121
Table 16 — 0XV140-500 Electrical Data, Dual Point Power, High Tier, Variable Speed Fans (cont)
LEGEND
NOTES:
1. Units are suitable for use on electrical systems where voltage
supplied to the unit terminals is not below or above the listed
minimum and maximum limits. Maximum allowable phase imbal-
ance is: voltage, 2%; amps 10%.
2. Evaporator heater (where applicable) is wired into the control cir-
cuit so it is always operable as long as the control power supply
disconnect is on, even if any safety device is open.
3. For MCA that is less than or equal to 380 amps, 3 conductors are
required.
For MCA between 381-760 amps, 6 conductors are required.
For MCA between 761-1140 amps, 9 conductors are required.
For MCA between 1141-1520 amps, 12 conductors are required.
Calculation of conductors required is based on 75 C copper wire.
4. Based on the operational characteristics of a VFD, the “inrush”
current normally associated with a chiller is limited and will be
lower than the MCA rating of the chiller.
5. Wiring for main field supply must be rated 75 C minimum. Use
copper for all units. Refer to Table 8 for power entry option.
6. MCA and MOCP values shown are inclusive of control power
transformer loads.
UNIT
30XV
UNIT VOLTAGE
NUMBER OF
COND FANS
STANDARD CONDENSER FANS
HIGH STATIC CONDENSER FANS
CONTROL
CIRCUIT
V(3 Ph) Hz
Supplied
MCA
MOCP
REC FUSE SIZE
MCA
MOCP
REC FUSE SIZE Voltage
1 PH,
60 Hz
MCA
and
MOCP
Min
Max CKT 1 CKT 2 CKT 1
CKT 2
CKT 1
CKT 2
CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2 CKT 1 CKT 2
275
380
400
460
575
60
60
60
60
342
360
414
518
418
440
506
633
8
8
8
8
8
8
8
8
327.1
311.3
269.9
217.0
320.4
304.6
264.4
212.5
500
500
450
350
500
500
400
350
400
400
350
300
400
400
350
250
337.5
321.3
278.7
223.8
330.8
314.6
273.2
219.4
500
500
450
350
500
500
450
350
400
400
350
300
400
400
350
300
115
115
115
115
60
60
60
60
380
400
415
440
50
50
50
50
342
360
374
396
418
440
457
484
8
8
8
8
8
8
8
8
334.2
318.3
306.9
289.6
327.5
311.6
300.1
282.9
500
500
500
450
500
500
500
450
400
400
400
350
400
400
400
350
344.7
328.3
316.5
298.8
338.0
321.6
309.8
292.1
500
500
500
450
500
500
500
450
450
400
400
350
400
400
400
350
115
115
115
115
60
60
60
60
300
380
400
460
575
60
60
60
60
342
360
414
518
418
440
506
633
9
9
9
9
9
9
9
9
343.6
326.2
282.9
226.6
336.8
319.5
277.3
222.2
500
500
450
350
500
500
450
350
450
400
350
300
400
400
350
300
355.2
337.5
292.8
234.4
348.5
330.8
287.2
230.0
500
500
450
350
500
500
450
350
450
400
350
300
450
400
350
300
115
115
115
115
60
60
60
60
380
400
415
440
50
50
50
50
342
360
374
396
418
440
457
484
9
9
9
9
9
9
9
9
350.7
334.6
323.0
304.2
344.0
327.9
316.3
297.5
500
500
500
500
500
500
500
500
450
400
400
400
450
400
400
350
362.6
345.9
333.8
314.5
355.9
339.2
327.1
307.8
500
500
500
500
500
500
500
500
450
450
400
400
450
400
400
400
115
115
115
115
60
60
60
60
325
380
400
460
575
60
60
60
60
342
360
414
518
418
440
506
633
10
10
10
10
10
10
10
10
376.3
358.7
310.7
248.8
369.6
352.0
305.1
244.4
600
600
500
400
600
500
500
400
450
450
400
300
450
450
400
300
389.2
371.2
321.7
257.4
382.5
364.5
316.1
253.0
600
600
500
400
600
600
500
400
600
600
500
400
450
450
400
300
115
115
115
115
60
60
60
60
380
400
415
440
50
50
50
50
342
360
374
396
418
440
457
484
10
10
10
10
10
10
10
10
384.8
365.9
354.1
333.8
378.1
359.2
347.4
327.1
600
600
500
500
600
600
500
500
450
450
450
400
450
450
450
400
398.0
378.4
366.2
345.2
391.3
371.7
359.5
338.5
600
600
600
500
600
600
500
500
500
450
450
450
500
450
450
400
115
115
115
115
60
60
60
60
350
380
400
460
575
60
60
60
60
342
360
414
518
418
440
506
633
11
11
11
11
9
9
9
9
470.3
447.4
388.4
311.9
340.6
323.3
281.0
226.0
700
700
600
500
500
500
450
350
600
600
500
400
400
400
350
300
484.5
461.2
400.5
321.4
352.3
334.6
290.9
233.7
800
700
600
500
500
500
450
350
600
600
500
400
450
400
350
300
115
115
115
115
60
60
60
60
380
400
415
440
50
50
50
50
342
360
374
396
418
440
457
484
11
11
11
11
9
9
9
9
480.2
457.3
441.5
416.0
347.8
330.4
318.8
301.3
800
700
700
700
500
500
500
500
600
600
600
500
450
400
400
400
494.7
471.1
454.8
428.5
359.7
341.7
329.6
311.5
800
700
700
700
500
500
500
500
600
600
600
600
450
400
400
400
115
115
115
115
60
60
60
60
400
380
400
460
575
60
60
60
60
342
360
414
518
418
440
506
633
11
11
11
11
11
11
11
11
492.2
468.1
406.3
325.7
482.3
458.1
398.1
319.1
800
700
600
500
800
700
600
500
600
600
500
400
600
600
500
400
506.5
481.9
418.4
335.1
496.5
472.0
410.2
328.6
800
800
600
500
800
700
600
500
600
600
500
400
600
600
500
400
115
115
115
115
60
60
60
60
380
400
415
440
50
50
50
50
342
360
374
396
418
440
457
484
11
11
11
11
11
11
11
11
502.1
478.0
460.9
435.4
492.2
468.0
451.0
425.4
800
800
700
700
800
700
700
700
600
600
600
600
600
600
600
600
516.7
491.8
474.3
448.0
506.7
481.8
464.3
438.0
800
800
700
700
800
800
700
700
700
600
600
600
600
600
600
600
115
115
115
115
60
60
60
60
450
380
400
460
575
60
60
60
60
342
360
414
518
418
440
506
633
12
12
12
12
12
12
12
12
532.4
506.8
439.8
352.9
522.5
496.8
431.6
346.3
800
800
700
500
800
800
700
500
700
600
600
450
700
600
600
450
548.0
512.3
388.2
311.6
538.0
511.9
444.8
356.6
800
800
700
600
800
800
700
600
700
700
600
450
700
700
600
450
115
115
115
115
60
60
60
60
380
400
415
440
50
50
50
50
342
360
374
396
418
440
457
484
12
12
12
12
12
12
12
12
543.7
518.0
499.6
471.2
533.7
508.0
489.6
461.3
800
800
800
700
800
800
800
700
700
700
600
600
700
600
600
600
559.5
533.1
514.1
484.9
549.6
523.1
504.1
475.0
800
800
800
800
800
800
800
700
700
700
700
600
700
700
600
600
115
115
115
115
60
60
60
60
MCA
—
Minimum Circuit Amps
MOCP —
Maximum Overcurrent Protection
VFD
—
Variable Frequency Drive
Summary of Contents for 30XV140-500
Page 5: ...5 Fig 2 30XV 140 160 180 Std Tier 140 Mid Tier Air Cooled Chiller...
Page 6: ...6 Fig 2 30XV 140 160 180 Std Tier 140 Mid Tier Air Cooled Chiller cont...
Page 7: ...7 Fig 2 30XV 140 160 180 Std Tier 140 Mid Tier Air Cooled Chiller cont...
Page 8: ...8 Fig 3 30XV 140 High Tier 160 180 Mid Tier 200 Std Tier Air Cooled Chiller...
Page 9: ...9 Fig 3 30XV 140 High Tier 160 180 Mid Tier 200 Std Tier Air Cooled Chiller cont...
Page 10: ...10 Fig 3 30XV 140 High Tier 160 180 Mid Tier 200 Std Tier Air Cooled Chiller cont...
Page 11: ...11 Fig 4 30XV 160 180 High Tier 200 Mid Tier Air Cooled Chiller...
Page 12: ...12 Fig 4 30XV 160 180 High Tier 200 Mid Tier Air Cooled Chiller cont...
Page 13: ...13 Fig 4 30XV 160 180 High Tier 200 Mid Tier Air Cooled Chiller cont...
Page 14: ...14 Fig 5 30XV 200 High Tier Air Cooled Chiller...
Page 15: ...15 Fig 5 30XV 200 High Tier Air Cooled Chiller cont...
Page 16: ...16 Fig 5 30XV 200 High Tier Air Cooled Chiller cont...
Page 17: ...17 Fig 6 30XV 225 Std Tier Air Cooled Chiller...
Page 18: ...18 Fig 6 30XV 225 Std Tier Air Cooled Chiller cont...
Page 19: ...19 Fig 6 30XV 225 Std Tier Air Cooled Chiller cont...
Page 20: ...20 Fig 7 30XV 225 Mid Tier Air Cooled Chiller...
Page 21: ...21 Fig 7 30XV 225 Mid Tier Air Cooled Chiller cont...
Page 22: ...22 Fig 7 30XV 225 Mid Tier Air Cooled Chiller cont...
Page 23: ...23 Fig 8 30XV 225 High Tier Air Cooled Chiller...
Page 24: ...24 Fig 8 30XV 225 High Tier Air Cooled Chiller cont...
Page 25: ...25 Fig 8 30XV 225 High Tier Air Cooled Chiller cont...
Page 26: ...26 Fig 9 30XV 250 275 Std Tier Air Cooled Chiller...
Page 27: ...27 Fig 9 30XV 250 275 Std Tier Air Cooled Chiller cont...
Page 28: ...28 Fig 9 30XV 250 275 Std Tier Air Cooled Chiller cont...
Page 29: ...29 Fig 10 30XV 250 275 Mid Tier 300 Std Tier Air Cooled Chiller...
Page 30: ...30 Fig 10 30XV 250 275 Mid Tier 300 Std Tier Air Cooled Chiller cont...
Page 31: ...31 Fig 10 30XV 250 275 Mid Tier 300 Std Tier Air Cooled Chiller cont...
Page 32: ...32 Fig 11 30XV 250 275 High Tier 300 Mid Tier 325 Std Tier Air Cooled Chiller...
Page 33: ...33 Fig 11 30XV 250 275 High Tier 300 Mid Tier 325 Std Tier Air Cooled Chiller cont...
Page 34: ...34 Fig 11 30XV 250 275 High Tier 300 Mid Tier 325 Std Tier Air Cooled Chiller cont...
Page 35: ...35 Fig 12 30XV 300 High Tier 325 Mid Tier Air Cooled Chiller...
Page 36: ...36 Fig 12 30XV 300 High Tier 325 Mid Tier Air Cooled Chiller cont...
Page 37: ...37 Fig 12 30XV 300 High Tier 325 Mid Tier Air Cooled Chiller cont...
Page 38: ...38 Fig 13 30XV 325 High Tier Air Cooled Chiller...
Page 39: ...39 Fig 13 30XV 325 High Tier Air Cooled Chiller cont...
Page 40: ...40 Fig 13 30XV 325 High Tier Air Cooled Chiller cont...
Page 41: ...41 Fig 14 30XV 350 Standard Tier Air Cooled Chiller...
Page 42: ...42 Fig 14 30XV 350 Standard Tier Air Cooled Chiller cont...
Page 43: ...43 Fig 14 30XV 350 Standard Tier Air Cooled Chiller cont...
Page 44: ...44 Fig 15 30XV 350 Mid Tier Air Cooled Chiller...
Page 45: ...45 Fig 15 30XV 350 Mid Tier Air Cooled Chiller cont...
Page 46: ...46 Fig 15 30XV 350 Mid Tier Air Cooled Chiller cont...
Page 47: ...47 Fig 16 30XV 350 High Tier Air Cooled Chiller...
Page 48: ...48 Fig 16 30XV 350 High Tier Air Cooled Chiller cont...
Page 49: ...49 Fig 16 30XV 350 High Tier Air Cooled Chiller cont...
Page 50: ...50 Fig 17 30XV 400 Standard Tier Air Cooled Chiller...
Page 51: ...51 Fig 17 30XV 400 Standard Tier Air Cooled Chiller cont...
Page 52: ...52 Fig 17 30XV 400 Standard Tier Air Cooled Chiller cont...
Page 53: ...53 Fig 18 30XV 400 Mid 450 Standard Tier Air Cooled Chiller...
Page 54: ...54 Fig 18 30XV 400 Mid 450 Standard Tier Air Cooled Chiller cont...
Page 55: ...55 Fig 18 30XV 400 Mid 450 Standard Tier Air Cooled Chiller cont...
Page 56: ...56 Fig 19 30XV 400 High 450 Mid 500 Std Tier Air Cooled Chiller...
Page 57: ...57 Fig 19 30XV 400 High 450 Mid 500 Std Tier Air Cooled Chiller cont...
Page 58: ...58 Fig 19 30XV 400 High 450 Mid 500 Std Tier Air Cooled Chiller cont...
Page 59: ...59 Fig 20 30XV 450 High 500 Mid Tier Air Cooled Chiller...
Page 60: ...60 Fig 20 30XV 450 High 500 Mid Tier Air Cooled Chiller cont...
Page 61: ...61 Fig 20 30XV 450 High 500 Mid Tier Air Cooled Chiller cont...
Page 62: ...62 Fig 21 30XV Split Unit 40A B High 45A B Mid 50A B Standard Tier Air Cooled Chiller...
Page 63: ...63 Fig 21 30XV Split Unit 40A B High 45A B Mid 50A B Standard Tier Air Cooled Chiller cont...
Page 64: ...64 Fig 21 30XV Split Unit 40A B High 45A B Mid 500A B Standard Tier Air Cooled Chiller cont...
Page 65: ...65 Fig 22 30XV Split Unit 45A B High 50A B Mid Tier Air Cooled Chiller...
Page 66: ...66 Fig 22 30XV Split Unit 45A B High 50A B Mid Tier Air Cooled Chiller cont...
Page 67: ...67 Fig 22 30XV Split Unit 45A B High 50A B Mid Tier Air Cooled Chiller cont...
Page 103: ...103 Fig 44 Field Control and Power Wiring...
Page 104: ...104 Fig 44 Field Control and Power Wiring cont...