background image

29

15 - MAINTENANCE

15.1 - Refrigerant charging - adding charge

IMPORTANT
These units are designed for use with R-134a only. DO NOT
USE ANY OTHER refrigerant in these units.
CAUTION
When adding or removing charge, circulate water through
the condenser (HX) and cooler at all times to prevent
freezing. Freezing damage is considered abuse and may void
the Carrier warranty.
CAUTION
DO NOT OVERCHARGE system. Overcharging results in
higher discharge pressure with higher cooling fluid
consumption, possible compressor damage and higher power
consumption.

15.2 - Indication of low charge on a 30HXC system

NOTE
To check for low refrigerant charge on a 30HXC, several
factors must be considered. A flashing liquid-line sightglass is
not necessarily an indication of inadequate charge. There are
many system conditions where a flashing sightglass occurs
under normal operation. The 30HXC metering device is
designed to work properly under these conditions.

1. Make sure that the circuit is running at a full-load condi-

tion. To check whether circuit A is fully loaded, follow the
procedure described in the Controls manual.

2. It may be necessary to use the Manual Control feature to

force the circuit into a full-load condition. If this is the case,
see the instructions for using the Manual Control feature in
the Controls manual.

3. With the circuit running at full-load, verify that the cooler

leaving fluid temperature is in the range of 6°C ± 1.5.

4. At this condition, observe the refrigerant in the liquid line

sightglass. If there is a clear sightglass, and no signs of
flashing, then the circuit is adequately charged. Skip the
remaining steps.

5. If the refrigerant appears to be flashing, the circuit is

probably low on charge. Verify this by checking the EXV
position (see Controls IOM).

6. If the opening position of the EXD is greater than 60%, and

if the liquid-line sightglass is flashing, then the circuit is
low on charge. Follow the procedure for adding charge.

15.2.1 - To add charge to the 30HXC systems

1. Make sure that the unit is running at full-load, and that the

cooler leaving fluid temperature is in the range of 5.6 -
7.8 °C.

2. At these operating conditions, check the liquid-line

sightglass. If there is a clear sightglass, then the unit has
sufficient charge. If the sightglass is flashing, then check
the EXD Percent Open. If this is greater than 60%, then
begin adding charge.

NOTE
A flashing liquid-line sightglass at operating conditions other
than those mentioned above is not necessarily an indication
of low refrigerant charge.

3. Add 2.5 kg of liquid charge into the evaporator using the

charging valve located on the top of the evaporator.

4. Observe the EXD Percent Open value. The EXD should

begin closing as charge is being added. Allow the unit to
stabilize. If the EXD Percent Open remains above 60%, and
there are still bubbles in the sightglass, add an additional
2.5 kg of liquid charge.

5. Allow the unit to stabilize, and again check the EXD

Percent Open. Continue adding 2.5 kg of liquid refrigerant
charge at a time, and allow the unit to stabilize before
checking the EXD position.

6. When the EXD Percent Open is in the range of 40 - 60%,

check the liquid line sightglass. Slowly add enough
additional liquid charge to ensure a clear sightglass. This
should be done slowly to avoid overcharging the unit.

7. Verify adequate charge by continuing to run at full-load

with 6°C ± 1.5 evaporator leaving fluid temperature. Check
that the refrigerant is not flashing in the liquid-line
sightglass. The EXD Percent Open should be between 40
and 60%. The cooler level indicator should be in the range
of 1.5 - 2.5.

15.2.2 - Indication of low charge on 30GX systems

1. Make sure that the circuit is running at a full-load condition

and that the condensing temperature is 50°C ± 1.5. To
check whether circuit A is fully-loaded, follow the
procedure in the Controls IOM.

2. It may be necessary to use the Manual Control feature to

force the circuit into a full-load condition. If this is the case,
see the instructions for using the Manual Control function
(procedure in the Controls IOM).

3. With the circuit running at full-load, verify that the cooler

leaving fluid temperature is in the range of 6°C ± 1.5.

4. Measure the air temperature entering the condenser coils.

Measure the liquid temperature after the tee where the two
coil liquid lines join. The liquid temperature should be
8.3°C above the air temperature entering the coils. If the
difference is more than this and the sightglass is flashing,
the circuit is uncharged. Proceed to step 5.

5. Add 2.5 kg of liquid charge into the cooler using charging

valve located in the top of the cooler.

6. Allow the system to stabilize and then recheck the liquid

temperature. Repeat step 5 as needed allowing the system
to stabilize between each charge addition. Slowly add
charge as the sightglass begins to clear to avoid over-
charging.

15.2.3 - Space temperature, outdoor air temperature
(optional)
These temperatures are used to measure the temperature of the
space or the outside air temperature respectively for reset
control based on Outside Air or Space Temperature reset
options.

Summary of Contents for 30GX Series

Page 1: ...w Compressor Water Cooled Liquid Chillers and Air Cooled Liquid Chillers 30HXC Nominal cooling capacity 290 1325 kW 30GX Nominal cooling capacity 285 1205 kW 50 Hz Installation operation and maintenan...

Page 2: ...The cover photograph is for illustrative purposes only and is not part of any offer for sale or contract...

Page 3: ...080 190 18 11 2 30HXC 200 285 19 11 3 30HXC 310 375 19 11 4 30GX 082 162 20 11 5 30GX 182 20 11 6 30GX 207 267 21 11 7 30GX 298 358 21 11 8 Piping connections 22 12 ELECTRICAL CHARACTERISTICS 23 12 1...

Page 4: ...t leaks or damage PROVIDE A DRAIN connection in the vent line near each pressure relief device to prevent a build up of condensate or rain water 1 INTRODUCTION Prior to initial start up of the 30HXC a...

Page 5: ...C110 2705 3220 2000 1000 3283 3438 950 30HXC175 30HXC190 3550 3 DIMENSIONS CLEARANCES WEIGHT DISTRIBUTION 3 1 30HXC 080 190 NOTE Refer to the certified dimensional drawings supplied with the unit when...

Page 6: ...be removal Clearances D and E can be either on the left or on the right hand side Water inlet Water outlet Power supply kg total operating weight Clearances required for operation and maintenance 2 4...

Page 7: ...h the unit when designing an installation Water inlet Water outlet Clearances required for evaporator tube removal Clearances can be either on the left or on the right hand side Power supply kg total...

Page 8: ...ing an installation Multiple chiller installation see note 2 SOLID SURFACE AREA SOLID SURFACE AREA Clearances required for evaporator tube removal Clearances can be either on the left or on the right...

Page 9: ...5 C Power input compressor at unit operating limits evaporator water entering leaving temperature 15 C 10 C condenser entering leaving water temperature 40 C 45 C and a nominal voltage of 400 V data g...

Page 10: ...nomized compressor E Economized compressor INOM Average current draw of the compressor at Eurovent conditions MHA Must hold amperes maximum operating current at 360 V LRA Locked rotor current with acr...

Page 11: ...d in the values above N A Not available The 30HXC 080 375 units for high condensing temperatures are directly derived from the standard models Their applicat ion range is the same as that of the stand...

Page 12: ...73 290 326 352 388 449 492 528 582 642 704 776 Maximum power input kW 127 141 154 175 191 207 234 253 286 319 355 380 429 462 506 572 Circuit A kW 193 228 253 286 253 253 286 Circuit B kW 127 127 127...

Page 13: ...he chilled water entering temperature EVAPORATOR RECIRCULATION Compressors Reference Size I nom MHA LRA LRA Y LRA S 1 cp LRA S 2 cp 06NA2146S7N 39 70 95 605 191 220 06NA2174S7N 46 90 120 715 226 260 0...

Page 14: ...hillers The chillers maintain a constant leaving water temperature under all flow conditions For this to happen the minimum flow rate must be higher than the minimum flow given in the table of permiss...

Page 15: ...30HXC 100 30GX 092 102 30HXC 110 30GX 112 122 30GX 132 5 30HXC 120 130 6 30HXC 140 155 30GX 152 162 7 8 9 10 30HXC 175 190 30GX 182 30HXC 200 30GX 207 227 30HXC 230 30GX 247 30HXC 260 285 30GX 267 11...

Page 16: ...6 30HXC 080 090 100 110 30HXC 120 130 30HXC 140 155 30HXC 200 30HXC 230 260 285 30HXC 310 345 375 30HXC 175 190 100 10 1 1 10 100 9 9 Condenser pressure drop curve Water flow rate l s Pressure drop kP...

Page 17: ...nd are complete and undamaged Do not store units in an area exposed to weather because of sensitive control mechanism and electronic devices 10 2 Moving and siting the unit 10 2 1 Moving Do not remove...

Page 18: ...HXC110 30HXC175 30HXC100 30HXC090 30HXC080 13 5 36 39 X Z Y 1 1 2000 mm mini 1200 mm mini 11 LIFTING INSTRUCTIONS 11 1 30HXC 080 190 This diagram is shown for information only Refer to certified drawi...

Page 19: ...0 mm min 1200 mm min 3500 mm min 1200 mm min 11 LIFTING INSTRUCTIONS CONT 11 2 30HXC 200 285 This diagram is shown for information only Refer to certified drawings NOTE When all lifting and positionin...

Page 20: ...X mm 1440 1650 1650 1650 2155 2155 1440 1440 30GX092 30GX102 60 MAX 1 2 2 5 T M X 60 27MINI Y Z 2300 mm min 2000 mm min NOTE When all lifting and positioning operations are finished it is recommended...

Page 21: ...572 6363 Z mm 890 927 890 886 Y mm 1440 1430 1440 1420 30GX207 30GX247 30GX227 30GX267 X mm 2870 3320 2870 3300 60 MAX 1 2 2 5 T M 60 MINI 2300 mm min Y Z 11 LIFTING INSTRUCTIONS CONT 11 6 30GX 207 26...

Page 22: ...vapour barrier 11 8 2 Evaporator and condenser connections The evaporator and condenser are of the multi tube shell and tube type with removable water boxes to facilitate cleaning of the tubes Before...

Page 23: ...ssible 2 and is therefore accepta ble MOTOR 12 ELECTRICAL CHARACTERISTICS The 30HXC 080 190 and 30GX 082 182 have only one power disconnect isolating switch The 30HXC 200 375 and 30GX 207 358 have two...

Page 24: ...Cu 170 1 x 150 XLPE Al 210 30HX 140 1 x 95 XLPE Cu 180 1 x 185 XLPE Al 220 30HX 155 1 x 95 XLPE Cu 180 1 x 240 XLPE Al 225 30HX 175 1 x 120 XLPE Cu 185 1 x 240 XLPE Al 225 30HX 190 1 x150 XLPE Cu 190...

Page 25: ...0 OPT 150 1 x 95 XLPE Cu 170 2 x 120 PVC Al 265 30HXC 120 OPT 150 1 x 120 XLPE Cu 180 2 x 120 XLPE Al 205 30HXC 130 OPT 150 1 x 120 XLPE Cu 160 2 x 120 XLPE Al 210 30HXC 140 OPT 150 1 x 150 XLPE Cu 17...

Page 26: ...o water passes 14 4 Oil separator 30GX In the air cooled units the oil separator is a pressure vessel that is mounted under the outside vertical condenser coils Discharge gas enters at the top of the...

Page 27: ...flow across the motor windings as needed On units equipped with economizers flash gas leaves the top of the economizer and continually flows to the motor windings All refrigerant used for motor cooli...

Page 28: ...V14 EV31 EV33 EV33 EV37 EV32 EV34 EV34 EV38 EV34 EV36 EV36 EV32 EV32 EV33 EV35 EV35 EV31 EV31 EV17 EV17 EV17 EV18 EV18 EV18 EV15 EV15 EV15 EV16 EV16 EV16 EV11 EV11 EV11 EV12 EV12 EV12 EV11 EV11 EV12 E...

Page 29: ...ioned above is not necessarily an indication of low refrigerant charge 3 Add 2 5 kg of liquid charge into the evaporator using the charging valve located on the top of the evaporator 4 Observe the EXD...

Page 30: ...excess oil charge may impair correct unit operation 15 5 Integral oil filter change An integral oil filter in the 06N screw compressor is specified to provide a high level of filtration 3 required for...

Page 31: ...vacuum The switch is a manual reset type that can be reset after the pressure has once again risen above 70 kPa It is critical that the switch be a manual reset type to preclude the compressor from s...

Page 32: ...ere any shipping damage If so where Will this damage prevent unit start up Unit is level in its installation Power supply agrees with the unit nameplate Electrical circuit wiring has been sized and in...

Page 33: ...art chiller if voltage imbalance is greater than 2 Contact local power company for assistance All incoming power voltage is within rated voltage range Check cooler water loop Water loop volume liters...

Page 34: ...control Minimum load select Condenser pump control Loading sequence select Condenser flow switch Lead lag sequence select Condenser water sensors Head pressure control Motormaster select If installed...

Page 35: ......

Page 36: ...03 1999 Supersedes No 13173 76 March 1998 Manufacturer Carrier s a Montluel France Manufacturer reserves the right to change any product specifications without notice Printed in the Netherlands on ch...

Reviews: