Advanced Setup
19
Select fan coil system type:
2
= 2-pipe fan coil
4
= 4-pipe fan coil
Select display operation:
1
= Single Setpoint
2
= Dual Setpoint
See page 32
4
2
1
= Heat only system
2
= Cool only system
3
= Heat/Cool Auto changeover
4
= Heat/Cool Aux Electric
heat, Lockout Electric Heat
when Hot Water is available
5
= Heat/Cool total electric
heat,
no
Hot Water,
only
Electric Heat.
Continued
MODE
Press
MODE
Press
MODE
Press
Step #6 only appears if step #5 = 2.
2-PIPE SYSTEM OPERATION
Note: #3 & #4 require accessory changeover sensor
Note:
When Single Setpoint is selected, the heating or
cooling setpoint will always be displayed. To display the room temperature,
press and hold the MODE button for two seconds. The degree icon will blink
when the large number is displaying room temperature and will remain
solid when displaying the heating or cooling setpoint.