6. Align the slots in the blanket with the suction tube on the

compressor. See Fig. 5.

7. Secure the blanket near suction tube with the hook and

loop strips. See Fig. 5.

8. Wrap the blanket around the compressor terminal box. See

Fig. 6.
For 30MP016 units with compressor insulation, cut out the

sound blanket around the compressor terminal box. The

compressor power leads should be placed outside the

sound blanket.
For 30MP050-071 units, the blanket will not cover the

compressor terminal box. See Fig. 7.

9. Attach the hook and loop strip on the vertical seam to se-

cure the blanket to the compressor. See Fig. 6.

10. For 30MP040,045 units, return control box to its original

position and tighten the 4 control box retaining screws on

each side of the unit.

11. Attach top flap of blanket with the hook and loop strip

while aligning the discharge opening with the discharge

line. See Fig. 6.

a. For units 38APS025-065, 38APD025-060, and

30RAP018-060: All wires pass through top cover

seam.

b. For unit 38APD070-130: ‘B’ Circuit wires pass

through top cover seam. ‘A’ Circuit wires pass under

the blanket.

c. For units 30MP016-045, 30RAP011,016, and

30RAP070-150: All wires pass under the blanket.

Except 30MP016 with compressor insulation as

noted in Step 8.

d. For units 30MP050-071: The wires pass outside the

blanket, the terminal box is outside the blanket, and

there is a cutout for the oil equalizer line. See Fig. 7

for 30MP050-071 units.

12. For 30RAP100-150 units, install the sound blanket cap by

aligning the discharge opening with the discharge line and

attaching the cap with the hook and loop strip to the sound

blanket.

13. Repeat Steps 3 through 12 for installation of sound blanket

to all compressors.

14. Replace the access panel by reversing the procedure in Step

3 or Step 4, if necessary.

15. Restore power.

SLOTTED LATCHES (2)

COMPRESSOR

ACCESS

Fig. 3 — Compressor Access Panel with 2 

Latches — 38APS040,050

a38-7216

BACK – EVAPORATOR END

REMOVE LEFT 

S

IDE

ENCLO

S

URE PANEL

a30-6066

Fig. 4 — Left Side Enclosure Panel —

30MP016-071

Fig. 5 — Align Blanket Slots with Suction Tube

HOOK AND LOOP

STRIPS

COMPRESSOR

DISCHARGE LINE

TERMINAL BOX

BLANKET

SUCTION TUBE

BLANKET SLOT

ALIGNING WITH 

SUCTION TUBE

Reviews: