4

Final Tubing Check

IMPORTANT

: Check to be certain factory tubing on both indoor

and outdoor unit has not shifted during shipment. Ensure tubes are
not rubbing against each other or any sheet metal or wires. Pay
close attention to feeder tubes, making sure wire ties on feeder
tubes are secure and tight.

Installing with Indoor Piston

Air Conditioner Matched with Factory Approved Piston
Indoor

Air conditioners may be installed with piston fan coils as a system

when the air conditioner and fan coil are listed as a system in the

AHRI directory. All rated piston fan coils are shipped with the
appropriate size piston for the equal tonnage air conditioner.

Matching air conditioners with piston indoors of larger tonnage
size requires a TXV.

Air Conditioner Applied as Replacement Component

If the air conditioner is installed as a replacement component in an

existing piston indoor system, the piston size in the indoor unit

should be changed to the size required for the air conditioner which
can be found in the Product Data

CAUTION

!

PRODUCT OPERATION HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
If using a TXV in conjunction with a single--phase

reciprocating compressor, a compressor start capacitor and

relay are required.

Units with Cooling Mode TXV

Units installed with cooling mode TXV require charging by the
subcooling method.

1. Operate unit a minimum of 15 minutes before checking

charge.

2. Measure liquid service valve pressure by attaching an accur-

ate gage to service port.

3. Measure liquid line temperature by attaching an accurate

thermistor type or electronic thermometer to liquid line near
outdoor coil.

4. Refer to unit rating plate for required subcooling temperat-

ure.

5. Refer to Table 2 --

Rating Plate (required) Subcooling Tem-

perature

. Find the point where required subcooling temper-

ature intersects measured liquid service valve pressure.

6. To obtain required subcooling temperature at a specific

liquid line pressure, add refrigerant if liquid line temperature

is higher than indicated or reclaim refrigerant if temperature

is lower. Allow a tolerance of

3

_

F (

1.7

_

C).

Units with Indoor Piston

Units installed with indoor pistons require charging by the

superheat method.
The following procedure is valid when indoor airflow is within

21 percent of its rated CFM.

1. Operate unit a minimum of 15 minutes before checking

charge.

2. Measure suction pressure by attaching an accurate gage to

suction valve service port.

3. Measure suction temperature by attaching an accurate ther-

mistor type or electronic thermometer to suction line at ser-
vice valve.

4. Measure outdoor air

dry bulb temperature with thermo-

meter.

5. Measure indoor air (entering indoor coil) wet--bulb temper-

ature with a sling psychrometer.

6. Refer to Table 3 --

Superheat Charging -- AC Only

. Find

outdoor temperature and evaporator entering air wet--bulb
temperature. At this intersection, note superheat. Where a
dash (----) appears on the table, do not attempt to charge sys-

tem under these conditions or refrigerant slugging may oc-
cur. Charge must be weighted in, adding or removing 0.6

oz/ft of 3/8 liquid line above or below 15 feet (4.6m) re-
spectively.

7. Refer to Table 4 --

Required Suction--Line Temperature

.

Find superheat temperature (from #6 above) and suction
pressure. At this intersection, note suction line temperature.

8. If unit has a higher suction line temperature than charted

temperature, add refrigerant until charted temperature is

reached.

9. If unit has a lower suction line temperature than charted

temperature, reclaim refrigerant until charted temperature is

reached.

10. When adding refrigerant, charge in liquid form into suction

service port using a flow--restricting device.

11. If outdoor air temperature or pressure at suction valve

changes, charge to new suction line temperature indicated

on chart.

12. Optimum performance will be achieved when the operating

charge produces 10

_

F suction superheat at suction service

valve with 95

_

F (35

_

C) outdoor ambient and 80

_

F (27

_

C)

dry bulb (67

_

F / 19

_

C) wet bulb) indoor temperature (DOE

“A” test conditions) at rated airflow.

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

Catalog No: 24ACA4---ACC4---03SI

Replaces: 24ACC4--- 02SI

Summary of Contents for 24AAA5

Page 1: ...y or operation WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Before installing modifying or servicing system main electrical disconnect switch...

Page 2: ...clearance wiring refrigerant piping and service Allow 24 in 609 6 mm clearance to service end of unit and 48 in 1219 2 mm above unit For proper airflow a 6 in 152 4 mm clearance on 1 side of unit and...

Page 3: ...Notes 1 Do not apply capillary tube or fixed orifice indoor coils to these units 2 For Tubing Set lengths between 50 and 200 ft 15 2 and 61 0 m horizontal or 20 ft 6 1 m vertical differential 250 ft 7...

Page 4: ...ature is higher than indicated or reclaim refrigerant if temperature is lower Allow a tolerance of 3_F 1 7_C Units with Indoor Piston Units installed with indoor pistons require charging by the superh...

Page 5: ...2 33 90 32 88 31 86 30 335 98 37 96 36 94 34 92 33 90 32 88 31 345 100 38 98 37 96 36 94 34 92 33 90 32 364 104 40 102 39 100 38 98 37 96 36 94 34 374 106 41 104 40 102 39 100 38 98 37 96 36 384 108 4...

Page 6: ...Allow a tolerance of 3_F 1 7_C Note Indoor dry bulb between 70_F and 80_F 21_C and 27_C Table 4 Required Suction Line Temperature SUPERHEAT TEMP _F SUCTION PRESSURE AT SERVICE PORT PSIG 107 8 112 2 1...

Page 7: ...ower 24v 40va minimum NOTE Use of available 24v accessories may exceed the minimum 40va power requirement Determine total transformer loading and increase the transformer capacity or split the load wi...

Page 8: ...ft 4 57 m Line Set Charge lb kg 24ABB3 24ACC4 24ACA4 C 24AAA5 18 4 10 1 86 4 77 2 16 4 5 2 04 4 87 2 21 24 4 22 1 91 4 20 1 91 4 20 1 91 4 60 2 09 30 4 90 2 22 5 67 2 57 5 67 2 57 5 67 2 57 36 5 00 2...

Page 9: ...ft 6 10 m vertical differential refer to Residential Piping and Longline Guideline Additional requirement for Low Ambient Controller full modulation feature MotorMasterr Control 24 VAC HOT 24 VAC COM...

Page 10: ...ave Puron suction line filter driers in line longer than 72 hours S Do not install a suction line filter drier in liquid line S POE oils absorb moisture rapidly Do not expose oil to atmosphere S POE o...

Reviews: