background image

24SCA4, 24SCA5: Installation Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

8

Final Wiring Check

IMPORTANT: 

Check  factory  wiring  and  field  wire  connections    to

ensure terminations are secured properly. Check wire routing to ensure

wires are not in contact with tubing, sheet metal, etc.

Compressor Crankcase Heater

When  equipped  with  a  crankcase  heater,  furnish  power  to  heater  a

minimum of 24 hr before starting unit. To furnish power to heater only,

set thermostat to OFF and close electrical disconnect to outdoor unit. 
A crankcase heater is required if refrigerant tubing is longer than 80 ft.

(24 m) or when outdoor unit is 35 ft. (6 m) below indoor unit.  Refer to

the Residential Piping and Long Line Guideline and Service Manual.

Install Electrical Accessories

Refer  to  the  individual  instructions  packaged  with  kits  or  accessories

when installing.

Start-Up

Follow these steps to properly start up system:

1. After  system  is  evacuated,  fully  open  liquid  and  vapor  service

valves. 

2. Unit is shipped with valve stem(s) front seated (closed) and caps

installed. Replace stem caps after system is opened to refrigerant

flow.  Replace  caps  finger-tight  and  tighten  with  wrench  an

additional 1/12 turn. 

3. Close electrical disconnects to energize system. 
4. Set  room  thermostat  at  desired  temperature.  Be  sure  set  point  is

below indoor ambient temperature.

5. Set  room  thermostat  to  COOL  and  fan  control  to  ON  or AUTO

mode,  as  desired.  Operate  unit  for  15  minutes.  Check  system

refrigerant charge.

3-Phase Monitor

In 3-phase units a small circuit board is factory installed to monitor line

voltage. A  small  led  will  flash  if  a  phase  problem  exists.  See  code

descriptions on monitor.  If LED is flashing, disconnect power to unit

and interchange 2 field-wiring leads on unit contactor.

A00010

Fig. 8 – 3-Phase Monitor Control

(Applies to 3-Phase Units Only)

Sequence of Operation

Turn on power to indoor and outdoor units. Transformer is energized. 
On a call for cooling, thermostat makes circuits R-Y and R-G. Circuit

R-Y  energizes  contactor,  starting  outdoor  fan  motor  and  compressor

circuit. R-G energizes indoor unit blower relay, starting indoor blower

motor on high speed. 
When thermostat is satisfied, its contacts open, de-energizing contactor

and blower relay. Compressor and motors should stop. 
If  indoor  unit  is  equipped  with  a  time-delay  relay  circuit,  the  indoor

blower will run up to 90 seconds to increase system efficiency.

CAUTION

!

UNIT OPERATION AND SAFETY HAZARD

Failure to follow this caution may result in personal injury, equipment

damage or improper operation.
• Do not overcharge system with refrigerant.

• Do not operate unit in a vacuum or at negative pressure.

• Compressor dome temperatures may be hot.

CAUTION

!

PERSONAL INJURY HAZARD

Failure to follow this caution may result in personal  injury.
Wear  safety  glasses,  protective  clothing,  and  gloves  when  handling

refrigerant and observe the following:
• Front seating service valves are equipped with Schrader valves.

Table 5 – Three-Phase Monitor LED Indicator

LED

STATUS

OFF

No call for compressor operation

FLASHING

Reversed  phase

ON

Normal

CAUTION

!

UNIT DAMAGE HAZARD

Failure  to  follow  this  caution  may  result  in  equipment  damage  or

improper operation.
Ensure compressor rotation is correct.  
• 3-phase scroll compressors are rotation sensitive.

• A  flash  LED  on  phase  monitor  indicates  reverse  rotation.    (See

Table 5

)

This will not allow contractor to be energized.
• Disconnect power to unit and interchange 2 field-wiring leads on unit

contactor.

Summary of Contents for 24SCA4

Page 1: ...s patios decks etc where unit operation sound may disturb customer 3 Ensure that vapor and liquid tube diameters are appropriate for unit capacity 4 Run refrigerant tubes with no bends with centerline...

Page 2: ...arance Requirements When installing allow sufficient space for airflow clearance wiring refrigerant piping and service Allow 24 in 610 mm clearance to service end of unit and 48 in 1219 mm above unit...

Page 3: ...emove any grit or debris Insert line set tube ends into service valve tube stubs Apply heat absorbing paste or heat sink product between service valve and joint Wrap service valves with a heat sinking...

Page 4: ...this vacuum depth 1 Vacuum unit to 500 microns 2 When isolating the unit from the pump the pressure shall not rise above 1500 microns in 10 minutes Final Tubing Check IMPORTANT Check to be certain fa...

Page 5: ...a minimum of 15 minutes before checking charge 2 Measure suction pressure by attaching an accurate gage to suction valve service port 3 Measure suction temperature by attaching an accurate thermistor...

Page 6: ...12 44 110 43 108 42 106 41 104 40 102 39 416 114 46 112 44 110 43 108 42 106 41 104 40 427 116 47 114 46 112 44 110 43 108 42 106 41 439 118 48 116 47 114 46 112 44 110 43 108 42 450 120 49 118 48 116...

Page 7: ...rommet and connect leads to control wiring Refer to thermostat Installation Instructions for wiring specific unit combinations see Fig 7 Use No 18 AWG color coded insulated 35 C minimum wire If thermo...

Page 8: ...ll flash if a phase problem exists See code descriptions on monitor If LED is flashing disconnect power to unit and interchange 2 field wiring leads on unit contactor A00010 Fig 8 3 Phase Monitor Cont...

Page 9: ...checked at another time when the both indoor and outdoor temperatures are in a more favorable range NOTE If line length is beyond 80 ft 24 m or greater than 35 ft 11 m vertical separation See Residen...

Page 10: ...any other purpose the following procedures shall be used 1 Safely remove the refrigerant using a recovery pump certified for flammable refrigerants 2 Purge the refrigerant circuit with nitrogen gas 3...

Reviews: