background image

11

Step 5 — Install Accessories

ELECTRICAL — A number of electrical accessories are
available to provide the following optional features (for details,
refer to the Controls, Start-Up, Operation, Service, and
Troubleshooting book):

Energy Management Module (used for any of the fol-
lowing types of temperature reset, demand limit and ice
features):
— 4 to 20 mA leaving fluid temperature reset (requires

field-supplied 4 to 20 mA generator)

— 4 to 20 mA cooling set point reset (requires field-

supplied 4 to 20 mA generator)

— Discrete inputs for 2-step demand limit (requires field-

supplied dry contacts)

— 4 to 20 mA demand limit (requires field-supplied 4 to

20 mA generator)

— Discrete input for Ice Done switch (requires field-

supplied dry contacts)

Chilled fluid flow switch/interlock

Navigator display:
Provides hand-held, mobile capability using easy to read
4-line display. Keypad function is the same as the Scrolling
Marquee module. Features magnet for ‘hands free’ service
of components.

HOT GAS BYPASS — Hot  gas  bypass  usually  is  not rec-
ommended because it results in application of equipment out
of its normal design application range. However, if its use is
required, the appropriate hot gas bypass package may be used.
For installation details, refer to separate instructions supplied
with the accessory package.

Step 6 — Refrigerant Circuit

LEAK TESTING — Units are shipped with complete op-
erating charge of R-22 (see Tables 1A-1B) and should be
under sufficient pressure to conduct a leak test. If there is no
pressure in the system, use standard refrigeration practices to
search for the leak. Repair the leak using good refrigeration
practices. After leaks are repaired, system must be evacuated
and dehydrated prior to recharging with refrigerant.
DEHYDRATION — Refer to Carrier Standard Service Tech-
niques Manual, Chapter 1, Refrigerants, Sections 6 and 7 for
details. Do not use compressor to evacuate system.
REFRIGERANT CHARGE (Refer to Table 1A or 1B) —
Immediately ahead of filter drier in each circuit is a factory-
installed liquid line service valve. Each valve has a 

1

/

4

-in.

Schrader connection for charging liquid refrigerant.

Summary of Contents for 30GTN015

Page 1: ...h and fire extinguisher nearby when brazing Use care in handling rigging and setting bulky equipment See Tables 1A and 1B for Physical Data INSTALLATION Step 1 Rig and Place the Unit RIGGING Preferred...

Page 2: ...Tube Direct Expansion Net Water Volume gal L 6 8 25 7 9 9 37 5 12 8 48 4 Maximum Design Working Pressure psig kPa Refrigerant Side 235 1620 Water Side 150 1034 WATER CONNECTIONS in Inlet and Outlet 2...

Page 3: ...pe power source with a warning that power must not be turned off except when unit is being serviced The cooler drain connection is at the opposite end from the compressor See Fig 3 5 Insulate the drai...

Page 4: ...b Kg 30GTN015 1640 744 30GTN015C 1732 786 30GTN020 1821 826 30GTN020C 1945 882 50 Hz UNIT Lb Kg 30GTN015 1741 790 30GTN015C 1833 831 30GTN020 1864 846 30GTN020C 1988 902 UNIT A 30GTN015 1219 4 0 30GTN...

Page 5: ...unit is 60 Hz UNIT Lb Kg 30GTN025 2170 984 30GTN025C 2324 1054 30GTN030 2268 1029 30GTN030C 2474 1122 50 Hz UNIT Lb Kg 30GTN025 2193 995 30GTN025C 2347 1065 30GTN030 2332 1058 30GTN030C 2538 1151 LEG...

Page 6: ...nit 2 Dimensions in are in millimeters 3 The approximate operating weight of the unit is 60 Hz UNIT Lb Kg 30GTN035 2965 1345 30GTN035C 3273 1485 LEGEND C Copper Coils COMPR Compressor MTG Mounting NEC...

Page 7: ...lock are 350 kcmil for 30GTN030 035 208 230 3 60 and 30GTN030 230 3 50 units 2 0 AWG for all other units 6 Terminals for field power supply are suitable for copper copper clad aluminum or aluminum con...

Page 8: ...342 51 1 80 198 8 60 230 60 198 254 15 380 415 50 342 440 60 5 100 229 0 80 230 50 198 254 15 025 208 230 60 187 253 124 7 200 458 4 150 115 60 104 127 30 460 60 414 506 60 7 100 229 2 80 115 60 104...

Page 9: ...80 60 418 342 51 1 80 198 8 60 230 60 198 254 15 380 415 50 342 440 63 0 100 231 5 80 230 50 198 254 15 025 208 230 60 187 253 124 7 200 458 4 150 115 60 104 127 30 460 60 414 506 60 7 100 232 3 80 11...

Page 10: ...diagram 5 For GCS accessory remove jumper wire between terminals 5 and 8 on terminal block TB2 6 For part wind start accessory remove gray jumper wire between C A1 C1 and C A1A C1 Time delay relay sho...

Page 11: ...of components HOT GAS BYPASS Hot gas bypass usually is not rec ommended because it results in application of equipment out of its normal design application range However if its use is required the ap...

Page 12: ...ntinue or change at any time specifications or designs without notice and without incurring obligations PC 903 Catalog No 563 068 Printed in U S A Form 30GTN 10SI Pg 12 1201 1 00 Replaces New Book 2 T...

Reviews: