39TF
Air Flow
(m
3
/h)
Cooling Coil
Rows
ESP (Pa)
80
120
160
200
240
280
320
010
1000
4
0.18
0.18
0.25
0.32
6
0.18
0.25
0.32
0.32
015
1500
4
0.32
0.32
0.32
0.32
0.37
6
0.32
0.32
0.32
0.37
0.45
020
2000
4
0.32
0.32
0.37
0.37
0.45
0.45
6
0.32
0.37
0.37
0.45
0.45
0.55
025
2500
4
0.45
0.55
0.55
0.75
0.75
0.75
6
0.55
0.55
0.75
0.75
0.75
0.75
030
3000
4
0.55
0.75
0.75
0.75
0.75
1.1
1.1
6
0.75
0.75
0.75
0.75
1.1
1.1
1.1
040
4000
4
1.1
1.1
1.1
1.1
1.1
1.1
1.5
6
1.1
1.1
1.1
1.1
1.1
1.5
1.5
050
5000
4
1.1
1.5
1.5
1.5
1.5
2.2
2.2
6
1.5
1.5
1.5
1.5
2.2
2.2
2.2
060
6000
4
1.5
1.5
1.5
1.5
2.2
2.2
2.2
6
1.5
1.5
1.5
2.2
2.2
2.2
2.2
070
7000
4
1.5
1.5
2.2
2.2
2.2
2.2
2.2
6
1.5
2.2
2.2
2.2
2.2
2.2
3.0
080
8000
4
2.2
2.2
2.2
2.2
2.2
3.0
3.0
6
2.2
2.2
2.2
2.2
3.0
3.0
3.0
090
9000
4
2.2
2.2
2.2
2.2
2.2
3.0
3.0
6
2.2
2.2
2.2
2.2
3.0
3.0
3.0
105
10500
4
3.0
3.0
3.0
3.0
3.0
3.0
4.0
6
3.0
3.0
3.0
3.0
3.0
4.0
4.0
120
12000
4
3.0
3.0
3.0
4.0
4.0
4.0
6
3.0
3.0
4.0
4.0
4.0
4.0
135
13500
4
3.0
3.0
4.0
4.0
6
3.0
4.0
4.0
4.0
150
15000
4
4.0
4.0
4.0
5.5
6
4.0
4.0
5.5
5.5
NOTE:
1. This table lists the motor power value of each type of unit under different external static pressures. (Unit: kW)
General Data-39TF-B/D Unit ESP and Power
10
CARRIER
Summary of Contents for 010