8
EM24 M1/M2 use
EM24 M1/M2 - Instruction manual | CARLO GAVAZZI Controls SpA
Step
Action
Button
6
In the
EnE PrES
page, set
YES
7
Confirm operation
Setting a parameter
Example procedure: how to set
P int. ti
=30 and save changes.
Step
Action
Button
1
Power on the energy analyzer
2
Press the joystick for at least 3 seconds
3
In the
PASS?
page, select the correct password (default 0)
4
Confirm operation
5
Scroll pages until
P int. ti
6
Enter the editing mode
7
Select 30
8
Confirm operation
9
Scroll pages until
End
to exit
Summary of Contents for EM24 M1
Page 2: ...EM24 M1 M2 Three phase energy analyzer USER MANUAL...
Page 17: ...EM24 M1 M2 Analizzatore di energia per sistemi trifase MANUALE UTENTE...
Page 32: ...EM24 M1 M2 Dreiphasen Energieanalysator BETRIEBSANLEITUNG...
Page 47: ...EM24 M1 M2 Analyseur d nergie triphas MANUEL D EMPLOI...
Page 62: ...EM24 M1 M2 Analizador de energ a trif sico INSTRUCCIONES DE USO...
Page 77: ...EM24 M1 M2 Trefaset energianalyseapparat BRUGERMANUAL...