range (displaying and blinking of the measured value or displaying of the
“EEE”/ “-EE” message).
Note: by selecting this function the “SE.t”, “HYS” parameters are not
active.
do : down/low alarm set-point. The relay will be activated when the
measured value goes below the set-point value.
uP : up/high alarm set-point. The relay will be activated when the
measured value goes over the set-point value.
d.do : alarm set-point similar to “do”, but with alarm inhibition eventually
present when LDI35 is switched on. The control starts only after the first
condition of non-alarm has been signalled.
uP.L : up/high alarm set-point with latch function.
The alarm functions as per “uP”, but the alarm can be reset only manually when
the
key is pressed for at least 5 seconds during the measuring phase.
do.L : down/low alarm set-point with latch function. The alarm functions
as per “do” and can be reset only manually when the
key is pressed
for at least 5 seconds during the measuring phase.
SEt : value of the alarm set-point to be programmed within the following
range: Lo.
≤
SEt
≤
Hi.
HYS : programming of the hysteresis value of the set-point. The
hysteresis is a numerical value included within the range: 0
≤
HYS
≤
1999/9990 and represents the difference between the value of the ON
alarm status and the value of the OFF alarm status. The hysteresis
modifies the value of the OFF alarm status not only with regards to the