Accessory Description and Usage (Listed Alphabetically) -- CONTINUED

11. MotorMaster

r

Low--Ambient Controller

A fan--speed control device activated by a temperature sensor,

designed to control condenser fan motor speed in response to the
saturated, condensing temperature during operation in cooling

mode only. For outdoor temperatures down to --20

_

F (--28.9

_

C), it

maintains condensing temperature at 100

_

F

±

10

_

F (37.8

_

C

±

5.5

_

C).

Usage Guideline:

A MotorMaster

r

Low Ambient Controller or

Low--Ambient Pressure Switch must be used when

cooling operation is used at outdoor temperatures
below 55

_

F (12.8

_

C).

Suggested for all commercial applications.

12. Outdoor Air Temperature Sensor

Designed for use with Carrier Thermostats listed in this

publication. This device enables the thermostat to display the
outdoor temperature. This device also is required to enable special

thermostat features such as auxiliary heat lock out.

Usage Guideline:

Suggested for all Carrier thermostats listed in this
publication.

13. Outdoor Thermostat

An SPDT temperature--actuated switch which turns on
supplemental electric heaters when outdoor air temperature drops

below a user--selected set point.

Usage Guideline:

Electric supplemental heat applications in non--variable

speed indoor units when electric heat staging is desired.

Usage Guideline:

Some local codes may require limiting the heating head
pressure in the vapor line in some applications.

14. Secondary Outdoor Thermostat

An SPDT temperature--actuated switch which turns on third--stage
of supplemental electric heaters when outdoor air temperature

drops below the second--stage set point.

Usage Guideline:

Outdoor thermostat applications where electric heater is

capable of 3--stage operation.

15. Snow Stand

Coated wire rack which supports unit 18 in. (457.2 mm) above
mounting pad to allow for drainage from unit base.

Usage Guideline:

Suggested in the following applications:

Heat pump installations in heavy snowfall areas.
Heat pump installations in snow drift locations.
Heat pump installations in areas of prolonged

subfreezing temperatures.
All commercial installations.

16. Sound Hood

Wraparound sound reducing cover for the compressor. Reduces the

sound level up to 2 dBA.

Usage Guideline:

Suggested when unit is installed closer than 15 ft

(4.57 m) to quiet areas, bedrooms, etc.

Suggested when unit is installed between two houses less

than 10 ft (3.05 m) apart.
Usage Guideline:

Suggested in the following applications:
Heat pump installations in heavy snowfall areas.
Heat pump installations in snowdrift locations.
Heat pump installations in areas of prolonged
subfreezing temperatures.
All commercial installations.

17. Thermostatic Expansion Valve (TXV) Bi--Flow

A modulating flow--control valve which meters refrigerant liquid

flow rate into the evaporator in response to the superheat of the
refrigerant gas leaving the evaporator.

Usage Guideline:

Required in all heat pump applications

18. Time--Delay Relay

An SPST delay relay which briefly continues operation of indoor
blower motor to provide additional cooling after the compressor

cycles off.

Note:

Most indoor unit controls include this feature. For those that

do not, use the guideline below.

Usage Guideline:

Accessory required to meet ARI rating, where indoor

not equipped.

25H

C

S

3C

Summary of Contents for 25HCS3C

Page 1: ...Compressor sound blanket Comfort S System supports Thermidistatt or standard thermostat controls Reliability S Armor Platet coil fin corrosion protection S Front seating service valves S Scroll compr...

Page 2: ...achieve rated capacity and efficiency Installation of this product should follow all manufacturing refrigerant charging and air flow instructions Failure to confirm proper charge and air flow may red...

Page 3: ...allowable total equivalent length is 250 ft 76 2 m The maximum vertical separation is 200 ft 60 96 m when outdoor unit is above indoor unit and 60 ft 18 28 m when the outdoor unit is below the indoor...

Page 4: ...essory for all Carrier electronic thermostats except the non programmable air conditioner version and builder s thermostats It allows the temperature at a remote location outdoors to be displayed on t...

Page 5: ...to keep the lubricant warm during off cycles Improves compressor lubrication on restart and minimizes the chance of liquid slugging Usage Guideline Required in low ambient cooling applications Require...

Page 6: ...ectric heaters when outdoor air temperature drops below the second stage set point Usage Guideline Outdoor thermostat applications where electric heater is capable of 3 stage operation 15 Snow Stand C...

Page 7: ...er than 10 AWG is used consult applicable tables of the NEC ANSI NFPA 70 Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2 Time Delay fu...

Page 8: ...8 DIMENSIONS 25HCS3C...

Page 9: ...1 7 14 6 17 6 20 5 23 4 kW 25HCS324C FA4CN F C 024 25HCS348C FC4DN F B 048 25HCS336C FC4DN F B 036 25HCS360C FC4DN F B 060 BASED ON INDOOR ENT AIR AT 70 F AND AT RATED CFM 25HCS318C FA4CN F C 018 25HC...

Page 10: ...ious examples Wall Wall Wall Wall 24 Service 6 152 4 mm 24 609 6 Service 24 609 6 Service 24 609 6 Service 24 609 6 Service 24 609 6 24 609 6 24 609 6 12 304 8 12 304 8 12 304 8 12 304 8 6 152 4 Note...

Page 11: ...0 80 13 00 24000 8 30 14900 1 3037403 25HCS324C30 FF1ENE030 23400 10 80 13 00 24000 8 40 14900 1 3037406 25HCS324C30 FK4DN B F 003 23800 12 50 15 00 23400 8 80 14100 1 3037404 25HCS324C30 FK4DNF001 23...

Page 12: ...14A 58CV A X 070 12 28400 10 80 13 00 28400 7 70 17100 1 3037418 25HCS330C30 CAR 3017A 58CV A X 090 16 28400 11 00 13 20 28200 7 70 17000 1 3037417 25HCS330C30 CAR 3017A 58MV B C 060 14 28400 10 80 13...

Page 13: ...8 20 21000 1 3037567 25HCS336C30 CAR 3621A 58PH 110 20 34400 11 00 13 00 35000 8 40 21000 1 3037506 25HCS336C30 CAR 4221A 58CV A X 110 20 34400 11 00 13 20 34800 8 30 21000 1 3037503 25HCS336C30 CAR...

Page 14: ...70 23800 1 3037586 25HCS342C30 CAR 4224A 58MV B C 040 14 39500 11 00 13 20 40000 7 70 24200 1 3037587 25HCS342C30 CAR 4224A 58MV B C 120 20 39500 11 00 13 50 40000 7 70 24000 1 3037663 25HCS342C30 CAR...

Page 15: ...3037650 25HCS342C30 CSRH 4812A 58MV B C 100 20 41000 11 20 13 50 40500 8 00 24200 1 3037651 25HCS342C30 CSRH 4812A 58MV B C 120 20 41000 11 20 13 50 40000 8 00 24200 1 3037683 25HCS342C30 CSRH 4812A 5...

Page 16: ...000 8 20 29800 1 3037735 25HCS348C30 CSRH 6012A 58CV A X 090 16 46000 11 20 13 50 46000 8 30 29800 1 3037736 25HCS348C30 CSRH 6012A 58CV A X 110 20 46000 11 20 13 50 46000 8 40 29800 1 3037737 25HCS34...

Page 17: ...70 13 70 2 15 675 72 20 52 10 72 1 31 19 77 10 45 1 46 18 98 10 18 1 62 18 15 9 89 1 80 17 28 9 59 2 00 16 37 9 27 2 21 67 18 64 13 73 1 30 17 93 13 44 1 44 17 19 13 14 1 61 16 42 12 83 1 78 15 60 12...

Page 18: ...0 89 CAR 2414A 1 01 1 01 CAR 2417A 1 01 1 01 CAR 3014A 1 02 1 02 CAR 3017A 1 02 1 02 CNRF 2418A 1 01 1 01 CNRH 2417A 1 01 1 01 CNRH 3017A 1 02 1 02 CNRV 2414A 1 01 1 01 CNRV 2417A 1 01 1 01 CNRV 3014...

Page 19: ...99 0 99 58CV A X 070 12 CNRH 3617A 0 99 0 99 58CV A X 070 12 CNRV 3014A 0 99 0 99 58CV A X 070 12 CSRH 3012A 0 99 0 99 58CV A X 070 12 CSRH 3612A 1 01 1 00 58CV A X 070 12 CAR 3017A 0 99 0 97 58CV A...

Page 20: ...090 16 CNRH 4221A 0 99 0 96 58CV A X 090 16 CNRV 3617A 0 98 0 98 58CV A X 090 16 CSRH 3612A 0 98 0 95 58CV A X 090 16 CSRH 4212A 0 99 0 95 58CV A X 090 16 CAR 3621A 0 98 0 96 58CV A X 110 20 CAR 4221A...

Page 21: ...7 13 37 13 4 13 35 63 35 63 4 55 34 09 34 09 5 01 Cooling Indoor Model Capacity Power Furnace Model FC4DN F B 042 1 00 1 00 CSRH 4812A 1 01 1 03 FC4DN F B 048 1 02 1 01 FK4DN B F 003 0 98 0 96 FK4DN B...

Page 22: ...odel Capa city Power Furnace Model FC4DN F B 048 1 00 1 00 CSRH 6012A 0 98 0 98 FK4DNB006 1 01 0 95 FK4DNF005 0 99 0 95 CAR 4817A 0 94 0 92 58CV A X 090 16 CNRH 4821A 0 96 0 94 58CV A X 090 16 CNRH 60...

Page 23: ...4 60 68 38 37 73 5 01 65 49 36 67 5 47 62 53 35 60 5 98 59 43 34 48 6 54 56 21 33 32 7 14 67 64 95 49 52 4 53 62 36 48 43 4 94 59 68 47 33 5 40 56 94 46 20 5 91 54 09 45 03 6 46 51 12 43 81 7 06 63 6...

Page 24: ...16 96 16 96 1 50 16 39 16 39 1 48 75 525 7 00 6 44 1 24 8 98 8 25 1 32 11 19 10 20 1 40 13 72 12 19 1 49 16 47 14 99 1 61 18 71 18 71 1 70 19 76 19 76 1 74 19 86 19 86 1 74 600 7 15 6 58 1 26 9 14 8 4...

Page 25: ...1 00 0 96 CNRH 3017A 1 00 0 99 CNRV 2414A 1 00 0 96 CNRV 2417A 1 00 0 96 CNRV 3014A 1 00 0 99 CNRV 3017A 1 00 0 99 CSRH 2412A 1 00 0 96 CSRH 3012A 1 00 0 99 CAR 2414A 0 99 0 96 58CV A X 070 12 CAR 301...

Page 26: ...01 58CV A X 070 12 CSRH 3012A 0 98 1 00 58CV A X 070 12 CSRH 3612A 0 96 0 96 58CV A X 070 12 CAR 3017A 0 98 0 99 58CV A X 090 16 CAR 3617A 0 97 0 98 58CV A X 090 16 CNRH 3017A 0 98 0 99 58CV A X 090...

Page 27: ...8CV A X 090 16 CSRH 4212A 0 97 0 95 58CV A X 090 16 CAR 3621A 1 01 1 00 58CV A X 110 20 CAR 4221A 0 99 0 98 58CV A X 110 20 CNRH 3617A 1 01 1 01 58CV A X 110 20 CNRH 4221A 0 99 0 97 58CV A X 110 20 CN...

Page 28: ...RV 4221A 0 99 1 03 58CV A X 110 20 CNRV 4821A 0 99 0 98 58CV A X 110 20 CSRH 4212A 1 00 1 00 58CV A X 110 20 CSRH 4812A 1 00 0 99 58CV A X 110 20 CAR 4224A 0 98 1 01 58CV A X 135 22 CAR 4824A 0 99 0 9...

Page 29: ...6012A 0 98 0 99 CAR 4817A 0 96 0 99 58CV A X 090 16 CNRH 4821A 0 98 1 02 58CV A X 090 16 CNRH 6024A 0 98 1 02 58CV A X 090 16 CSRH 4812A 0 98 1 01 58CV A X 090 16 CSRH 6012A 0 98 1 00 58CV A X 090 16...

Page 30: ...5 67 83 67 83 5 29 68 80 68 80 5 30 2250 26 22 24 12 4 21 31 81 29 23 4 35 37 85 34 51 4 50 44 65 39 66 4 67 52 37 47 66 4 87 59 78 59 78 5 03 64 71 64 71 5 17 64 66 64 66 5 14 75 1750 24 93 22 93 4 2...

Page 31: ...motors will be totally enclosed 1 phase type with class B insulation and permanently lubricated bearings Shafts will be corrosion resistant Fan blades will be statically and dynamically balanced Cond...

Page 32: ...7310 W Morris St S Indianapolis IN 46231 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 25HCS3C 1PD Replaces New Pri...

Reviews: