background image

26

14 - MAJOR SYSTEM COMPONENTS AND
OPERATION DATA

14.1 - Geared twin screw compressor

• 30HXC and 30GX units use 06N geared twin screw

compressors

• 06NA are used on 30GX (air-cooled condensing application)
• 06NW are used on 30HXC (water-cooled condensing

application)

• Nominal capacities range from 39 to 80 tons. Economized or

non economized models are used depending on the 30HXC
and 30GX unit size.

14.1.1 - Oil Filter
The 06N screw compressor has an oil filter integral in the
compressor housing. This filter is field replaceable.

14.1.2. - Refrigerant
The 06N screw compressor is specially designed to be used in
R134 a system only.

14.1.3 - Lubricant
The 06N screw compressor is approved for use with the
following lubrifiant.
CARRIER MATERIAL SPEC PP 47-32

14.1.4 - Oil Supply Solenoid Valve
An oil supply solenoid valve is standard on the compressor to
isolate the compressor from oil flow when the compressor is
not operating.
The oil solenoid is field replaceable.

14.1.5 - Suction & Economizer Screens
To increase the reliability of the compressor, a screen has been
incorporated as a standard feature into suction and economizer
inlets of the compressor.

14.1.6  - Unloading System
The 06N screw compressor has an unloading system that is
standard on all compressors. This unloading system consists of
two steps of unloading that decrease the compressor capacity
by rerouting partially compressed gas back to suction.

14.2 - Evaporator

30HXC and 30GX chillers use a flooded evaporator. The water
circulates in the tubes and the refrigerant is on the outside in
the shell. One vessel is used to serve both refrigerant circuits.
There is a center tube sheet which separates the two refrigerant
circuits. The tubes are 3/4" diameter copper with an enhanced
surface inside and out. There is just one water circuit, and
depending on the size of the chiller, there may be two or three
water passes. A cooler liquid level sensor provides optimized
flow control.
At the top of the cooler are the two suction pipes, one in each
circuit. Each has a flange welded to it, and the compressor
mounts on the flange.

14.3 - Condenser and oil separator (30HXC)

30HXC chiller use a vessel that is a combination condenser
and oil separator. It is mounted below the cooler. Discharge gas
leaves the compressor and flows through an external muffler to
the oil separator, which is the upper portion of the vessel. It

enters the top of the separator where oil is removed, and then
flows to the bottom portion of the vessel, where gas is
condensed and subcooled. One vessel is used to serve both
refrigerant circuits. There is a center tube sheet which separates
the two refrigerant circuits. The tubes are 3/4" or 1" diameter
copper with enhanced surface inside and out. There is just one
water circuit with two water passes.

14.4 - Oil separator (30GX)

In the air-cooled units, the oil separator is a pressure vessel that
is mounted under the outside vertical condenser coils.
Discharge gas enters at the top of the separator where much of
the oil separates and drains to the bottom. The gas then flows
through a wire mesh screen where the remaining oil is
separated and drains to the bottom.

14.5 - Electronic Expansion Device (EXD)

The microprocessor controls the EXD through the EXV control
module. The EXD will either be an EXV or an Economizer.
Inside both these devices is a linear actuator stepper motor.
High-pressure liquid refrigerant enters the valve through the
bottom. A series of calibrated slots are located inside the orifice
assembly. As refrigerant passes through the orifice, the pres-
sure drops and the refrigerant changes to a 2-phase condition
(liquid and vapor). To control refrigerant flow for different
operating conditions, the sleeve moves up and down over the
orifice, thereby changing effective flow area of expansion
device. The sleeve is moved by a linear stepper motor. The
stepper motor moves in increments and is controlled directly
by the processor module. As the stepper motor rotates, motion
is transferred into linear movement by the lead screw. Through
the stepper motor and lead screws, 1500 discrete steps of
motion are obtained. The large number of steps and long stroke
result in very accurate control of refrigerant flow. Each circuit
has a liquid level sensor mounted vertically into the top of the
cooler shell. The level sensor consists of a small electric
resistance heater and three thermistors wired in series
positioned at different heights inside the body of the well. The
heater is designed so that the thermistors will read
approximately 93.3°C in dry air. As the refrigerant level rises
in the cooler, the resistance of the closest thermistor(s) will
greatly change. This large resistance difference allows the
control to accurately maintain a specified level. The level
sensor monitors the refrigerant liquid level in the cooler and
sends this information to the PSIO-1. At initial start-up, the
EXV position is at zero. After that, the microprocessor keeps
accurate track of the valve position in order to use this infor-
mation as input for the other control functions. It does this by
initializing the EXV’s at startup. The processor sends out
enough closing pulses to the valve to move it from fully open
to fully closed, then resets the position counter to zero. From
this point on, until the initialization, the processor counts the
total number of open and closed steps it has sent to each valve.

14.6 - Economizer

Economizers are installed on 30HXC 190, 285 and 375 and
30GX 182, 267 and 358.
The economizer improves both the chiller capacity and
efficiency as well as providing compressor motor cooling.
Inside the economizer are both a linear EXV stepper motor and
a float valve. The EXV is controlled by the PIC to maintain the

Summary of Contents for 30GX Series

Page 1: ...w Compressor Water Cooled Liquid Chillers and Air Cooled Liquid Chillers 30HXC Nominal cooling capacity 290 1325 kW 30GX Nominal cooling capacity 285 1205 kW 50 Hz Installation operation and maintenan...

Page 2: ...The cover photograph is for illustrative purposes only and is not part of any offer for sale or contract...

Page 3: ...080 190 18 11 2 30HXC 200 285 19 11 3 30HXC 310 375 19 11 4 30GX 082 162 20 11 5 30GX 182 20 11 6 30GX 207 267 21 11 7 30GX 298 358 21 11 8 Piping connections 22 12 ELECTRICAL CHARACTERISTICS 23 12 1...

Page 4: ...t leaks or damage PROVIDE A DRAIN connection in the vent line near each pressure relief device to prevent a build up of condensate or rain water 1 INTRODUCTION Prior to initial start up of the 30HXC a...

Page 5: ...C110 2705 3220 2000 1000 3283 3438 950 30HXC175 30HXC190 3550 3 DIMENSIONS CLEARANCES WEIGHT DISTRIBUTION 3 1 30HXC 080 190 NOTE Refer to the certified dimensional drawings supplied with the unit when...

Page 6: ...be removal Clearances D and E can be either on the left or on the right hand side Water inlet Water outlet Power supply kg total operating weight Clearances required for operation and maintenance 2 4...

Page 7: ...h the unit when designing an installation Water inlet Water outlet Clearances required for evaporator tube removal Clearances can be either on the left or on the right hand side Power supply kg total...

Page 8: ...ing an installation Multiple chiller installation see note 2 SOLID SURFACE AREA SOLID SURFACE AREA Clearances required for evaporator tube removal Clearances can be either on the left or on the right...

Page 9: ...5 C Power input compressor at unit operating limits evaporator water entering leaving temperature 15 C 10 C condenser entering leaving water temperature 40 C 45 C and a nominal voltage of 400 V data g...

Page 10: ...nomized compressor E Economized compressor INOM Average current draw of the compressor at Eurovent conditions MHA Must hold amperes maximum operating current at 360 V LRA Locked rotor current with acr...

Page 11: ...d in the values above N A Not available The 30HXC 080 375 units for high condensing temperatures are directly derived from the standard models Their applicat ion range is the same as that of the stand...

Page 12: ...73 290 326 352 388 449 492 528 582 642 704 776 Maximum power input kW 127 141 154 175 191 207 234 253 286 319 355 380 429 462 506 572 Circuit A kW 193 228 253 286 253 253 286 Circuit B kW 127 127 127...

Page 13: ...he chilled water entering temperature EVAPORATOR RECIRCULATION Compressors Reference Size I nom MHA LRA LRA Y LRA S 1 cp LRA S 2 cp 06NA2146S7N 39 70 95 605 191 220 06NA2174S7N 46 90 120 715 226 260 0...

Page 14: ...hillers The chillers maintain a constant leaving water temperature under all flow conditions For this to happen the minimum flow rate must be higher than the minimum flow given in the table of permiss...

Page 15: ...30HXC 100 30GX 092 102 30HXC 110 30GX 112 122 30GX 132 5 30HXC 120 130 6 30HXC 140 155 30GX 152 162 7 8 9 10 30HXC 175 190 30GX 182 30HXC 200 30GX 207 227 30HXC 230 30GX 247 30HXC 260 285 30GX 267 11...

Page 16: ...6 30HXC 080 090 100 110 30HXC 120 130 30HXC 140 155 30HXC 200 30HXC 230 260 285 30HXC 310 345 375 30HXC 175 190 100 10 1 1 10 100 9 9 Condenser pressure drop curve Water flow rate l s Pressure drop kP...

Page 17: ...nd are complete and undamaged Do not store units in an area exposed to weather because of sensitive control mechanism and electronic devices 10 2 Moving and siting the unit 10 2 1 Moving Do not remove...

Page 18: ...HXC110 30HXC175 30HXC100 30HXC090 30HXC080 13 5 36 39 X Z Y 1 1 2000 mm mini 1200 mm mini 11 LIFTING INSTRUCTIONS 11 1 30HXC 080 190 This diagram is shown for information only Refer to certified drawi...

Page 19: ...0 mm min 1200 mm min 3500 mm min 1200 mm min 11 LIFTING INSTRUCTIONS CONT 11 2 30HXC 200 285 This diagram is shown for information only Refer to certified drawings NOTE When all lifting and positionin...

Page 20: ...X mm 1440 1650 1650 1650 2155 2155 1440 1440 30GX092 30GX102 60 MAX 1 2 2 5 T M X 60 27MINI Y Z 2300 mm min 2000 mm min NOTE When all lifting and positioning operations are finished it is recommended...

Page 21: ...572 6363 Z mm 890 927 890 886 Y mm 1440 1430 1440 1420 30GX207 30GX247 30GX227 30GX267 X mm 2870 3320 2870 3300 60 MAX 1 2 2 5 T M 60 MINI 2300 mm min Y Z 11 LIFTING INSTRUCTIONS CONT 11 6 30GX 207 26...

Page 22: ...vapour barrier 11 8 2 Evaporator and condenser connections The evaporator and condenser are of the multi tube shell and tube type with removable water boxes to facilitate cleaning of the tubes Before...

Page 23: ...ssible 2 and is therefore accepta ble MOTOR 12 ELECTRICAL CHARACTERISTICS The 30HXC 080 190 and 30GX 082 182 have only one power disconnect isolating switch The 30HXC 200 375 and 30GX 207 358 have two...

Page 24: ...Cu 170 1 x 150 XLPE Al 210 30HX 140 1 x 95 XLPE Cu 180 1 x 185 XLPE Al 220 30HX 155 1 x 95 XLPE Cu 180 1 x 240 XLPE Al 225 30HX 175 1 x 120 XLPE Cu 185 1 x 240 XLPE Al 225 30HX 190 1 x150 XLPE Cu 190...

Page 25: ...0 OPT 150 1 x 95 XLPE Cu 170 2 x 120 PVC Al 265 30HXC 120 OPT 150 1 x 120 XLPE Cu 180 2 x 120 XLPE Al 205 30HXC 130 OPT 150 1 x 120 XLPE Cu 160 2 x 120 XLPE Al 210 30HXC 140 OPT 150 1 x 150 XLPE Cu 17...

Page 26: ...o water passes 14 4 Oil separator 30GX In the air cooled units the oil separator is a pressure vessel that is mounted under the outside vertical condenser coils Discharge gas enters at the top of the...

Page 27: ...flow across the motor windings as needed On units equipped with economizers flash gas leaves the top of the economizer and continually flows to the motor windings All refrigerant used for motor cooli...

Page 28: ...V14 EV31 EV33 EV33 EV37 EV32 EV34 EV34 EV38 EV34 EV36 EV36 EV32 EV32 EV33 EV35 EV35 EV31 EV31 EV17 EV17 EV17 EV18 EV18 EV18 EV15 EV15 EV15 EV16 EV16 EV16 EV11 EV11 EV11 EV12 EV12 EV12 EV11 EV11 EV12 E...

Page 29: ...ioned above is not necessarily an indication of low refrigerant charge 3 Add 2 5 kg of liquid charge into the evaporator using the charging valve located on the top of the evaporator 4 Observe the EXD...

Page 30: ...excess oil charge may impair correct unit operation 15 5 Integral oil filter change An integral oil filter in the 06N screw compressor is specified to provide a high level of filtration 3 required for...

Page 31: ...vacuum The switch is a manual reset type that can be reset after the pressure has once again risen above 70 kPa It is critical that the switch be a manual reset type to preclude the compressor from s...

Page 32: ...ere any shipping damage If so where Will this damage prevent unit start up Unit is level in its installation Power supply agrees with the unit nameplate Electrical circuit wiring has been sized and in...

Page 33: ...art chiller if voltage imbalance is greater than 2 Contact local power company for assistance All incoming power voltage is within rated voltage range Check cooler water loop Water loop volume liters...

Page 34: ...control Minimum load select Condenser pump control Loading sequence select Condenser flow switch Lead lag sequence select Condenser water sensors Head pressure control Motormaster select If installed...

Page 35: ......

Page 36: ...03 1999 Supersedes No 13173 76 March 1998 Manufacturer Carrier s a Montluel France Manufacturer reserves the right to change any product specifications without notice Printed in the Netherlands on ch...

Reviews: