Specifications are subject to change without notice (14.04.2010)
3
2
x: multiple of AC53a rating, Tx: duration of current surge, F: duty cycle.
RGC
Motor Ratings:
HP (UL508) / kW (IEC60947-4-2) @ 40°C
115 VAC
230 VAC
400 VAC
480 VAC
600 VAC
RGC..20
½HP / 0.18kW 1-½HP / 0.37kW
2HP /
0.75kW
3HP / 1.1kW
3HP / 1.5kW
RGC..30
3/4HP / 0.37kW
2HP /
1.1kW
3HP / 1.5kW
5HP /
2.2kW
5
HP
/ 3.7kW
Output specifications
RGC..20..
RGC..30..
Rated operational current
AC-51 rating @ Ta=40°C
20 AAC
30 AAC
AC-53a rating @ Ta=40°C
5 AAC
10 AAC
Number of starts (x:6, Tx:6s, F:50%) at 40˚C
2
30
30
Min. operational current
150 mAAC
250 mAAC
Rep. overload current -
UL508: T
AMB
=40°C, t
ON
=1s, t
OFF
=9s, 50cycles
60 AAC
84 AAC
Maximum transient surge current (I
TSM
)
325 Ap
600 Ap
Maximum off-state leakage current
3 mA
3 mA
I²t (10ms)
Typical
525 A²s
1800 A²s
Crititcal dv/dt (@ Tj = 40°C)
1000 V/us
1000 V/us
Output Power Dissipation
Current Derating
0W
3W
6W
9W
12W
15W
18W
21W
24W
27W
30W
33W
RGC1..20
Load Current (AAC)
Po
w
er
Di
ss
ip
at
io
n
(W
)
RGC1..30