Physical data — English
30HR,HS UNIT AND COMPRESSOR
UNIT 30HR,HS SIZE
070
080
090
100
110
120
140
160
APPROXIMATE OPERATING
WEIGHT (lb)*
HR
4760
4945
5070
6436
6575
6714
7355
7775
HS
3305
3360
3420
4360
4420
4480
5065
5175
REFRIGERANT (R-22)
OPERATING CHG (lb)†
HR
104
119
129
138
146
154
172
192
HS
15.3
15.3
15.3
21.0
21.0
21.0
27.0
27.0
COMPRESSOR 06E**
(Reciprocating,
Semi-Hermetic,
1750 rpm)
HR
Ckt A 2150 A150 6175 A150 6175 F175 6175 A150 6175 F175 6175 F175 6299 F175 6299 F299
Ckt B
6175
6175
6175
6175 A150 6175 A150 6175 F175 6299 F175 6299 F299
HS
Ckt A 2250 A250 6275 A250 6275 F275 6275 A250 6275 F275 6275 F275 6299 F275 6299 F299
Ckt B
6275
6275
6275
6275 A250 6275 A250 6275 F275 6299 F275 6299 F299
Capacity Control Steps
(see page 31)
6
6
6
8
8
8
8
8
Circuit Split, % Capacity
Ckt A
57
62.5
67
50
55
50
50
50
Ckt B
43
37.5
33
50
45
50
50
50
CONDENSER PART NO. 09RP---
HR
Ckt A
043
054
070
054
070
070
070
084
Ckt B
033
033
033
054
054
070
070
084
REFRIGERANT CONN. (in. ODM)
Liquid Line
HS
Ckt A
7
⁄
8
1
1
⁄
8
1
1
⁄
8
1
1
⁄
8
1
1
⁄
8
1
1
⁄
8
1
1
⁄
8
1
1
⁄
8
Ckt B
7
⁄
8
7
⁄
8
7
⁄
8
1
1
⁄
8
1
1
⁄
8
1
1
⁄
8
1
1
⁄
8
1
1
⁄
8
Discharge Line
Ckt A
1
5
⁄
8
1
5
⁄
8
2
1
⁄
8
1
5
⁄
8
2
1
⁄
8
2
1
⁄
8
2
1
⁄
8
2
1
⁄
8
Ckt B
1
3
⁄
8
1
3
⁄
8
1
3
⁄
8
1
5
⁄
8
1
5
⁄
8
2
1
⁄
8
2
1
⁄
8
2
1
⁄
8
LEGEND
ODM — Outside Diameter Male
*Includes refrigerant operating charge.
†The 30HR unit is shipped with full operating charge; 30HS unit is shipped with holding charge only
(cooler operating charge shown — condenser and interconnecting piping charge must be added for
total system charge).
**Prefix (no. of unloaders): A, F = none; 2, 6 = one.
5