VMU-C Instruction manual
46
3.2 PLANT CONFIGURATION
Hovering the mouse over “PLANT” will display a drop-down menu consisting of three
items: “COM SETUP” , “DRIVER” and “SETTING”
Plant Configuration Menu
3.2.1 COM SETUP
Hovering the mouse over “COM Setup” will grant access to the page shown below,
relevant to COM1 port according to the relevant RS485 parameters.
The configuration of the “COM 2” port must be carried out during the configuration of the
energy meters / inverters connected to VMU-C.
COM port Setup
Note:
The communication port RS485 (COM 1) is specifically designed for the
communication with the VMU-M belonging to the system and controlled by VMU-C.
Define the following parameters in this page:
-
Baud-rate
(selectable values are: 9600, 19200, 38400 and 115200 bps)
-
Parity
(selectable values are: none, odd or even)
-
Data bits
(selectable values are 8 or 7 bits)
-
Stop bits
(selectable values are 1 or 2 bits)
Press “Save setting” to store data.