Set the Scale Low value to correspond with the minimum value of the process
output in electrical units. For 0-5V, set to 0. For 1-5V, set to 1. For 4-20mA, set
to 4.
Set the Scale High value to correspond with the maximum value of the process
output in electrical units. For 0-5V, set to 5. For 1-5V, set to 5. For 4-20mA, set
to 20.
Set the Range Low value to the minimum temperature (or humidity) that will
correspond with the Scale Low value (default is 0.0).
Set the Range High value to the maximum temperature (or humidity) that will
correspond with the Scale High value (default is 100.0).
6. If an offset (or calibration) is needed, adjust the o.CA parameter accordingly
7. Press and hold the infinity button for 2 seconds to exit to home page
Once all changes are made refer to Section 14 to relock the controllers.