ELECTRICAL DATA
UNIT SIZE---
VOLTAGE,
SERIES
V/PH
OPER VOLTS*
COMPR
FAN
MCA
MIN WIRE
SIZE
{
MIN WIRE SIZE
{
MAX
LENGTH
(FT)
}
MAX
LENGTH
(FT)
}
MAX FUSE**
or
CKT BRK AMPS
MAX
MIN
LRA
RLA
FLA
60
°
C
75
°
C
60
°
C
75
°
C
18--- 30
208/230/1
253
197
40.3
7.7
0.5
10.1
14
14
78
74
15
24--- 31
54.0
10.4
0.75
13.8
14
14
57
54
20
30--- 31
68.0
14.1
1.1
18.7
14
14
42
40
30
36--- 31
77.0
14.4
1.1
19.1
12
12
65
62
30
42--- 30
104.0
19.2
1.4
25.4
10
10
79
75
40
48--- 31
137.0
20.2
1.2
26.4
10
10
76
72
40
60--- 32
141.0
25.3
1.2
32.9
8
8
94
90
50
60--- 33
150.0
22.4
1.2
29.2
8
8
94
90
50
30--- 51
208/230/3
253
197
58.0
9.9
1.1
13.5
14
14
67
64
20
36--- 51
88.0
10.0
1.4
13.9
14
14
65
62
20
42--- 50
88.0
12.8
1.4
17.4
12
12
83
79
25
48--- 51
83.1
13.1
1.2
17.6
12
12
82
78
25
60--- 52
104.0
15.8
1.2
21.0
10
10
110
104
30
60--- 53
123.0
17.3
1.2
22.8
10
10
101
96
35
36--- 61
460/3
506
414
38.0
5.8
0.7
7.9
14
14
230
219
15
42--- 60
44.0
6.0
0.7
8.2
14
14
222
211
15
48--- 61
41.0
6.1
0.6
8.2
14
14
222
211
15
60--- 62
52.0
7.3
0.6
9.7
14
14
187
178
15
60--- 63
55.0
8.4
0.6
11.1
14
14
164
156
15
* Permissible limits of the voltage range at which the unit will operate satisfactorily
{
If wire is applied at ambient greater than 30
˚
C (86
˚
F), consult table 310---16 of the NEC (ANSI/NFPA 70). The ampacity of non---metallic---sheathed cable
(NM), trade name ROMEX, shall be that of 60
˚
C (140
˚
F) conditions, per the NEC (ANSI/NFPA 70) Article 336---26. If other than uncoated (no---plated), 60
or 75
˚
C (140 or 167
˚
C) insulation, copper wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables
of the NEC (ANSI/NFPA 70).
}
Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2%.
** Time---Delay fuse.
FLA
--- Full Load Amps
LRA
--- Locked Rotor Amps
MCA
--- Minimum Circuit Amps
RLA
--- Rated Load Amps
NOTE
: Control circuit is 24---V on all units and requires external power source. Copper wire must be used from service disconnect to unit.
All motors/compressors contain internal overload protection.
A--WEIGHTED SOUND LEVEL (DBA)
UNIT SIZE---VOLTAGE,SERIES
STANDARD
RATING
TYPICAL OCTAVE BAND SPECTRUM (without tone adjustment)
125
250
500
1000
2000
4000
8000
18--- 30
76
53.0
61.5
66.5
69.0
67.0
62.5
56.5
24--- 31
76
53.0
61.5
68.5
69.0
66.0
63.5
60.5
30--- 31
30--- 51
76
51.0
63.0
67.0
69.0
67.0
65.5
62.0
36--- 31
36--- 51
36--- 61
76
53.5
65.0
69.5
70.0
68.5
65.5
61.0
42--- 30
42--- 50
42--- 60
79
60.5
68.5
71.5
75.5
69.5
65.5
66.0
48--- 31
48--- 51
48--- 61
80
51.5
63.5
66.0
76.0
68.0
66.5
63.5
60--- 32/33
60--- 52/53
60--- 62/63
80
53.0
62.5
67.0
72.5
67.5
67.5
66.0
A--WEIGHTED SOUND POWER (DBA) WITH ACCESSORY SOUND HOOD
UNIT SIZE---VOLTAGE,SERIES
STANDARD
RATING
TYPICAL OCTAVE BAND SPECTRUM (without tone adjustment)
125
250
500
1000
2000
4000
8000
18--- 30
73
53.5
62.0
67.5
69.0
67.0
62.0
56.0
24--- 31
74
53.5
61.5
68.5
68.5
66.0
62.5
57.0
30--- 31
30--- 51
73
53.5
62.5
67.0
68.5
66.0
62.5
58.0
36--- 31
36--- 51
36--- 61
76
53.5
65.0
69.5
70.0
68.5
65.5
61.0
42--- 30
42--- 50
42--- 60
78
61.5
68.0
71.5
74.5
68.5
63.0
61.5
48--- 31
48--- 51
48--- 61
79
53.0
63.5
65.0
75.0
66.0
62.0
59.5
60--- 32/33
60--- 52/53
60--- 62/63
76
53.5
61.0
67.0
71.5
64.5
62.5
62.0
24AB
R
3