background image

24VNA6: Installation Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

3

A07588

Fig. 1 – Connecting Tubing Installation

The outdoor unit contains the correct amount of refrigerant charge for

operation  with AHRI  rated  and  factory-approved  smallest  indoor  unit

when connected by 15 ft (4.57 m) of field-supplied or factory accessory

tubing.
Adjust refrigerant charge by adding or removing the charge to/from the

unit  depending  on  lineset  length  and  indoor  unit  as  calculated  and

displayed on the UI. The user interface (UI) calculates required charge

adjustment and total system charge required.  For proper unit operation,

check refrigerant charge using charging information in the Check Charge

section of this instruction.

IMPORTANT: 

Liquid-line  size  is  3/8-in.  OD  for  all  24VNA6

applications including long line applications.

IMPORTANT: 

Always  install  the  factory-supplied  liquid-line  filter

drier. Obtain replacement filter driers from your distributor or branch.

Installation

IMPORTANT: 

Effective January 1, 2015, all split system and packaged

air  conditioners  must  be  installed  pursuant  to  applicable  regional

efficiency standards issued by the Department of Energy.
Specifications for this unit in residential new construction market require

the  outdoor  unit,  indoor  unit  (including  metering  device),  refrigerant

tubing sets, and filter drier, and muffler listed in pre-sale literature. There

can be no deviation. Consult the Service Manual – Air Conditioners and

Heat Pumps Using Puron Refrigerant to obtain required unit changes for

specific applications and for R-22 retrofit.

Step 1 – Check Equipment and Job Site

Unpack Unit

Move to final location. Remove carton taking care not to damage unit. 
This unit employs one louver spacer on each of the four sides to prevent

louver  movement  during  operation.    The  louver  spacers  are  trapped

between the coil surface and louver at the approximate center of each

side (See 

Fig. 2

).  This louver spacer should be present and, if dislodged

during shipment, must be reinstalled before unit is placed into operation.

A11380a

Fig. 2 – Louver Spacer Location

Inspect Equipment

File  claim  with  shipping  company  prior  to  installation  if  shipment  is

damaged or incomplete. Locate unit rating plate on unit corner panel. It

contains information needed to properly install unit. Check rating plate

to be sure unit matches job specifications.

Step 2 – Install on a Solid, Level Mounting Pad

If conditions or local codes require the unit be attached to pad, tie down

bolts should be used and  fastened through knockouts provided in  unit

base pan. Refer to unit mounting pattern in 

Fig. 3

 to determine base pan

size and knockout hole location.

Fig. 3 – Tiedown Knockout Locations

For  hurricane  tie  downs,  contact  distributor  for  details  and  PE

(Professional Engineer) Certification, if required.

CAUTION

!

EQUIPMENT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage.
If  proper  lineset  routing  techniques  are  not  followed,  variable  speed

systems  can  be  susceptible  to  lineset  transmitted  noise  inside  the

dwelling and, in extreme cases, tubing breakage.

INSULATION

SUCTION TUBE

LIQUID TUBE

OUTDOOR WALL

INDOOR WALL

LIQUID TUBE

SUCTION TUBE

INSULATION

CAULK

HANGER STRAP

(AROUND SUCTION

TUBE ONLY)

JOIST

1” (25.4 mm)

 MIN

THROUGH THE WALL

SUSPENSION

UNIT BASE PAN

Dimension in. (mm)

TIEDOWN KNOCKOUT LOCATIONS in. (mm)

A

B

C

35 X 35

(889 X 889)

9–1/8(231.8)

6–9/16 (166.7) 28–7/16 (722.3)

3/4 IN.DIA TIEDOWN

KNOCKOUTS IN BASEPAN

TWO (2) PLACES

C

B

A

VIEW FROM TOP

Summary of Contents for 24VNA6 Series

Page 1: ...thin 24VNA6 11 Step13 System Functions and Major Components 12 Primary Control Module 12 Utility Interface With Infinity Control 12 Infinity Control Green Communications COMM Light 12 Amber Status Lig...

Page 2: ...ration with enough bends to provide 10 ft 3 05 m of total line set length outside the dwelling 3 Ensure that vapor and liquid tube diameters are appropriate for unit capacity 4 Run refrigerant tubes a...

Page 3: ...t and Job Site Unpack Unit Move to final location Remove carton taking care not to damage unit This unit employs one louver spacer on each of the four sides to prevent louver movement during operation...

Page 4: ...ant piping arrangements with equivalent lengths of greater than 80 ft 24 38 m and or when elevation difference between indoor and outdoor unit is greater than 20 ft 6 10 m follow the piping configurat...

Page 5: ...stallation CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation If ANY refrigerant tubing is buried provide a 6 in 152 4 mm vertical rise at s...

Page 6: ...lves see Table 1 Sweat Connections Use refrigerant grade tubing Service valves are closed from factory and ready for brazing After wrapping service valve with a wet cloth braze sweat connections using...

Page 7: ...nate transferred noise If further communication issues exist consider using shielded low voltage wires and only connect shielding to C terminal at end nearest indoor coil Final Wiring Check IMPORTANT...

Page 8: ...Do not attempt to operate the system in heating or cooling mode at this time Mode OFF Vapor and liquid line service valves should be fully closed 2 If the outdoor ambient temperature is between 65 F...

Page 9: ...e text line set and vapor line to choose line set length and vapor line diameter see Fig 17 and Fig 18 After complete press next to advance to next screen 12 If this is a new install i e the ODU is fa...

Page 10: ...ice and without obligations 10 A200035 Fig 17 Select Line Set Length Vapor Line Diameter A200036 Fig 18 Adjust Line Set Length Vapor Line Diameter that is Installed A200037 Fig 19 Charging Mode Select...

Page 11: ...or and outdoor unit prior to servicing unit A200040 Fig 22 Pump Down Setup Screen A200041 Fig 23 Pump Down Status Screen Evacuation and Recovery of Refrigerant from within 24VNA6 Because the 5 ton uni...

Page 12: ...he user interface UI displays the operation mode and fault codes as specified in the troubleshooting section See Table 7 for codes and definitions NOTE Only one code will be displayed on the outdoor u...

Page 13: ...any time specifications and designs without notice and without obligations 13 A200049 Fig 26 Variable Speed Control Board with optional Utility Relay A200044 Fig 27 Primary Control Board Status LED Ye...

Page 14: ...an air cooled device that communicates with the PCM and drives the compressor to the demanded RPM The VFD provides DC voltage to the fan motor and sends a fan RPM signal to the electronics on the fan...

Page 15: ...temporarily Pressure Switch Protection The outdoor unit is equipped with high pressure switch If this switch opens the VFD will lose line power and the compressor and fan motor will not operate The hi...

Page 16: ...ting Locations Failed Thermistor Default Operation Factory defaults have been provided in the event of failure of outdoor air thermistor OAT and or outdoor coil thermistor OCT If the OAT sensor should...

Page 17: ...lash and first long flash is 1 0 second Time between code repeating is 2 5 seconds with LED OFF Codes are easily read from user interface UI or the 5x7 LED display on the PCM EXAMPLE 3 short flashes f...

Page 18: ...ommon C COM Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com SRTN Outdoor Sensor Humidifier Solenoid Valve Remote Room Sensor Y1 J1 Jumper on Control Board Jumper Wire Required for...

Page 19: ...High Temperature Limit 35 11 58 Compressor High Compression Limit 36 15 55 Compressor Low Compression Limit 38 13 53 Compressor Starting Error 54 Compressor No Pump 18 High Differential Pressure Start...

Page 20: ...pressor Underspeed Shutdown 84 11 58 VFD Heat Sink Overtemp Shutdown 85 13 53 DC Under Voltage Shutdown 14 54 DC Over Voltage Shutdown 86 06 46 VFD Communication Error 87 13 53 VFD Initialization Erro...

Page 21: ...8 71 VFD Estimator Malfunction 4 hours 39 53 Fan Start Malfunction 4 hours 39 55 Unexpected Fan Shutdown Malfunction 4 hours 39 58 Fan Motor Malfunction 4 hours 53 41 OST Open Low Temp Duration of Eve...

Page 22: ...nal residential HVAC training resources that help strengthen careers and businesses We believe in providing high quality learning experiences both online and in the classroom Access My Learning Center...

Reviews: