 500 microns 2 When isolating the unit from the pump the pressure shall not rise above 1500 microns in 10 minutes Final Tubing Check IM...

Page 5: ...inimum of 15 minutes before checking charge 2 Measure suction pressure by attaching an accurate gage to suction valve service port 3 Measure suction temperature by attaching an accurate thermistor typ...

Page 6: ...44 110 43 108 42 106 41 104 40 102 39 416 114 46 112 44 110 43 108 42 106 41 104 40 427 116 47 114 46 112 44 110 43 108 42 106 41 439 118 48 116 47 114 46 112 44 110 43 108 42 450 120 49 118 48 116 47...

Page 7: ...met and connect leads to control wiring Refer to thermostat Installation Instructions for wiring specific unit combinations see Fig 7 Use No 18 AWG color coded insulated 35 C minimum wire If thermosta...

Page 8: ...ctory charge amount and desired subcooling are shown on unit rating plate Charging method is shown on information plate inside unit For TXV use subcooling method For piston use superheat method To pro...

Page 9: ...coastal applications See Owner s Manual for information WARNING PERSONAL INJURY AND OR PROPERTY DAMAGE HAZARD Failure to follow this warning could result in personal injury and or property damage For...

Page 10: ...ice and without obligations 10 Training My Learning Center is your central location for professional residential HVAC training resources that help strengthen careers and businesses We believe in provi...

Reviews: