Fan data

30RY

Minimum available

Nominal available

Maximum available

static pressure*

static pressure

static pressure

Pressure

Flow

Pressure

Flow

Pressure

Flow

Pa

l/s

Pa

l/s

Pa

l/s

017-026

0

2500

100

1940

150

1530

033

0

2920

100

2500

200

1940

040-050

0

4580

150

3890

230

3330

060

0

5560

150

4720

230

4030

070-080

0

6810

150

5830

230

5280

* Operation without duct system

Maximum air entering temperature, °C

30RY

At minimum

At nominal

At maximum

air flow

air flow

air flow

017-026

44

46

47.5

033

44

46

47

040-050

44.5

46

47

060

44.5

46

47

070-080

44.5

46

47

Performance correction factors

30RY

Cooling capacity

Power input

Min. flow

Max. flow*

Min. flow

Max. flow*

017-026

0.98

1.01

1.03

0.97

033

0.98

1.005

1.03

0.98

040-050

0.985

1.005

1.02

0.98

060

0.985

1.005

1.02

0.98

070-080

0.985

1.005

1.01

0.98

* Operation without duct system

Correction factor for the published performances, given at nominal air flow

Accessory suction filter pressure drop

Unit size

Additional pressure drop, Pa

0

2

4

6

8

10

12

14

017/026

033

040/050

060

070/080

Accessory reference number:
30RY-017-033: 30RY-900—002—EE—
30RY-040-080: 30RY-900—012—EE—

Replacement filter reference number:
—KH—12AE-005—EE—

30RY-017-033: quantity: 4
30RY-040-080: quantity: 6

The connection of the return air duct is now very easy, directly
on the air filter accessory.

Filter access for maintenance is ensured by removing the two
Metric screws on the unit side (rear view of the unit).

The cover panel, supplied with a handle, can now be removed.

The filters are attached to each other with a bracket that permits
sliding them into the frames.

10.5.3 - Fan discharge
A square flange is supplied mounted on the unit. An available
standard round flange can easily be installed at the fan discharge,
if the installer prefers the use of a round connection duct.

The unit is supplied with a cover panel on the discharge
side. This panel has to be removed before connection to the
duct system.

30RY-017-033: standard 560 mm diameter fan
30RY-040-080: standard 710 mm diameter fan

It is advisable to make the connection to the duct system with a
flexible collar. If this recommendation is not observed, a lot of
vibration and noise may be transmitted to the building structure.

The unit construction does not permit the support of a duct
weighing more than 10 kg. Non-observance may lead to
damage of the unit.

10.5.4 - Applicable regulations for units used with an air
duct system
Ensure that the return or supply air openings cannot accidentally
be obstructed by panels (for example low return air or opening
of doors).

Unit performances are given for an air-side pressure drop that
is indicated in the Physical Data table.

The three tables that follow contain fan characteristics, maxi-
mum air entering temperatures and performance correction
factors, depending on the air system used with the units.

Summary of Contents for 30RY 017

Page 1: ...Installation operation and maintenance instructions AQUASNAP For the operation of the control please refer to the Pro Dialog Control manual for the 30RA RH 30RY RYH B series Carrier is participating...

Page 2: ...loop volume 12 6 6 30RY unit operating range at full and part load 12 6 7 Pressure drop in the plate heat exchangers 13 7 ELECTRICAL CONNECTION 14 7 1 Power supply 15 7 2 Voltage phase imbalance 15 8...

Page 3: ...tual subcooling 24 12 4 Refrigerant guidelines 25 12 5 Recharging liquid refrigerant 25 12 6 Undercharge 25 12 7 Characteristics of R407C 25 12 8 Electrical maintenance 25 12 9 Condenser coil 26 13 AQ...

Page 4: ...d before operating the unit In certain cases the globe stops are installed on ball valves These valves are factory supplied lead sealed in the open position This system permits isolating and removing...

Page 5: ...ioration and injuries to people Faults and leaks must be repaired immediately The authorized technician must have the responsibility to repair the fault immediately Each time repairs have been carried...

Page 6: ...be trapped between this valve and the expansion device This valve is situated on the liquid line before the filter drier box Do not attempt to repair or recondition any safety devices when corrosion o...

Page 7: ...connections and service operations For the centre of gravity coordinates the position of the unit mounting holes and the weight distribu tion points refer to the certified dimensional drawing supplied...

Page 8: ...s and arrangements are in place and comply with the current European standard Verify that all document for pressure containers certificates name plates files instruction manuals that are required docu...

Page 9: ...location of fixing points weight distribution and coordinates of the centre of gravity refer to the certified dimensional drawings B Install a condensate collection channel around the unit or install...

Page 10: ...070 080 Power circuit Nominal power supply V ph Hz 400 3 50 Voltage range V 360 440 Control circuit supply The control circuit is supplied via the unit mounted transformer Maximum unit power input kW...

Page 11: ...re range 10 C to 46 C class 4K3 altitude 2000 m presence of hard solids class 4S2 no significant dust present presence of corrosive and polluting substances class 4C2 negligible vibration and shock cl...

Page 12: ...vaporator T of 2 8 K must be guaranteed which corresponds to a water flow rate of 0 9 l s per kW 6 5 Water loop volume 6 5 1 Minimum water loop volume The minimum water loop volume in litres is given...

Page 13: ...17 2 30RY 021 3 30RY 026 4 30RY 033 5 30RY 040 6 30RY 050 7 30RY 060 8 30RY 070 9 30RY 080 1 10 100 1000 2000 1 10 1 2 3 4 5 6 7 8 9 6 7 Pressure drop in the plate heat exchangers Pressure drop kPa Wa...

Page 14: ...ections For copper cables use electrolytic copper AMP type cable stiffeners with 6 mm terminal for sizes 017 to 080 30RY X mm Y mm 017 033 1180 761 040 080 190 762 NOTES The 30RY units have only one p...

Page 15: ...isolator switch are designed for the number and type of wires listed in the table below The calculations are based on the maximum machine current see electrical data tables and the standard installati...

Page 16: ...be recommended 10 pH Ideal case pH neutral at 20 25 C 7 pH 8 ATTENTION Charging adding or draining fluid from the water circuit must be done by qualified personnel using air vents and materials suitab...

Page 17: ...n switching the unit off in winter Add ethylene glycol with an adequate concentration to protect the installation up to a temperature of 10 K below the lowest temperature likely to occur at the instal...

Page 18: ...c module are equipped with a flow switch and an internal piping heater Legend Components of the unit and hydronic module 1 Victaulic screen filter 2 Expansion tank 3 Safety valve 4 Available pressure...

Page 19: ...rve to obtain the desired operating point see example for 30RY 080 The pres sure drop reading in the plate heat exchanger is used to control and adjust the nominal system flow rate The pressure drop i...

Page 20: ...ly closing the control valve until you obtain the specific pressure drop that corresponds to the nominal flow rate at the required unit operating point If the system has an excessive pressure drop in...

Page 21: ...ide a removable window on the return air duct to permit maintenance of the air temperature sensor 10 5 2 Air return with accessory filter The suction side connection collar must first be removed Insta...

Page 22: ...ry Filter access for maintenance is ensured by removing the two Metric screws on the unit side rear view of the unit The cover panel supplied with a handle can now be removed The filters are attached...

Page 23: ...ntactor power supply If the pump is not supplied with the unit unit without hydronic module verify that the power input of the field installed pump does not exceed the rating of the standard pump cont...

Page 24: ...heck all heat exchangers and all pipework If water jets are used inside the units e g to clean the coils the lower holes for possible condensate removal must be blocked 12 2 Verification of the refrig...

Page 25: ...specialists Their activities must be overseen and checked by properly trained people To minimise discharge to the atmosphere refrigerants and lubricating oil must be transferred using methods which re...

Page 26: ...4 51 04 28 75 63 67 67 64 10 22 12 27 77 19 5 46 77 51 55 29 64 07 68 02 10 25 22 94 28 56 19 75 47 29 52 05 29 25 64 47 68 39 12 9 Condenser coil We recommend that finned coils are inspected regularl...

Page 27: ...operations please refer to the paragraph on diagnostics and breakdowns of the 30RA RH 30RY RYH B Pro Dialog Plus controls manual IMPORTANT Before each equipment maintenance operation please ensure tha...

Page 28: ...ssors fans and pumps Check the compressor fan and pump winding status Mechanical checks Check the tightening of the fan tower fan compressor and control box fixing bolts Check that no water has penetr...

Page 29: ...mage prevent unit start up Unit is level in its installation Power supply agrees with the unit name plate Electrical circuit wiring has been sized and installed properly Unit ground wire has been conn...

Page 30: ...to 080 3 50 litres nominal kW capacity for air conditioning 30RY 017 to 040 Proper loop volume established Proper loop corrosion inhibitor included litres of Proper loop freeze protection included if...

Page 31: ...this machine Once all checks have been made start the unit in the LOCAL ON position Unit starts and operates properly Temperatures and pressures WARNING Once the machine has been operating for a while...

Page 32: ...persedes order No 13427 76 04 2002 Manufactured by Carrier SA Montluel France Manufacturer reserves the right to change any product specifications without notice Printed in the Netherlands Printed on...

Reviews: