Carrier 30GTN015 Installation Instructions Manual Download Page 9

9

Table 3B — Electrical Data — Unit with Factory-Installed Motormaster® I Control

LEGEND

*Units are suitable for use on electrical systems where voltage sup-

plied to unit terminals is not below or above listed minimum and
maximum limits.

NOTE: Never operate a motor where a phase imbalance in supply
voltage is greater than 2%. Use the following formula to determine
the percent voltage imbalance.

Percent Voltage Imbalance

Example: Supply voltage is 240-3-60.

AB = 243 v
BC = 236 v
AC = 238 v 

Determine maximum deviation from average voltage:

(AB) 243 – 239 = 4 v
(BC) 239 – 236 = 3 v
(AC) 239 – 238 = 1 v

Maximum deviation is 4 v. Determine percent voltage imbalance: 

This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.

UNIT

SIZE

30GTN

UNIT

CONTROL CIRCUIT

Voltage

V-Hz (3 Ph)

Supplied*

MCA

MOCP

ICF

Rec Fuse

Size

V-Hz

(Single Ph)

Supplied

MCA and

MOCP

Min

Max

Min

Max

015

208/230-60

187

253

82.2

125

278.4

100

115-60

104

127

30

460-60

414

506

38.3

60

129.3

45

115-60

104

127

30

575-60

518

633

30.8

50

105.6

40

115-60

104

127

30

380-60

418

342

43.9

70

152.8

60

230-60

198

254

15

380/415-50

342

440

51.9

80

181.5

70

230-50

198

254

15

020

208/230-60

187

253

97.4

150

357.4

125

115-60

104

127

30

460-60

414

506

49.6

80

182.3

60

115-60

104

127

30

575-60

518

633

42.0

70

129.6

50

115-60

104

127

30

380-60

418

342

51.1

80

198.8

60

230-60

198

254

15

380/415-50

342

440

63.0

100

231.5

80

230-50

198

254

15

025

208/230-60

187

253

124.7

200

458.4

150

115-60

104

127

30

460-60

414

506

60.7

100

232.3

80

115-60

104

127

30

575-60

518

633

51.5

80

173.6

70

115-60

104

127

30

380-60

418

342

64.7

110

254.8

80

230-60

198

254

15

380/415-50

342

440

71.0

110

261.5

90

230-50

198

254

15

030

208/230-60

187

253

145.5

250

518.4

175

115-60

104

127

30

460-60

414

506

68.7

110

262.3

90

115-60

104

127

30

575-60

518

633

54.0

90

185.6

70

115-60

104

127

30

380-60

418

342

73.6

125

287.8

90

230-60

198

254

15

380/415-50

342

440

90.3

150

353.5

110

230-50

198

254

15

035

208/230-60

187

253

203.0

350

708.6

250

115-60

104

127

30

460-60

414

506

91.1

150

357.4

110

115-60

104

127

30

575-60

518

633

80.7

125

289.0

100

115-60

104

127

30

380-60

418

342

111.1

175

393.7

150

230-60

198

254

15

ICF

Maximum Instantaneous Current Flow during starting
(the point in the starting sequence where the sum of
the LRA for the starting compressor, plus the total
RLA for all running compressors, plus the total FLA for
all running fan motors is maximum).

MCA

Minimum Circuit Amps (complies with National Elec-
trical Code [NEC, U.S.A.], Section 430-24)

MOCP —

Maximum Overcurrent Protection

= 100 x

max voltage deviation from average voltage

average voltage

Average voltage =

243 + 236 + 238

3

=

239 v

% Voltage Imbalance = 100 x

4

239

= 1.7%

IMPORTANT: Contact your local electric utility company
immediately if the supply voltage phase imbalance is more
than 2%.

Summary of Contents for 30GTN015

Page 1: ...h and fire extinguisher nearby when brazing Use care in handling rigging and setting bulky equipment See Tables 1A and 1B for Physical Data INSTALLATION Step 1 Rig and Place the Unit RIGGING Preferred...

Page 2: ...Tube Direct Expansion Net Water Volume gal L 6 8 25 7 9 9 37 5 12 8 48 4 Maximum Design Working Pressure psig kPa Refrigerant Side 235 1620 Water Side 150 1034 WATER CONNECTIONS in Inlet and Outlet 2...

Page 3: ...pe power source with a warning that power must not be turned off except when unit is being serviced The cooler drain connection is at the opposite end from the compressor See Fig 3 5 Insulate the drai...

Page 4: ...b Kg 30GTN015 1640 744 30GTN015C 1732 786 30GTN020 1821 826 30GTN020C 1945 882 50 Hz UNIT Lb Kg 30GTN015 1741 790 30GTN015C 1833 831 30GTN020 1864 846 30GTN020C 1988 902 UNIT A 30GTN015 1219 4 0 30GTN...

Page 5: ...unit is 60 Hz UNIT Lb Kg 30GTN025 2170 984 30GTN025C 2324 1054 30GTN030 2268 1029 30GTN030C 2474 1122 50 Hz UNIT Lb Kg 30GTN025 2193 995 30GTN025C 2347 1065 30GTN030 2332 1058 30GTN030C 2538 1151 LEG...

Page 6: ...nit 2 Dimensions in are in millimeters 3 The approximate operating weight of the unit is 60 Hz UNIT Lb Kg 30GTN035 2965 1345 30GTN035C 3273 1485 LEGEND C Copper Coils COMPR Compressor MTG Mounting NEC...

Page 7: ...lock are 350 kcmil for 30GTN030 035 208 230 3 60 and 30GTN030 230 3 50 units 2 0 AWG for all other units 6 Terminals for field power supply are suitable for copper copper clad aluminum or aluminum con...

Page 8: ...342 51 1 80 198 8 60 230 60 198 254 15 380 415 50 342 440 60 5 100 229 0 80 230 50 198 254 15 025 208 230 60 187 253 124 7 200 458 4 150 115 60 104 127 30 460 60 414 506 60 7 100 229 2 80 115 60 104...

Page 9: ...80 60 418 342 51 1 80 198 8 60 230 60 198 254 15 380 415 50 342 440 63 0 100 231 5 80 230 50 198 254 15 025 208 230 60 187 253 124 7 200 458 4 150 115 60 104 127 30 460 60 414 506 60 7 100 232 3 80 11...

Page 10: ...diagram 5 For GCS accessory remove jumper wire between terminals 5 and 8 on terminal block TB2 6 For part wind start accessory remove gray jumper wire between C A1 C1 and C A1A C1 Time delay relay sho...

Page 11: ...of components HOT GAS BYPASS Hot gas bypass usually is not rec ommended because it results in application of equipment out of its normal design application range However if its use is required the ap...

Page 12: ...ntinue or change at any time specifications or designs without notice and without incurring obligations PC 903 Catalog No 563 068 Printed in U S A Form 30GTN 10SI Pg 12 1201 1 00 Replaces New Book 2 T...

Reviews: