Essential information
EM24 W1 - Instruction manual | CARLO GAVAZZI Controls SpA
EM24 W1 - Instruction manual | CARLO GAVAZZI Controls SpA
Essential information
Measurement management
Easy connection
If the “Measure” parameter is set to A (easy connection), for the calculation of the active energy the power is always integrated, both in the case of imported
and exported power . The current direction does not affect the measurement. If the “Measure” parameter is set to B (without easy connection), both the active
imported and exported are available.
Average value calculation (dmd)
The system calculates the average value of electrical variables in a set integration interval.
Dmd values are available on display only. The dmd interval is automatically set equal to the transmission interval and it is not synchronized with the transmission
interval.
Communication
Frames
The frames are packages of messages sent by EM24 containing the variables measured. The variables and their encoding included in the frame depend on the
type of frame selected:
Frame 1
Variable
Data Format
Engineering unit
DIF
[hex]
VIF
[hex]
VIFE#1
[hex]
VIFE#2
[hex]
VIFE#3
[hex]
Total imported active energy
32 bit integer
Wh*100
04
05
Error flag
8 bit integer
01
FD
17
Frame 2
Variable
Data Format
Engineering unit
DIF
[hex]
VIF
[hex]
VIFE#1
[hex]
VIFE#2
[hex]
VIFE#3
[hex]
Total imported active
energy
32 bit integer
Wh*100
04
05
Total imported reactive
energy
32 bit integer
kVarh*0.1
04
FB
82
75
Total exported reactive
energy
32 bit integer
kVarh*0.1
04
FB
82
F5
3C
Imported active power
32 bit integer
Watt*0.1
04
2A
Error flag
8 bit integer
01
FD
17
Frame 3
Variable
Data Format
Engineering unit
DIF
[hex]
VIF
[hex]
VIFE#1
[hex]
VIFE#2
[hex]
VIFE#3
[hex]
Total imported active
energy
32 bit integer
Wh*100
04
05
Total imported reactive
energy
32 bit integer
kVarh*0.1
04
FB
82
75
Total exported reactive
energy
32 bit integer
kVarh*0.1
04
FB
82
F5
3C
Imported active power
32 bit integer
Watt*0.1
04
2A
Imported reactive power
32 bit integer
Var
04
FB
14
Exported reactive power
32 bit integer
Var
04
FB
94
3C
Summary of Contents for EM24 W1
Page 2: ...EM24 W1 Three phase energy analyzer USER MANUAL ...
Page 19: ...EM24 W1 Analizzatore di energia trifase MANUALE D USO ...
Page 36: ...EM24 W1 Dreiphasen Energieanalysator BETRIEBSANLEITUNG ...
Page 53: ...EM24 W1 Analyseur d énergie triphasé MANUEL D EMPLOI ...
Page 71: ...EM24 W1 Analizador de energía trifásica MANUAL DE USUARIO ...
Page 88: ...EM24 W1 Trefaset energianalyseapparat BRUGERMANUAL ...