RSBT
Troubleshooting
2
Problembehebung
6
Ricerca guasti
11
Défauts
16
Soluciones
21
Fejlfinding
26
Page 1: ...RSBT Troubleshooting 2 Problembehebung 6 Ricerca guasti 11 D fauts 16 Soluciones 21 Fejlfinding 26...
Page 2: ...m 11 12 14 Bypass 21 22 24 Idle ON 11 14 11 12 21 22 Ramping ON 11 14 11 12 21 22 Bypass ON 11 14 11 12 21 24 Alarm ON 11 12 11 14 21 22 Alarms The RSBT includes a number of diagnostics and protection...
Page 3: ...voltage is out of these limits for more than 5 seconds the line voltage out of range alarm will be triggered RSBT40 models have auto adjustable over voltage and under voltage alarm limits that can be...
Page 4: ...Action to recover alarm The alarm will self recover after 5 minutes If the soft starter remains in alarm for more than 5 minutes due to consecutive alarms then a power reset reset of L1 L2 L3 is requi...
Page 5: ...se the RSBT moel is under rated for the load it is controlling Alarm recovery period 5 minutes Consecutive alarms for hard reset 2 Action to recover alarm The alarm will self recover after a period of...
Page 6: ...ng Gr ne LED Position der Relaiskontakte RSBT 45 mm V21 RSBT 120 mm CV0 CVC Alarm 11 12 14 Alarm 11 12 14 berbr ckung 21 22 24 Leerlaufzustand Ein 11 14 11 12 21 22 Anlaufzustand Ein 11 14 11 12 21 22...
Page 7: ...ausgel st RSBT40 Modelle verf gen ber automatisch einstellbare ber und Unterspannungsala rmgrenzen die auch vom Benutzer ge ndert werden k nnen Sofern sie nicht ge ndert werden werden sie automatisch...
Page 8: ...ufeinanderfolgender Alarme l nger als 5 Minuten in Alarm bleibt ist ein Power Reset Reset von L1 L2 L3 f r RSBT40 und Reset von A1 A2 f r RSBT60 Modelle erforderlich Problembehebung berpr fen Sie ob d...
Page 9: ...e sicher dass die Umgebungstemperatur um das Sanftstartger t herum innerhalb der zul ssigen Grenzwerte liegt Anzahl der Blinksignale 8 Alarm Strom anormal bei berbr ckung Alarmbeschreibung Das RSBT mi...
Page 10: ...asen 10 ist Aufeinanderfolgende Alarme f r hartes R CKSETZEN n v Aktion zur Beseitigung des Alarms Sobald die Spannungen an L1 L2 und L3 innerhalb einer Toleranz von 10 liegen beginnt eine Erholungsph...
Page 11: ...mentazione LED verde Posizione contatti rel RSBT 45 mm V21 RSBT 120 mm CV0 CVC Allarme 11 12 14 Allarme 11 12 14 Bypass 21 22 24 Inattivo ON 11 14 11 12 21 22 Rampa ON 11 14 11 12 21 22 Bypass ON 11 1...
Page 12: ...I modelli RSBT40 hanno limiti di allarme di sovratensione e sottotensione regolabili automaticamente che possono essere modificati anche dall utente A meno che non vengano modificati si regoleranno a...
Page 13: ...l allarme L allarme si disattiva trascorsi 5 minuti Se l avviatore statico rimane in allarme per pi di 5 minuti a causa di allarmi consecutivi necessario un ripristino dell alimentazione ripristino di...
Page 14: ...ssimo di partenze h consentito Verificare che la temperatura ambiente dove installato il componente sia entro i limiti ammessi Numero di lampeggi 8 Allarme Corrente non normale durante il bypass Descr...
Page 15: ...te le fasi 10 Allarmi consecutivi che richiedono un RESET completo N A Azione per disattivare l allarme L allarme inizier un auto recupero di 5 minuti dal momento in cui le tensioni su L1 L2 L3 si tro...
Page 16: ...s Etat Alimentation LED verte Position des contacts de relais RSBT 45 mm V21 RSBT 120 mm CV0 CVC Alarme 11 12 14 Alarme 11 12 14 Bipasse 21 22 24 Marche vide ALLUM E 11 14 11 12 21 22 tat acc l ration...
Page 17: ...de tension de ligne hors plage se d clenche Les mod les RSBT40 ont des limites d alarme de surtension et de sous tension auto r glables qui peuvent galement tre modifi es par l utilisateur moins qu i...
Page 18: ...d acquittement d une alarme L alarme est automatiquement acquitt e 5 minutes plus tard Si le d marreur progressif reste en alarme pendant plus de 5 minutes suite des alarmes cons cutives une r initial...
Page 19: ...BT d clenche cette alarme et d sactive la sortie Cette condition peut se produire en cas de surcharge ou de d classement de la version du RSBT par rapport la charge qu il contr le P riode d acquitteme...
Page 20: ...de d fauts Constater le bon serrage des connexions c t secteur et c t charge V rifier la tension aux bornes L1 L2 L2 L3 L1 L3 et constater la pr sence d un ventuel d s quilibre V rifier la r sistance...
Page 21: ...o del rel Estado Alimentaci n LED verde Posici n de contacto del rel RSBT 45 mm V21 RSBT 120 mm CV0 CVC Alarma 11 12 14 Alarma 11 12 14 Bypass 21 22 24 Reposo ON 11 14 11 12 21 22 Rampa ON 11 14 11 12...
Page 22: ...egundos se disparar la alarma por tensi n de alimentaci n fuera de rango Los modelos RSBT40 tienen l mites de alarma de sobrevoltaje y bajo voltaje autoajustables que el usuario tambi n puede modifica...
Page 23: ...a alarma se recuperar autom ticamente despu s de 5 minutos Si el arrancador suave permanece en alarma durante m s de 5 minutos debido a alarmas consecutivas hay que reiniciar la alimentaci n reset de...
Page 24: ...mero especificado de arranques hora Comprobar que la temperatura ambiente del entorno del arrancador est dentro de los l mites N mero de parpadeos 8 Alarma Corriente an mala durante el bypass Descrip...
Page 25: ...eraci n de la alarma 5 minutos M ximo n de reset consecutivos N A Acci n para auto recuperar la alarma La alarma comenzar un periodo de autorecuperaci n de 5 minutos desde el momento que la diferencia...
Page 26: ...Tilstand Forsyning gr n LED Position for rel kontakt RSBT 45 mm V21 RSBT 120 mm CV0 CVC Alarm 11 12 14 Alarm 11 12 14 Bypass 21 22 24 Idle TIL 11 14 11 12 21 22 Rampe TIL 11 14 11 12 21 22 Bypass TIL...
Page 27: ...re end 5 sekunder udl ses netsp nding uden for omr de alarmen RSBT40 modeller har automatisk justerbare over og undersp ndingsalarmgr nser som ogs kan ndres af brugeren Medmindre de ndres justeres de...
Page 28: ...T NDE for lysnettet L1 L2 L3 for at udf re en fuld nulstilling Derved bliver alarmen nulstillet Fejlfinding Kontroller at den rigtige model af RSBT anvendes Kontroller om tilslutningerne til kompresso...
Page 29: ...n med en klemm ler i en hvilken som helst af L1 L2 L3 faserne og kontroller om str mmen er inden for de forventede niveauer Hvis str mmen er h jere end RSBT nominel str m skal du ndre RSBT til en st r...