EG320/EG340 USER MANUAL
MAiNtENANcE & PRodUct cARE
10
Troubleshooting
Symptom
Circumstances
Possible Cause
(solution)
Fixture won’t turn on…
…after test button pressed
Sunlight interfering with communications (try again later
in the day)
Too far away (get closer)
Programmer battery dead (replace batteries)
Programmer not aimed at EMS receiver (aim carefully)
Blown battery fuse (check wiring, replace battery fuse)
Fixture wiring problem (check fixture wiring for short/
open circuit)
Fixture won’t turn on…
…at night time
EMS programmed incorrectly (check programmer knob/
switch settings, reprogram EMS)
Blown battery fuse (check wiring, replace battery fuse)
Solar panel shaded, causing drained batteries & low-
voltage disconnect (prune trees, move pole)
Solar panel wiring problem caused drained batteries &
low-voltage disconnect (check SOLAR PANEL wiring)
Fixture wiring problem (check fixture wiring for short/
open circuit)
Fixture turns off…
… in the middle of the night
EMS programmed to run for specific time after dusk.
This may be correct operation. Please check with your
Carmanah distributor.
Solar panel shaded, causing drained batteries & low-
voltage disconnect (prune trees, move pole)
Fixture turns on…
… during the day
EMS not programmed, or programmed incorrectly
(check programmer knob/switch settings, reprogram
EMS)
Solar panel wiring open circuit causing system to think it
is night. Check Solar panel wires & connectors.
Fixture dim…
… during the night
EMS programmed to run for specific time after dusk.
This may be correct operation. Please check with your
Carmanah distributor
Solar panel shaded, causing drained batteries & low
voltage disconnect (prune trees, move pole)
Green light on (night mode)...
… during the day
Solar panel wires not connected properly (check Solar
panel wires & connectors)
Green light flashing (night mode)...
… during the night
Short between battery & Solar panel wiring (check all
wiring)