ADVANCED PROGRAMMING
USEr:
(APPLiCAt” d only) it links an ID code (from 1 to 9999) to the
user of the displayed consumption (three 1-phase independent users by
instrument).
SELECtor:
it allows selecting the variables combination (page) to be
displayed according to the knob position (see fig.2); SELEC. 1 (2,3, LoC): it
selects the knob position (1, 2, 3 o
); PA.1 (36): it selects the page number
to be displayed (from No. 1 to 36 see TAB 3). If the page relevant to the cur-
rent position of the knob is not availbale for the required application, the
instrument will display the first page available according to the list in table 3.
SYS:
it allows selecting the electrical system. 3P.n: 3-phase unbalan-
ced with or without neutral; 3P.I: 3-phase balanced with or without neu-
tral 2P: 2-phase; 1P: single phase.
Ut rAtio:
VT ratio (0.1 to 6000). Example: if the connected VT primary
is 5kV and the secondary is 100V, the VT ratio to be set is 50 (that is
5000/100).
Ct rAtio:
CT ratio (0.1 to 60.00k). Example: if the connected CT pri-
mary is 3000A and the secondary is 5A, the CT ratio is 600 (that is:
3000/5).
P int.ti:
it is the integration time used to calculate the demanded
powers (Wdmd, VAdmd). The selectable range is between 1 and 30 minu-
tes.
diG in 1 / diG in 2 / diG in 3:
(“I3” option only) it allows defining the
digital inputs function: rEM: for reading the digital input status by means
of serial communication; SYnC: dmd calculation synchronisation; tAr:
multi-tariff management (see also Tab. 6); GAS: gas metering; Cold:
cold water metering; Hot: hot water metering; kWh + Hot: distant heating
(kWh) meters. PrESCAL.1 (or 2 or 3): it sets the weight of each pulse
(from 0.1 to 999.9 m
3
or kWh per pulse). Note: the digital inputs have to
be set with different modes among them, in case they are used for GAS,
CoLd o HoT kWh+ Hot.
FiLtEr.S:
it allows selecting the operating range of the digital filter as %
of the full scale values (1 to 100). Only in case of applications F, G and H.
FiLtEr.Co :
it allows selecting the filtering coefficient (from 1 to 32).
The higher the coefficient, the higher is the stability and the updating time
of the measurement.
AddrESS :
(“SI” option only) it allows selecting the serial address of
the instrument (from 1 to 247). bAudrAtE: it allows selecting the baud
rate (9.600 or 4.800 baud).
diG out. 1 / diG out. 2
(“01”, R2 or 03) it allows selecting the digital out-
puts function. PuLS: pulse output selection (the pulse weight is to be set too)
(kWh/kvarh per pulse from 0.001 to 10.00); tESt: activated on the pulse out-
put when “YES” is selected. In the further menu program the simulated power
value (kW or kvar) is corresponding to a pulse frequency proportional to it and
based on the “PULSEou.1/2/3”. The test is active until you exit from this menu.
AL: alarm output (this function is active only in case of application C, E, G and
H), selection of the variable to be controlled (Ph.AL: phase sequence alarm),
and deactivation setpoints “on AL” and “off AL”, the delay on activation “t dEL”
and the output status in normal condition, “nE” if normally energised or “nd”
if normally de-energised, are to be set too). rEM: it allows the remote control
of the digital output.
EnE t.rES:
it allows the reset of all the total counters.
End:
it allows exiting the programming mode by pressing the joy-
stick in direction 1 (see fig. 1). Joystick directions 4 and 5 allow brow-
sing the main menu again.
PROGRAMMAZIONE AVANZATA
USEr:
(solo “APPLiCAt” d) associa un codice identificativo (da 1 a
9999) all’utente del consumo visualizzato (3 utenti monofase indipenden-
ti per strumento).
SELECtor:
selezione combinazione variabili (pagina) di visualizzazio-
ne da associare alla posizione del selettore frontale (fig. 2); SELEC. 1 (2,
3, LoC): seleziona la posizione del selettore (1, 2, 3 o
); PA.1 (36): sele-
ziona la pagina da visualizzare (da No. 1 a 36 vedere TAB 3). Se la pagi-
na associata alla relativa posizione del selettore non è disponibile per l’ap-
plicazione richiesta, lo strumento visualizzerà la prima pagina disponibile
secondo l’elenco riportato in tab. 3.
SYS :
sistema elettrico: 3P.n: trifase sbilanciato con o senza neutro,
3P.I: trifase bilanciato con o senza neutro, 2P: bifase, 1P: monofase.
Ut rAtio :
rapporto TV (da 0,1 a 6000).
Esempio:
se il primario del TV
connesso è di 5kV e il secondario è di 100V il rapporto di TV corrispon-
de a 50 (ottenuto eseguendo il calcolo: 5000/100).
Ct rAtio :
rapporto TA (da 0,1 a 60,00k).
Esempio:
se il primario del
TA ha una corrente di 3000A e il secondario di 5A, il rapporto TA corri-
sponde a 600 (ottenuto eseguendo il calcolo: 3000/5).
P int.ti :
tempo di integrazione per il calcolo della potenza media:
selezionare il tempo desiderato da 1 a 30 minuti.
diG in 1 / diG in 2 / diG in 3 :
(solo con opzione “I3”) funzione
11
10
09
08
07
06
05
ITALIANO
17
16
15
14
13
12
11
10
09
08
07
06
05
ENGLISH
ingressi digitali: rEM: per la remotazione dello stato degli ingressi digita-
li; SYnC: sincronizzazione; tAr: tariffazione (Tab. 6); GAS: contatore gas;
Cold: contatore acqua fredda; Hot: contatore acqua calda; kWh + Hot:
teleriscaldamento (kWh). PrESCAL.1 (o 2 o 3): impostazione peso impul-
si (da 0,1 a 999,9 m
3
o kWh per impulso). Nota: nel caso di utilizzo per
GAS, CoLd o HoT kWh+ Hot, gli ingressi digitali devono essere imposta-
ti con modalità differenti tra loro.
FiLtEr.S :
campo di intervento del filtro digitale espresso in % del
valore di fondo scala (da 1 a 100). Solo per applicazioni F, G e H.
FiLtEr.Co :
coefficiente di filtraggio da 1 a 32. Aumentando il coeffi-
ciente aumenta la stabilità e il tempo di assestamento dei valori visualiz-
zati.
AddrESS :
(solo con opzione “SI”) indirizzo seriale: da 1 a 247.
bAudrAtE: velocità di trasmissione dati (9.600; 4.800 bit/s).
diG out. 1 / diG out. 2 / diG out. 3:
(solo con opzione “O1, R2 o O3”)
funzione uscita digitale: PuLS: come uscita impulsi, seleziona il peso del-
l’impulso (kWh/kvarh per impulso da 0,001 a 10,00); tESt: attivo su usci-
ta impulsi con selezione YES. Nel menù successivo impostare il valore di
potenza (kW o kvar) simulata a cui corrisponderà una frequenza degli
impulsi ad essa proporzionale in base a “PULSE.ou 1/2/3”, la funzione è
attiva finché si rimane nel menù. AL: come allarme (funzione attiva solo
per le applicazioni C, E, G e H), seleziona la variabile da controllare (Ph.AL:
allarme sequenza fase), le soglie “on AL” (attivazione) e “off AL” (disatti-
vazione) il ritardo all’attivazione, da 0 a 255s, “t dEL” e lo stato dell’usci-
15
14
13
12
ta a riposo “nE” normalmente eccitata o “nd” normalmente diseccitata.
rEM: permette il controllo in modo remoto dell’uscita digitale.
EnE t.rES:
azzeramento di tutti i contatori totali.
End :
per tornare al modo misura premere il joystick in direzione 1 (vedere figu-
ra 1), o in direzione 4-5 per restare nel menù di programmazione.
PROGRAMACIÓN AVANZADA
USEr (sólo “APPLiCAt” d):
vincula un código ID (de 1 a 9999) al usuario
del consumo visualizado (tres usuarios monofásicos independientes por ins-
trumento).
SELECtor:
permite seleccionar la combinación de variables (página) a visua-
lizar, según la posición del interruptor (ver fig. 2); SELEC. 1 (2, 3, LoC): seleccio-
na la posición del interruptor (1, 2, 3 o
); PA.1 (36): selecciona el número de
página a visualizar (desde 1 a 36, ver TAB 3). Si la página relativa a la posición
actual del selector no está disponible para la aplicación deseada, el instrumento
visualizará la primera página disponible según la lista de la tabla 3.
SYS:
Permite seleccionar el sistema eléctrico. 3P.n: trifásico desequi-
librado con o sin neutro; 3P.1: trifásico equilibrado con o sin neutro; 2P:
bifásico; 1P: monofásico.
Ut rAtio:
relación del trafo de tensión VT (0,1 a 6000).
Ej.
: si el prima-
rio del trafo conectado es 5kV y el secundario es 100V, la relación del
trafo de tensión es 50 (es decir, 5000/100).
08
07
06
05
ESPAÑOL
17
16
Ct rAtio:
relación del trafo de intensidad CT (0,1 a 60,00k).
Ej.:
si el
primario del trafo conectado es 3000A y el secundario es 5A, la relación
del trafo de intensidad es 600 (es decir, 3000/5).
P int.ti:
es el tiempo de integración usado para calcular las potencias deman-
dadas (Wdmd, VAdmd). El rango seleccionable está entre 1 y 30 minutos.
diG in 1 / diG in 2 / diG in 3 (sólo opción “I3”):
permite definir la fun-
ción de las entradas digitales: rEM: para lectura del estado de la entrada
digital mediante el puerto de comunicación serie; SYnC: cálculo de la sin-
cronización dmd; tAr: gestión multitarifa (ver también Tab. 6); GAS: medi-
ción de gas; Cold: medición de agua fría; Hot: medición de agua caliente;
kWh+Hot: lectura remota de calefacción (kWh). PrESCAL.1 (ó 2 ó 3): fija el
valor de cada pulso (de 0,1 a 999,9m
3
o kWh cada pulso). Si las entradas
digitales son empleadas para medir: GAS, agua fría, agua caliente o cale-
facción remota cada entrada digital debe fijarse con una función diferente.
FiLtEr.S :
permite seleccionar el rango de funcionamiento del filtro digital
como % del valor a fondo de escala (1 a 100). Solo para aplicaciones: F, G, H.
FiLtEr.Co :
permite seleccionar el coeficiente de filtrado (de 1 a 32).
Cuanto mayor sea el coeficiente, mayor es la estabilidad y el tiempo de
actualización de la medida.
AddrESS (sólo opción “SI”):
permite seleccionar la dirección serie del instru-
mento (de 1 a 247). bAudrAtE: permite seleccionar los baudios (9.600 ó 4.800).
diG out. 1 / diG out. 2 / diG out. 3 (sólo opciones “O1, R2 o O3”):
per-
mite seleccionar la función de las salidas digitales. PuLS: selección de salida
15
14
13
12
11
10
09
de pulsos, hay que fijar también el valor del pulso (kWh/kvarh por pulso de
0,001 a 10,00); tESt: activado en la salida de pulsos cuando se selecciona
“YES”. En el siguiente programa del menú, el valor de potencia simulado (kW
o Kvar) se corresponde a una frecuencia de pulso proporcional y basado en
“PULSE ou. 1/2/3”. El test está activo hasta que se sale de este menú. AL:
selección salida de alarma (esta función está activa sólo en el caso de las apli-
caciones C, E, G y H), selección de la variable a controlar (Ph.AL: alarma de
secuencia de fase) activación y desactivación de los puntos de consigna “on
AL” y “off AL”, retardo a la activación “tdEL” (de 0 a 255 segundos) y estado
de las salidas en condición normal, hay que fijar también “nE” si es normal-
mente activada o “nd” si es normalmente desactivada. rEM: permite el control
remoto de la salida digital.
EnE t.rES:
permite la puesta a cero de todos los contadores totales.
End:
permite salir del modo de programación presionando el joystick
en dirección 1 (ver fig. 1). Las direcciones 4 y 5 del joystick permiten ir
de nuevo al menú principal.
17
16
T
he menus availability depends on the “APPLiCAt” selection.
La presenza dei menù è in funzione della selezione
“APPLiCAt”.
La disponibilidad de los menús depende de la selección
“APPLiCAt”.
TAB 6
diG in
tAr
diG in 1 diG in 2
1
off
off
2
off
on
3
on
off
4
on
on
TAB 7
A
B, C
D
E, F, G, H
PASS ?
PASS ?
PASS ?
PASS ?
CnG_PASS
CnG_PASS
CnG_PASS
CnG_PASS
Colour
Colour
APPLicat
APPLicat
APPLicat
APPLicat
USEr
SELECtor
SELECtor
diG in 1-2
diG in 1-2
AddrESS
AddrESS
AddrESS
AddrESS
TAB. 5
Type / Tipo / Tipo
1st line / 1a linea / 1a línea
2nd line / 2a linea / 2a línea
3rd line / 3a linea / 3a línea
Meter information - Informazione strumento - Info
equipo
Firmware release - Revisione firmware - Versión del
firmware
Year of production- Anno di produzione - Año de pro-
ducción
Meter information - Informazione strumento - Info
equipo
Pulse LEd - LEd impulsi - LED pulsos
Number of kWh per pulse - Numero di kWh per impul-
so - Numero de kWh para pulso
Meter information - Info strumento - Info equipo
System (1-2-3-phase) - Sistema (1-2-3-fasi) -Sistema
(1-2-3 fases)
Connection (2-3-4-wire)- Connessione (2-3-4-fili) -
Conexión (2-3-4 hilos)
dmd (time) - dmd (tempo) - dmd (tiempo)
Meter information (AV5-6) - Info strumento (AV5-
6) - Info equipo
CT ratio - Rapporto TA - Trafo de Intensidad
Meter information (AV5-6) - Info strumento (AV5-
6) - Info equipo
VT/PT ratio - Rapporto TV - Trafo de Tensión
In case of alarm output - In caso di uscita allarme -
En caso de salida de alarma
Alarm output 1 or 2 status- Stato allarme 1 o 2 -
Estado de alarma 1 o 2
Set-point value - Valore della soglia - Valor del punto
de consigna
Variable type - Variabile allarmata - Variable de alarma
In case of pulse output - In caso di uscita impulsi -
En caso de salida de pulsos
Pulse output 1 or 2 variable link (kWh/kvarh) -
Variabile associata all’uscita 1 o 2 (kWh/kvarh) -
Variable conectada a la salida 1 o 2 (kWh/kvarh)
Output pulse weight (kWh-kvarh / pulse) -
Peso dell’impulso (kWh-kvarh / impulso) -
Valor del pulso (kWh-kvarh / pulso)
In case of communication port - Con porta di comu-
nicazione - Con puerto de comunicación
Serial port - Porta seriale - Puerto serie
Address - Indirizzo - Dirección
RS485 status (RX-TX) - Stato della RS485 (RX-TX) -
Estado RS485 (RX-TX)