Electrical data
COMPLETE UNIT
VOLT-
AGE
NOMINAL
208/230-3-60
460-3-60
575-3-60
06E COMPRESSOR
USAGE†
Supply
Range*
187-253
414-508
518-632
Circuit A
Circuit B
Compressor Number
UNIT 30
MkW
MCA
ICF
Rec
MFA
MCA
ICF
Rec
MFA
MCA
ICF
Rec
MFA
A1
A2
B1
B2
Fuse
Fuse
Fuse
Amps
Amps
Amps
HR
070
73.4
218
503
250
300
101
249
125
125
93
188
110
125
2150
A150
6175
—
080
82.3
244
529
300
300
114
262
125
150
105
200
125
125
6175
A150
6175
090
91.2
270
612
300
350
127
301
150
150
117
236
150
150
6175
F175
6175
100
103.8
161
529
200
225
140
262
150
175
129
200
150
150
6175
A150
6175
A150
110
112.7
187
669
225
250
153
327
175
175
141
260
150
175
6175
F175
6175
A150
161
200
225
120
121.6
187
695
225
250
166
340
200
200
153
272
175
175
6175
F175
6175
F175
140
155.8
241
816
300
350
112
403
150
150
95
323
110
125
6299
F175
6299
F175
160
190.0
284
1068
350
400
131
519
150
175
106
417
125
150
6299
F299
6299
F299
HS
070
84.7
271
579
300
350
113
282
125
150
102
203
125
125
2250
A250
6275
—
080
95.3
298
606
350
350
128
297
150
150
113
214
125
150
6275
A250
6275
090
105.9
325
706
350
400
143
341
175
175
124
252
150
150
6275
F275
6275
100
120.0
198
618
225
250
157
297
175
200
140
223
150
175
6275
A250
6275
A250
110
130.6
225
779
250
300
172
370
200
200
151
279
175
175
6275
F275
6275
A250
198
225
250
120
141.2
225
806
250
300
187
385
200
225
162
290
175
175
6275
F275
6275
F275
140
176.8
279
892
350
400
121
419
150
175
105
329
125
150
6299
F275
6299
F275
160
212.4
322
1119
400
450
138
528
175
175
120
435
150
150
6299
F299
6299
F299
INDIVIDUAL COMPRESSORS
UNIT 30
COMPRESSOR
208/230-3-60
460-3-60
575-3-60
06E
kW
RLA
LRA
MTA
RLA
LRA
MTA
RLA
LRA
MTA
HR
150
21.5
57
283
88
26
142
40
24
98
33
175
30.4
83
446
128
39
223
56
36
164
50
299
47.5
126
690
196
58
345
90
47
276
73
HS
250
24.7
73
345
112
29
173
45
27
120
40
275
35.3
100
506
156
44
253
68
38
176
57
299
53.1
143
690
222
61
345
95
53
276
82
LEGEND AND NOTES
Two electrical power circuits are required. A separate
entrance and a terminal block are provided for each cir-
cuit. Run 6 wires to unit from disconnect switch, 3 to
each circuit.
For size 110 units, the upper value is circuit A and lower
value is circuit B. For other size units, the value given is
per electrical circuit.
For all unshaded areas: Only 1 power circuit is required,
with a single entrance. Run 3 wires to unit, to a single
terminal block.
ICF
— Maximum Instantaneous Current Flow during starting (the
point in the compressor starting sequence where the
sum of the LRA for the starting compressor plus the RLA
for all running compressors is maximum).
Not for wire
sizing.
kW
— Maximum allowable power input (each compressor).
LRA
— Locked Rotor Amps.
MCA
— Minimum Circuit Amps (for wire sizing); complies with
NEC, Section 430-24 (U.S.A. Standard).
MFA
— Maximum Fuse Amps; 225% of largest compressor RLA
plus 100% of remaining compressor RLA. Size down to
the next standard fuse size.
MkW
— Maximum unit power input.
MTA
— Must Trip Amps (compressor circuit breaker).
NEC
— National Electrical Code (U.S.A.).
Rec Fuse
Amps
— Recommended dual element fuse amps; 150% of larg-
est compressor RLA plus 100% of remaining compres-
sor RLA. Size up to next standard fuse size.
RLA
— Rated Load Amps.
*Units are suitable for use on electrical systems where voltage supplied
to the unit terminals is not below or above the listed range limits.
†Circuits and compressors are numbered from left to right when viewed
from the front of the unit.
NOTES:
1. Maximum incoming wire size for 208/230 v is as follows:
Units 070-090 have one terminal block, 3 wires, 500 kcmil.
Units 100-160 have 2 terminal blocks, 3 wires per block, 500 kcmil.
2. Maximum incoming wire size for 460 and 575 v is as follows:
Wire size maximum is 500 kcmil for units 070-160.
Units 070-120 have one terminal block, 3 wires; units 140 and 160
have 2 terminal blocks, 3 wires per block.
3. Across-the-start is standard at all voltages.
4. Control circuit requires a separate-fused (15 amp), 115-v, single-ph,
60 Hz power supply, or accessory control power transformer.
5. Control circuit MCA is 7.2 and control circuit MFA is 15.
6. Compressor motors on all units are thermally protected by overtem-
perature sensors in the discharge side of the compressor.
7. Maximum allowable phase imbalance is: volts 2%; amps 10%.
8. Use copper, copper-clad aluminum, or aluminum conductors for field
power wiring.
29