Table 6 – Accessory Usage

ACCESSORY

REQUIRED FOR LOW---AMBIENT

COOLING APPLICATIONS

(Below 55

F/12.8

_

C)

REQUIRED FOR LONG LINE

APPLICATIONS*

REQUIRED FOR

SEA COAST

APPLICATIONS

(Within 2 miles/3.22 km)

Ball Bearing Fan Motor

Yes

{

No

No

Compressor Start Assist Capacitor and Relay

Yes

Yes

No

Crankcase Heater

Yes

Yes

No

Evaporator Freeze Thermostat

Yes

No

No

Hard Shut---Off TXV

Yes

Yes

No

Liquid Line Solenoid Valve

No

No

No

Motor Master

or Low---ambient Pressure Switch

Yes

No

No

Support Feet

Recommended

No

Recommended

Winter Start Control

Yes

No

No

* For tubing line sets between 50 and 200 ft. (15.24 and 60.96 m) and/or 20 ft. (6.10 m) vertical differential, refer to Residential Piping and Longline Guideline.

{

Additional requirement for Low---Ambient Controller (full modulation feature) MotorMaster

r

Control.

24 VAC HOT

24 VAC COM

R

C

G

W/W1

Y/Y2

R

C

C

A/C

THERMOSTAT

Typical

FAN COIL

AIR

CONDITIONER

G

W2

HEAT STAGE 1

COOL STAGE 1

INDOOR FAN

24 VAC HOT

24 VAC COM

R

C

G

W/W1

Y/Y2

R

C

C

A/C

THERMOSTAT

Typical

FURNACE

AIR

CONDITIONER

Y

G

W

HEAT STAGE 1

COOL STAGE 1

INDOOR FAN

A02326

LEGEND

24-V FACTORY WIRING

24-V FIELD WIRING

FIELD SPLICE CONNECTION

CONTACTOR

C

A97368

Fig. 7 -- Generic Wiring Diagrams

(See Thermostat Installation Instruction

for specific unit combinations)

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

Catalog No: 24ACA4---ACC4---03SI

Replaces: 24ACC4--- 02SI

Summary of Contents for 24AAA5

Page 1: ...y or operation WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Before installing modifying or servicing system main electrical disconnect switch...

Page 2: ...clearance wiring refrigerant piping and service Allow 24 in 609 6 mm clearance to service end of unit and 48 in 1219 2 mm above unit For proper airflow a 6 in 152 4 mm clearance on 1 side of unit and...

Page 3: ...Notes 1 Do not apply capillary tube or fixed orifice indoor coils to these units 2 For Tubing Set lengths between 50 and 200 ft 15 2 and 61 0 m horizontal or 20 ft 6 1 m vertical differential 250 ft 7...

Page 4: ...ature is higher than indicated or reclaim refrigerant if temperature is lower Allow a tolerance of 3_F 1 7_C Units with Indoor Piston Units installed with indoor pistons require charging by the superh...

Page 5: ...2 33 90 32 88 31 86 30 335 98 37 96 36 94 34 92 33 90 32 88 31 345 100 38 98 37 96 36 94 34 92 33 90 32 364 104 40 102 39 100 38 98 37 96 36 94 34 374 106 41 104 40 102 39 100 38 98 37 96 36 384 108 4...

Page 6: ...Allow a tolerance of 3_F 1 7_C Note Indoor dry bulb between 70_F and 80_F 21_C and 27_C Table 4 Required Suction Line Temperature SUPERHEAT TEMP _F SUCTION PRESSURE AT SERVICE PORT PSIG 107 8 112 2 1...

Page 7: ...ower 24v 40va minimum NOTE Use of available 24v accessories may exceed the minimum 40va power requirement Determine total transformer loading and increase the transformer capacity or split the load wi...

Page 8: ...ft 4 57 m Line Set Charge lb kg 24ABB3 24ACC4 24ACA4 C 24AAA5 18 4 10 1 86 4 77 2 16 4 5 2 04 4 87 2 21 24 4 22 1 91 4 20 1 91 4 20 1 91 4 60 2 09 30 4 90 2 22 5 67 2 57 5 67 2 57 5 67 2 57 36 5 00 2...

Page 9: ...ft 6 10 m vertical differential refer to Residential Piping and Longline Guideline Additional requirement for Low Ambient Controller full modulation feature MotorMasterr Control 24 VAC HOT 24 VAC COM...

Page 10: ...ave Puron suction line filter driers in line longer than 72 hours S Do not install a suction line filter drier in liquid line S POE oils absorb moisture rapidly Do not expose oil to atmosphere S POE o...

Reviews: